Burnham boiler error codes are not one list. Cast iron ES2, Series 2e and Series 3 boilers flash Err and StA numbers on the IQ control; Alpine and K2 condensing boilers show numbered soft and hard lockouts on a Sage2.X touchscreen; first generation Alpines flash E and b codes. Identify the control, then read the number.
Which Burnham control is showing the code: Err and StA, a red touchscreen, or a flashing E?
U.S. Boiler Company, maker of Burnham residential boilers (manuals here), uses three code systems:
- IQ control: an LED readout inside the door of ES2, Series 2e and Series 3 gas cast iron boilers, alternating “Err” or “StA” with a number. The IQ Option Panel below has its own Err 1 to 9.
- Sage2.X touchscreen: Alpine (ALP080B to ALP285B) and K2. The screen turns red and shows a numbered soft or hard lockout.
- MCBA display on early Alpines (manual 101602-01, 2008): “9” alternating with “b” plus two digits is a soft lockout; a flashing “E” plus two digits is a hard lockout.
The E01 to E08 lists on some contractor sites (E04 low water cutoff, E08 gas valve) match none of the seven Burnham manuals we read.
Burnham code 4, 5, 15, 32, 56 or 57: what does the number mean on your control?
Each control reads the number differently: Err 32 on an ES2 is a sensor failure, lockout 4 on an Alpine is a 210°F supply limit, and E 32 on a 2008 Alpine is a shorted return sensor.
| No. | IQ control: ES2, Series 2e, Series 3 | Alpine and K2, Sage2.X | Alpine, MCBA (2008) |
|---|---|---|---|
| 4 | Err 4: Flame Current Lower than Threshold | Hard lockout 4: supply high limit, over 210°F | E 04: Power failure occurred after lockout |
| 5 | Main control: not listed. Option Panel Err 5: Limit Output OFF in ON State | Alpine hard lockout 5: DHW high limit; K2: not listed | E 05: internal control failure |
| 15 | StA 15: Waiting for Limit to Close (a status) | Soft lockout 15: return temp higher than supply | E 15: internal control failure |
| 32 | Err 32: Temperature Sensor Failure | Not listed | E 32: shorted return temperature sensor |
| 56 | Err 56: Damper Failed to Close | Not listed | Not listed |
| 57 | Err 57: Flame Rod Shorted to Burner Ground | Not listed | Not listed |
What do Err and StA codes mean on ES2, Series 2e and Series 3 boilers?
Err numbers are faults; StA numbers are the sequence. StA 1, 4, 6, 7 and 8 (standby through running) are normal; 13 is soft lockout, 14 hard lockout, 20 damper failed to open.
IQ control Err codes (ES2 103780-13 and Series 3 103796-11)
| Err | Burnham’s wording | Owner check / technician job |
|---|---|---|
| 4 | Flame Current Lower than Threshold | Tech reads FLA, services pilot |
| 6, 23 | Flame Sensed Out of Normal Sequence; During Pre-purge | Tech tests, replaces valve |
| 18 | Electronics Failure | Cycle power once |
| 32 | Temperature Sensor Failure | Tech reseats P7, then sensor, then control |
| 35 | Duplicate Zone Alarm | Zone panel instructions |
| 55 | Damper Failed to Open | Owner: look for a blocked damper blade |
| 56 | Damper Failed to Close | Tech runs 24 VAC test below |
| 57 | Flame Rod Shorted to Burner Ground | Tech dries pilot, raises setpoint |
| 58, 59, 61 | AC Line Frequency; Line Voltage Error; Line Voltage Unstable | Tech checks supply voltage |
| 60 | Thermostat Input Higher than Threshold | Owner: check wires are tight |
| 63 | Soft Lockout, Recycles Exceeded | Tech: spark, pilot, main flame checks |
| 64 | Soft Lockout, Internal Failure | Tech cycles power, damper unplugged |
| 89 | Communication Lost | Tech checks wiring |
A soft lockout (StA 13) clears itself once the cause is gone and a one hour delay ends; the ES2 manual allows an earlier restart with rSt in Adjustment Mode or by cycling power. A failed light gets a 5 minute retry delay with no retry limit; a flame lost while running gets a 10 second recycle, and six losses in a row give Err 63.

