Weil McLain Boiler Error Codes by Boiler Line, With the Reset Location for Each

Technician checking a wall-hung boiler control while tracing weil mclain boiler error codes in a basement

Weil McLain boiler error codes differ by line. Ultra Series 1 and 2 show E and b numbers, AquaBalance shows A and F numbers, GV90+ and CGa Series 3 flash lights, and Ultra Series 3 and 4, Evergreen, ECO Tec and CGa Series 4 show worded faults. Identify the line first, then the code.

What the boiler showsBoiler lineWhere the reset isE or b plustwo digitsUltra Series 1, 2RESET buttonon display panelA or F plustwo digitsAquaBalance Series 2reset button,hold 1 secondWords on a screen,red in lockoutUltra S3, S4, WM97+,Evergreen, ECO TecMANUAL RESETon the screenWords on atwo-line displayCGa Series 4, CGi Series 5Enter, arrow toYES, EnterFlashing LEDs,no screenGV90+, CGa Series 3Cut 120 V power;GV90+ waits 45 sBlank screenNo code: power or displayBreaker, switch,then fuses
Compiled by The HVAC Brief from Weil-McLain manuals.

Which Weil-McLain line do you have, and where is its reset?

Match the display to a row: failed ignition is E 02 on an Ultra Series 2, A01 on an AquaBalance, and POWER plus FLAME on a GV90+. Navien works the other way, keeping most of its Navien boiler error codes the same from one US boiler line to the next.

Boiler line What a fault looks like Where the reset is
Ultra Series 1, 2 E plus two digits: hard lockout. 9, then b plus digits: soft RESET button on the display panel
Ultra Series 3, 4, WM97+, Evergreen, ECO Tec Words; Ultra flashes red to gray in lockout Manual reset screen on the display
CGa Series 4, CGi Series 5 Words on a two-line display Enter, arrow to YES, Enter
AquaBalance Series 2 A (hard) or F (soft) plus a number Front panel reset button, 1 second
GV90+ Series 2 LED combinations 120 V off or all thermostats down; wait 45 seconds
CGa Series 3 LED combinations Remove 120 V over 2 seconds, or wait 1 hour

Compiled by The HVAC Brief from the manuals and pages under Sources.

GV90+ Figure 92 says more than 2 seconds without 120 VAC clears a lockout, while the instructions beside it say 45 seconds, so use 45. The CGa Series 3 manual describes no control reset button, only one on the spill switch.

What do Ultra Series 1 and 2 codes mean, including E02, E04 and E28?

E 02 means ignition failed through 5 attempts, E 04 means voltage was lost after a lockout or incoming power fluctuated, and E 28 means the blower is not running.

Code Weil-McLain’s meaning
E 00 Flame detected on startup
E 02 Ignition failed through 5 attempts
E 03 Ignition or gas valve electrical problem
E 04 Voltage lost after lockout, or AC fluctuations on incoming power
E 05, 06, 08, 09, 11, 15, 44, 60, 61 Internal control, display or EEPROM failure
E 07 Gas valve relay error
E 12 External limit open, terminals 6 and 8
E 13, 14 Sensor problem (14: supply)
E 18, 19 Outlet (18) or return (19) water above 210°F
E 25 Temperature rise above 58°F
E 28 Blower not running
E 29 Blower signal not zero when it should be
E 30 Rise over 58°F, occurred 20 times
E 31, 32; E 36, 37 Outlet, return sensor short (31, 32) or open (36, 37)
E 52 Flue temperature exceeded 225°F
E 65 Blower signal too low

E 02 checks start with the gas valve, inlet pressure, vent and electrode. E 04 can be the supply: Weil-McLain names brown-outs and generators and offers relay 383-500-021.

Soft lockout b codes (these clear on their own)
Code Meaning
b 18, 19 Outlet or return above 203°F
b 24, 25 Return hotter than supply; outlet rose too quickly
b 26 External limit open, terminals 6 and 7
b 29, 65 Blower signal not zero; waiting for blower
b 30 Rise over 45°F; hard lockout after 20 tries
b 35, 40, 52 Flue sensor short, open; flue above 216°F

Why does the same fault name carry different limits on Ultra, Evergreen and ECO Tec?

Each control has its own thresholds: FLUE TEMP TOO HIGH forces a manual reset above 225°F on an Ultra Series 4 but above 220°F on Evergreen 110, 155 and ECO Tec Series 2. Rinnai varies by line in a similar way, reusing one code number for different faults, so the Rinnai boiler error codes start with the model on the rating label.

Fault Ultra Series 4 Evergreen 110, 155 ECO Tec Series 2
FLUE TEMP TOO HIGH Manual above 225°F Manual above 220°F Manual above 220°F
TEMP RISE TOO QUICKLY 2°F per second 2°F per second 10°F per second
Supply over return 58°F; 30 second wait 58°F; 30 second wait 60°F; waits step 2.5 to 6.5 minutes
LOW WTR CUTOFF OPEN Over 1 second: manual Over 5 seconds: manual Open: manual

WM97+ uses the 225°F flue limit; the 2008 Ultra Series 3 manual lists 220°F. Repeating temperature faults point to piping and the circulator. Ultra Series 4 AIR PRESSURE SW FAULT and EXPANSION BRD faults name parts residential boilers lack: check the boiler size selected in the U-Control against the rating label.

