Rinnai boiler error codes depend on the boiler line. I-Series and I-Series Plus boilers show three digits (110 no ignition, 120 flame failure, 430 water pressure). M-Series uses its own three-digit list, where 110 means a failed supply sensor. E-Series shows Error or Block numbers. Two-digit 10, 11 and 12 are tankless codes.

Which Rinnai boiler is on the wall: I-Series, M-Series, E-Series or a tankless heater?
Read the model number on the rating label first, because Rinnai reuses numbers across lines. Code 110 is No Ignition on an I-Series, a damaged supply sensor on an M-Series, and is not in the E-Series error list at all.
| Line | Model numbers on the label | What a code looks like |
|---|---|---|
| I-Series | i060C, i090C, i120C combi; i060S to i150S solo | Three digits, printed E:110 in the user manual |
| I-Series Plus | IP060160C to IP199199C combi; IP060S to IP199S solo | Three digits, plus LC, FFF, SS, SE |
| M-Series | M060C to M160C combi; M060S to M160S solo | Three digits, plus 1P, 3P and 5P alerts |
| E-Series | E75C, E110C (N or P suffix) | Error or Block plus two digits |
| Q-Series | Q85S, Q130S, Q175S, Q205S, Q175C | Flashing E or BL plus a number, alternating with Good |
| Rinnai tankless | RU, RUR, RE, RL, V and other water heaters | Two digits, 02 to 79 |
Compiled by The HVAC Brief from the Rinnai manuals listed under Sources, November 2026.
What do I-Series and I-Series Plus codes 100 to 720 mean?
An I-Series code names a circuit, and an error code alone on the screen means the boiler has shut down. The technician column comes from section 12.8 of Rinnai’s 2020 I-Series combi installation manual.
| Code | Rinnai’s wording | Owner check | What the technician checks |
|---|---|---|---|
| 100 | Air Supply or Exhaust Blockage/Condensate Trap is Full | Vent discharge and air intake clear; condensate line not blocked | Condensate trap, internal air filter, vent length, high altitude setting, fan wheel |
| 110 | No Ignition (Unit Not Turning On) | Gas on at the boiler and meter; propane tank not empty | Igniter, flame rod wire, gas solenoid valves, orifice for the gas type, flame rod voltage to ground during ignition |
| 120 | Flame Failure | Same gas checks as 110 | Gas type and inlet gas pressure, flame rod, PC board ground wire |
| 140 | Heat Exchanger Overheat | None | Overheat switch resistance, locked pump, closed CH valves, scale hot spots |
| 150, 170 | Venturi Control; Venturi Blockage | None | Venturi motor or gas valve assembly; debris in venturi and silencer |
| 310 to 393 | Thermistors: freeze, outgoing, heat exchanger, inlet, supply, return, indirect, exhaust, outdoor | None | Sensor wiring and resistance, then replace |
| 430 | High/Low Water Pressure | Read the gauge | Leaks, relief valve, fill valve, deaeration |
| 443 | Low Water Cut-Off (LWCO) | None | LWCO device or jumper; 24 VAC at the PCB |
| 520, 710 | Solenoid Valve Circuit | None | PC board output to the gas valve; DIP switch 5 OFF |
| 700, 720 | PC Board; Flame Rod | None | Flame rod and wire, wet wiring, then the PC board |
| LC | Scale Buildup in Heat Exchanger (Combi Only) | None | Flush the DHW plate heat exchanger; LC clears when scale is gone |
Compiled by The HVAC Brief from Rinnai manual 800000192 (Table 4) and manual 800000111 (section 12.8). Not shown: 021, 161, 180 to 250, 540, 610, 631 to 681, 831, 890; 999 (original I-Series only); 303 and 763 (Plus 175K and larger).
The owner column is narrow on purpose: the I-Series Plus user manual limits owners to monthly checks of vents, the condensate line and the gauge, and says to call a service provider whenever a code shuts the boiler down. Codes 110, 120, 520, 710 and 720 are gas valve and flame circuits; that is the stop line. If you smell gas, Rinnai says to call the gas supplier from a neighbor’s phone. A clogged trap behind code 100 is the same failure our condensate pump guide traces.