Burnham boiler error 56 or 57: is it the vent damper or the flame rod?
Err 56 is the vent damper circuit; Err 57 is the pilot flame rod touching ground.
For Err 56, Burnham’s isolation test runs with the code displayed: remove the call for heat and measure 24 VAC between terminal P6-5 and ground. If present, unplug the damper harness and measure again. Voltage still there means a bad control; none means the damper or harness.
For Err 57, the ES2 manual says the short “can result from excessive flue gas condensation” and lists drying the pilot, raising the setpoint and checking the ignition wire. Condensate from a boiler running too cool is the same problem our condensate pump guide and boiler not working checklist touch on.
What do Alpine and K2 lockout numbers mean on the Sage2.X touchscreen?
A soft lockout restarts by itself; a hard lockout needs the Reset button on the Active Fault display or on the Sage2.X control. Tap the blinking Help button to see which. Alpine keeps the last 10 lockouts in its Lockout History.
Alpine lockouts (103448-12, ALP080B to ALP285B)
| No. | Type | Burnham’s wording |
|---|---|---|
| 1 | Soft | Anti Short Cycle, a normal delay |
| 2 | Soft | Safety limit open: condensate float, thermal link, burner door thermostat, air pressure switch or high limit |
| 3 | Soft | External limit or LWCO open |
| 7 to 10 | Soft | Return, supply, DHW or stack sensor shorted or open |
| 11 | Soft | Ignition failure after 5 tries |
| 13 | Soft | Flame rod shorted to ground |
| 14, 16 | Soft | Supply to return rise too high; supply rose too quickly |
| 15 | Soft | Return higher than supply for 75 seconds |
| 17 | Soft | Waiting for blower speed, normal |
| 4, 5, 6 | Hard | Supply over 210°F; DHW over setpoint; stack over 204°F |
| 12 | Hard | Flame detected out of sequence |
| 18, 19 | Hard | Blower light off or purge rate proving failed |
| 20 to 22 | Hard | Safety or modulation parameter invalid or unverified |
| 23, 24 | Hard | 24VAC voltage low/high; Fuel Valve Error |
| 25 to 27 | Hard | Hardware, internal or unknown fault |
The K2WT manual (107672-03) uses the same numbers with four changes: no lockout 1, 5 or 9; lockout 2 is the external limit or LWCO and 3 the blocked flue/inlet switch; 28 or 53 and 54 are air proving switch faults; and the stack lockout is 214°F.
Burnham’s Alpine user manual (103449-01) gives owners one check: look for a bee’s nest or ice at a ground level vent terminal; the burner “should ignite approximately 30 seconds after the blockage is removed.”
On lockout 2 or 3, open Limit String Status. The Alpine manual warns that limits are wired in series, so every limit downstream of the open one also blinks. Chase the first blinking icon, not the last.

Why does a K2 lock out at 214°F flue temperature when an Alpine stops at 204°F?
Both current controls act in three steps: slow the blower, force a recycle, then hard lockout 6. They simply use different flue limits. The first Alpine control had one step, E 52 at 230°F.
Alpine water limits step the same way: 190°F slows the blower, 200°F recycles, 210°F is lockout 4. A supply to return rise above 43°F slows it, 53°F recycles, 63°F shuts down. Repeated lockout 4 or 14 means poor flow, so check the circulator first.
What did E and b codes mean on the first Alpine boilers?
The 2008 Alpine’s MCBA control, per the archived manual, used its own numbers: b 08 pressure switch circuit open, b 18 and b 19 supply or return above 200°F, b 24 return higher than supply; E 00 flame when there should be none, E 02 flame failure after 5 tries, E 03 gas valve error, E 12 low water cut-off open, E 31 to E 40 shorted or open sensors, E 52 flue over 230°F. E 05 to E 07, E 11, E 13 to E 17, E 44 and E 60 are internal control failures.