On older cast iron boilers, the reset and indicator lights sit on or inside the control behind the jacket door, depending on the line.
On older cast iron boilers, the reset and indicator lights sit on or inside the control behind the jacket door, depending on the line. AI illustration.

What do the flashing lights mean on a GV90+ or CGa Series 3?

On a GV90+ or CGa Series 3 the light combination is the code. Read it before cutting power, which clears a lockout.

Lights Usual meaning
POWER, once per second 120 VAC reversed or insufficient earth ground
POWER code 2, 3, 5, 6 Microprocessor or memory (2), LWCO circuit (3), water thermistors disagree (5), gas valve circuit (6)
POWER + TSTAT/CIRC Stray thermostat voltage, or return under 130°F for 30 minutes
POWER + PRESS SWITCH Switch closed early, or open 5 minutes after blower start
POWER + FLAME Three failed ignition attempts, or flame where none belongs
POWER + LIMIT Over-temperature; needs 45 seconds without power, return under 240°F
FLAME alone; LIMIT alone Flame loss or not sensed; open or shorted water sensor
TSTAT/CIRC alone Freeze protection, return under 40°F
LWCO solid; 3 rapid pulses Low water occurred; LWCO requires maintenance

A code means rapid POWER flashes, then 2 seconds off.

CGa Series 3 adds a DAMPER light, and its manual says propane pilots lock out after 4 tries with all LEDs flashing. A solid LWCO light means the low water cutoff tripped.

What do A and F codes mean on an AquaBalance?

A codes are hard lockouts cleared with the reset button held for 1 second; F codes clear themselves when the value returns to range. Burnham draws a similar line between soft and hard lockouts on the touchscreen of its Alpine condensing boilers, as the Burnham boiler error codes explain. AquaBalance limits resets to 5 in 24 hours.

Code Weil-McLain’s description
A01, A02 No ignition after five attempts; false flame
A03 High limit: pump does not run or no circulation
A04, A26 F07 3 times in 24 hours; F40 3 times in an hour
A05, A06 No fan feedback; 6 flame losses in 4 minutes
A16, A23 Outside sensor not connected; pressure not reached
A41, A42, A44 Sensor loose on pipe; two supply sensors disagree
A61, A62, A63, A65 Flame circuit, gas valve circuit, E2 prom, ADC errors
F07, F27 Exhaust temperature too high
F10 to F15 Water, exhaust sensor errors; fan feedback (F15)
F20, F21, F37, F40 Pressure near low, near high, too low, too high or control fault
F34, F35 Low mains voltage; frequency error
F43, F51 Heat exchanger protection; low water

F37 lists pressure under 8 psi; our boiler pressure guide covers normal readings.

What do CGa Series 4 and CGi Series 5 faults mean, including SPILL SWITCH?

SPILL SWITCH on a CGa means burner spill from possible vent blockage or wind, and it is the one to stop on.

Display Weil-McLain’s description
CONFIRM CONFIGURATION, CONFIG MISMATCH Board setup or harness number wrong
AUTO LIMIT, MANUAL LIMIT Limit chain open; rollout switch shows as manual
FALSE FLAME, FLAME LOST Flame with valve unpowered; flame lost running
IGNITION FAULT Maximum failed ignitions reached
BOILER OUT OPEN, SHORT; HARDWARE FAULT 1 to 8 Sensor faults; control board or valve harness
CH, DHW VOLTAGE HIGH Excess thermostat input voltage
SPILL SWITCH (CGa) Burner spill, possible vent blockage or wind
PS OPEN, LWCO OPEN Fault (CGi) Air pressure switch open; low water value

The boiler manual tells technicians to press the spill switch reset, but the user manual tells owners not to restart and to call a technician immediately.

Water pressure and circulation are the first checks before any lockout is reset.
Water pressure and circulation are the first checks before any lockout is reset. AI illustration.

How many times should you reset a locked-out Weil-McLain boiler?

Once, after writing down the fault; the CGa and CGi user manual says to call a technician if it re-occurs. The Ultra Series 4 manual adds: “Do not leave the boiler operating without a complete diagnosis.”

Owner checks are the safe ones for any boiler: breaker, switch, gauge, and vent piping. Stop on a flame fault, E 00 or spill trip. If you smell gas or a carbon monoxide alarm sounds, leave. If the boiler overheats, Weil-McLain says to leave the pump powered and shut gas off outside the appliance.

On an Ultra Series 4, a technician tests 102 to 132 VAC, gas at 4 to 13 inches w.c., ignition cable at 1000 ohms, a 3.5 mm igniter gap, and combustion at high and low fire. Its ignition row lists a blocked condensate trap and dirty burner, both annual service items.

How do you pull past error codes off the control?

On an Ultra Series 4, open DIAGNOSTICS, ERRORS, then LOCKOUT HISTORY for the last 3 lockouts; holding both arrows 5 seconds on ERRORS erases them. ECO Tec Series 2 keeps 6; AquaBalance holds 8 as H01 to H08.