Why does Rinnai code 110 mean a sensor on an M-Series and no ignition on an I-Series?
The M-Series control numbers its faults differently. In the M-Series combi manual, 110 is “Send Probe Damaged,” a supply sensor open or short, and 140 is a failed water pressure check, not an overheat.
| M-Series code | Rinnai’s wording | What triggers it |
|---|---|---|
| 101 | Overheat | Supply or return above 212°F for 3 seconds |
| 108, 109 | Supply pressure below minimum; above maximum | Below 10.1 PSI; above 43.5 PSI |
| 110, 112, 114 | Send, Return, Outdoor Probe Damaged | Sensor short or open circuit |
| 140 | Water Pressure Dynamic Check | Two 1P9 checks failed |
| 304 | Too Many Reset | Reset pressed more than 5 times in 15 minutes |
| 501, 504 | No Flame Detected; Flame Lift | Ignition or flame loss: press Reset |
Compiled by The HVAC Brief from Rinnai M-Series combi and solo installation manuals 800000063 and 800000065, section 12.6.
Rinnai’s M-Series rule: “A blocking code is a temporary error that can be automatically corrected by the boiler”; fault codes need Reset. Navien boiler error codes work the other way, with E110 meaning one fault on every line.
Rinnai boiler code 10, 11, 12, 14 or 17: is that a boiler code at all?
Usually not. A bare two-digit 10, 11, 12, 14, 16 or 17 is a Rinnai tankless water heater code. Comparing the two manuals line by line, we found the I-Series boiler reuses the tankless meaning with a digit added: tankless 11 No Ignition is boiler 110 No Ignition.
| Tankless code | Tankless wording | I-Series boiler code | Boiler wording |
|---|---|---|---|
| 10 | Air Supply, Exhaust Blockage or Condensate Trap is Full | 100 | Air Supply or Exhaust Blockage/Condensate Trap is Full |
| 11 | No Ignition | 110 | No Ignition |
| 12 | Flame Failure | 120 | Flame Failure |
| 14 | Thermal Fuse or Overheat Sensor (ODS) | 140 | Heat Exchanger Overheat |
| 16 | High Outgoing Water Temperature | 161 | High Outgoing Temperature |
| 17 | Venturi Blockage | 170 | Venturi Blockage |
| 72 | Flame Rod Fault | 720 | Flame Rod |
HVAC Brief comparison of Rinnai’s tankless diagnostic code manual 100000652 with I-Series Plus Table 4. The pattern is ours, not a Rinnai statement, and it breaks for thermistors: tankless 51 is the inlet thermistor, boiler 341.
The E-Series does show two digits. Its E75C/E110C installation manual (archived copy) lists Error 12 as “fuse 24 volt/3AT faulty” and Block 12 as the domestic hot water temperature difference “repeatedly exceeded.” On an E110C, then, code 12 is never a flame failure. Tankless owners: see our tankless water heater explainer.
What do Error and Block numbers mean on an E-Series E75C or E110C?
A Block is a pause the boiler clears itself; an Error is a lock. The E-Series manual says Error messages “are permanent locks which can only be removed by pressing the reset key.”
| E-Series message | Rinnai’s wording |
|---|---|
| Block 01 | External safety contact cut off |
| Block 11 | Central heating supply/return temperature difference repeatedly exceeded |
| Block 85 | No water flow detected; venting cycle started |
| Error 00, 02 | Poor flame-forming; no flame-forming |
| Error 14 | Supply sensor T1 ground connection; about 12 kOhm at 77°F |
| Error 18, 19 | Maximum flow, maximum return temperature exceeded |
Compiled by The HVAC Brief from the Rinnai E-Series installation and servicing instructions, chapter 15. The Q-Series user manual uses the same flashing E or BL display, but we could not read a clean Q-Series code table, so no Q meanings appear here.

Rinnai code 430 or 108: what should the pressure gauge read?