How many resets before you call, and what will the technician measure?
One reset after fixing a visible cause is reasonable; a second identical lockout is a service call. The Alpine user manual (103449-01) states “There are no user serviceable parts on this boiler.”
Owner checks outside the burner: a blank IQ display means no 120 VAC, so check the breaker; “tt” should read “on” during a call for heat; the gauge should sit near the 12 psi cold fill in our boiler pressure guide; a yellow LWCO light means low water, per our low water cutoff guide.
The technician reads flame current (FLA), 24 volts at the gas valve, inlet gas pressure against the rating plate and sensor resistance. Stop and call if you smell gas, see soot near the burner (a potential carbon monoxide hazard, per the Alpine manual) or find a tripped flame rollout switch, which the ES2 manual says must be replaced before the boiler runs again.
Burnham Independence and MegaSteam boilers run on other controls, and our steam heating explainer covers their pressure limits. Other brands number faults their own way, as the Weil-McLain error codes show.
Frequently asked questions
Where is the Burnham Alpine reset button?
On Sage2.X Alpines, a hard lockout is reset with the Reset button on the Active Fault display or on the Sage2.X control itself, per manual 103448-12. Early MCBA Alpines use the RESET button on the display. Soft lockouts restart by themselves once the cause clears.
How do I find Burnham boiler age by serial number?
No U.S. Boiler Company document we read publishes a serial number decoder. The ES2 manual tells owners to “provide model number and serial number when seeking information and support,” so call U.S. Boiler Customer Service at (717) 481-8400 with both numbers from the rating label.
Is there a Burnham boiler date code?
No Burnham manual we read defines a date code in the serial number. The date matters because the U.S. Boiler residential warranty covers stainless steel boilers such as Alpine and K2 for five years from the date of original manufacture, so ask the maker to confirm that date from the serial number.
What does Burnham boiler error code 5 mean?
On a Sage2.X Alpine, hard lockout 5 is the DHW high limit: the DHW sensor read above setpoint. On an ES2 or Series 3 IQ Option Panel, Err 5 is “Limit Output OFF in ON State.” On a 2008 MCBA Alpine, E 05 is an internal control failure.
How we researched this
In November 2026 we read seven Burnham and U.S. Boiler Company documents and compiled every code from them: ES2 (103780-13), Series 2e (109443-05) and Series 3 (103796-11) for the IQ control; Alpine (103448-12) and K2WT (107672-03) for Sage2.X; the Alpine user manual (103449-01); and an archived 2008 Alpine manual (101602-01). We also read the K2FT, K2WTC, ESC and MPO-IQ manuals and the warranty. No code meaning comes from blogs. We found no Burnham boiler sold as “Sure-Fire.”
Sources
- U.S. Boiler Company. “ES2 I&O manual, 103780-13.” https://s3-us-west-2.amazonaws.com/catsy.782/ES2+IO+Manual.pdf. Accessed November 2026.
- U.S. Boiler Company. “Series 3 I&O manual, 103796-11.” https://s3-us-west-2.amazonaws.com/catsy.782/Series+3+IO.pdf. Accessed November 2026.
- U.S. Boiler Company. “Series 2e I&O manual, 109443-05.” https://s3-us-west-2.amazonaws.com/catsy.782/Series+2e+IO+Manual.pdf. Accessed November 2026.
- U.S. Boiler Company. “Alpine I&O manual, 103448-12.” https://s3-us-west-2.amazonaws.com/catsy.782/Alpine+IO+Manual.pdf. Accessed November 2026.
- U.S. Boiler Company. “Alpine User’s Information Manual, 103449-01.” https://s3-us-west-2.amazonaws.com/catsy.782/Alpine+Residential+User+Manual.pdf. Accessed November 2026.
- U.S. Boiler Company. “K2WT I&O manual, 107672-03.” https://s3-us-west-2.amazonaws.com/catsy.782/K2WT+IO+Manual.pdf. Accessed November 2026.