Frequently asked questions

Where can I get a Weil McLain boiler error codes PDF?

Weil-McLain publishes no single code PDF; each fault table sits inside that line’s boiler manual. Ultra Series 4 is 550-100-440, pages 117 to 123. GV90+ Series 2 is 550-143-010, page 79. AquaBalance Series 2 is 550-100-325, pages 92 to 95.

What does a blinking red light on a Weil-McLain boiler mean?

On an Ultra Series 3 or 4, a screen flashing red to gray means lockout, while constant red marks a condition that can restart automatically. On a GV90+, the flashing POWER plus FLAME LEDs usually mean three failed ignition attempts.

Where is the reset button on a Weil-McLain Ultra boiler?

Ultra Series 1 and 2 have a RESET button on the display panel, and hard lockouts need it pressed. Series 3 and 4 manuals describe manual reset screens on the U-Control display instead, so a lockout clears from the menu.

What does a communication error mean on a Weil-McLain boiler?

The display and control lost contact. Ultra Series 4 shows DISPLAY COMM and ECO Tec Series 2 shows Communication errors, each after 30 seconds, and both reset automatically when contact returns. Check the control plug and the back of the display.

How we researched this

We read fault tables in 12 Weil-McLain manuals in November 2026, 3 as archived or hosted copies. We excluded code-list and contractor sites, whose rows disagreed with the manuals. Evergreen 220 to 399, ECO Tec Series 3, Simplicity, Ultra Oil and Gold boilers are not covered.

Sources

  1. Weil-McLain. “Ultra Series 4 Manual, 550-100-440/1025, pp. 115-123.” https://www.weil-mclain.com/wp-content/uploads/Ultra-Series-4-Boiler-Manual-550100440_1025.pdf. Accessed November 2026.
  2. Weil-McLain. “Ultra Series 1 and 2 Control Supplement, 550-100-029/0810, pp. 9, 26-32 (ManualsDir copy).” https://manualsdir.com/manuals/222340/weil-mclain-ultra-230-ultra-80-ultra-105-ultra-155-ultra-310.html. Accessed November 2026.
  3. Weil-McLain. “Ultra Series 3 Manual, 550-100-066/0608, pp. 85, 86 (archived copy).” https://web.archive.org/web/20101130094906id_/http://weil-mclain.com/en/multimedia-library/pdf/weil-mclain-pdf/products/boilers/gas-boilers/ultra-series-3/ultra-series-3-boiler-manual.pdf. Accessed November 2026.
  4. Weil-McLain. “WM97+ Manual, 550-142-085/0712, Figure 110 (archived copy).” https://web.archive.org/web/2014id_/http://www.weil-mclain.com/en/multimedia-library/pdf/weil-mclain-pdf/products/boilers/gas-boilers/wm97/WM9770-155BoilerManual.pdf. Accessed November 2026.
  5. Weil-McLain. “GV90+ Series 2 Manual, 550-143-010/0324, pp. 65, 79.” https://www.weil-mclain.com/wp-content/uploads/GV90-S2-Boiler-Manual-0324.pdf. Accessed November 2026.
  6. Weil-McLain. “CGa Series 4 Manual, 550-100-223/0425, pp. 64-67.” https://www.weil-mclain.com/wp-content/uploads/CGa-Series-4-Boiler-Manual-0425.pdf. Accessed November 2026.
  7. Weil-McLain. “CGi Series 5 Manual, 550-100-629/0926, pp. 76-79.” https://www.weil-mclain.com/wp-content/uploads/CGi-Series-5-Boiler-Manual-550100629-0926.pdf. Accessed November 2026.
  8. Weil-McLain. “CGa, CGi User Manual, 550-100-226/0425, pp. 4, 12.” https://www.weil-mclain.com/wp-content/uploads/Users-Manual-CGaS4-CGiS5-EGS7-PEGS7-LGBS2-3-0425.pdf. Accessed November 2026.
  9. Weil-McLain. “CGa Series 3 Manual, 550-142-300/1025, p. 49.” https://www.weil-mclain.com/wp-content/uploads/CGa-Series-3-Boiler-Manual-1025-2.pdf. Accessed November 2026.
  10. Weil-McLain. “AquaBalance Series 2 Manual, 550-100-325/0924, pp. 92-95, 102.” https://www.weil-mclain.com/wp-content/uploads/AquaBalance-Series-2-Boiler-Manual-0924.pdf. Accessed November 2026.
  11. Weil-McLain. “Evergreen 110/155 Manual, 550-100-210/D_1222, pp. 108-111.” https://www.weil-mclain.com/wp-content/uploads/Evergreen-Pro-Sizes-110-155-Boiler-Manual-1222-Web-Version.pdf. Accessed November 2026.
  12. Weil-McLain. “ECO Tec Series 2 Manual, 550-100-270/0924, pp. 134-147.” https://www.weil-mclain.com/wp-content/uploads/ECOTecS2-BoilerManual-0924.pdf. Accessed November 2026.