On an I-Series, 17 to 26 PSI. Rinnai’s 2020 combi manual says the boiler stops with E430 below 7.3 PSI and runs limited between 7.3 and 13 PSI. An M-Series runs between 14 and 43.5 PSI and shows Fault 108 below 10.1 PSI.
One oddity: the M-Series Fault 109 waits for 43.5 PSI, yet the supplied relief valve is rated 30 PSI, so the valve drips long before 109 appears. Pressure that climbs on heating points at the expansion tank, which our boiler pressure guide covers. I-Series code 443 belongs to a low water cutoff, a separate device or a factory jumper.
How do you reset a Rinnai boiler code, and when do you stop pressing Reset?
On an I-Series, press the blinking CH or DHW button; a code raised during hot water use may clear when the faucet closes. On an M-Series, press RESET, then OK at “Do you really want to perform the reset?” Stop after one try if the same code returns.
The M-Series enforces that limit itself: more than 5 resets in 15 minutes raises code 304 and you must wait 15 minutes. For history, an I-Series shows the last nine codes (hold DHW two seconds, then Up); an M-Series keeps the last 10 errors under menu 8.6. Other makes hide history elsewhere, as our Weil-McLain boiler error codes guide shows.
Frequently asked questions
What does Rinnai boiler code E110 mean?
On an original I-Series combi, E:110 is No Ignition. Rinnai’s installation manual has the technician confirm gas supply, bleed air from the gas line, and check the igniter, gas solenoid valves and flame rod voltage to ground during ignition. On an M-Series, 110 instead means the supply sensor is damaged.
What does Rinnai boiler error 17 mean?
Two-digit 17 is a tankless code, Venturi Blockage. On an I-Series boiler the same fault shows as 170. Rinnai’s installation manual says to check the venturi and silencer for blockage and, before resetting, confirm the condensate drain is clear and the venting is connected properly.
What is Rinnai boiler code 14?
On a Rinnai tankless heater, 14 is Thermal Fuse or Overheat Sensor (ODS); the I-Series boiler version is 140, Heat Exchanger Overheat, where the installer checks the overheat switch resistance, a locked pump and closed heating valves. On an E-Series boiler, Error 14 points at the supply sensor T1, which should read about 12 kOhm at 77°F.
What does FFF mean on a Rinnai boiler?
FFF is not a fault. Rinnai’s I-Series manual calls it a placeholder in the diagnostic code history showing that a service provider performed maintenance. The technician enters it after service by holding Up, then Down, then pressing the DHW button at the same time.
How we researched this
In November 2026 we read the code tables in nine Rinnai documents, listed below. We excluded Rinnai space heater codes, non-US models and third-party lists that cite no Rinnai document. Q-Series meanings are left out because the only Q-Series code table we could open was a scrambled mirror.
Sources
- Rinnai. “I-Series Plus 150K BTU and Smaller Boiler User Manual (800000192).” media.rinnai.us. Accessed November 2026.
- Rinnai. “I-Series Plus 175K BTU and Larger Condensing Boiler User Manual (800000218).” media.rinnai.us. Accessed November 2026.
- Rinnai. “I-Series Condensing Combi Boiler Installation and Operation Manual (800000111).” media.rinnai.us. Accessed November 2026.
- Rinnai. “I-Series Condensing Combi Boiler User Manual (800000114).” media.rinnai.us. Accessed November 2026.
- Rinnai. “M-Series Condensing Combi Boiler Installation and Operation Manual (800000063).” media.rinnai.us. Accessed November 2026.
- Rinnai. “M-Series Condensing Solo Boiler Installation and Operation Manual (800000065).” media.rinnai.us. Accessed November 2026.
- Rinnai. “Troubleshooting Tankless Water Heater Diagnostic Codes (100000652).” media.rinnai.us. Accessed November 2026.
- Rinnai. “Installation and Servicing Instructions, E-Series E75C/E110C” (archived copy). archive.org. Accessed November 2026.
- Rinnai. “User Information Manual, Q-Series Q85SN to Q205SP” (archived copy). archive.org. Accessed November 2026.

Leave a Reply