Navien boiler error codes are an E plus three digits, and most mean the same thing on every US line: E003 is ignition failure, E012 flame loss, E110 exhaust blockage or a clogged intake filter. The split is low pressure: NCB700, NHB-H and NFB-C show E302, while auto-fill NCB-E and NCB-H combis show E351.
Which Navien boiler is on the wall, and which button resets it?
Read the model on the rating label first: the six Navien boiler manuals differ on reset key, low-pressure code and pressure numbers. Only the NFB-C manual says to press and hold Reset.
| Line and models | Reset key | Low pressure shows as | Pressure figures in the manual |
|---|---|---|---|
| NCB-E (NCB-150E to NCB-240E) | Reset button | Auto refill; E351 after 5 minutes | LWCO 7.3 psig; fill at least 12 psi |
| NCB-H (NCB-190/060H to NCB-250/150H) | Back button | Auto refill; E351 after 5 minutes | LWCO 7.3 psig; fill at least 12 psi |
| NCB700 (NCB700-190/060 to NCB700-250/150) | Back button | E302, manual reset | LWCO 6 psi default; typical fill 12 psi |
| NHB-H (NHB-055H to NHB-150H) | Back button | E302, manual reset | LWCO 6 psi default; fill at least 6 psi |
| NFC-H (NFC-250/175H, NFC-250/200H) | Back button | Chart lists E351, not E302 | Fill at least 6 psi |
| NFB-C (NFB-301C, NFB-399C) | Press and hold Reset | E302, manual reset | Fill at least 12 psi |
The NPE-240A2 behind “Navien 240A” searches is a water heater with its own chart (last section). For a boiler showing no code, use our boiler not working checklist.
What does each Navien boiler error code mean on NCB, NHB, NFC and NFB models?
Meanings hold across lines; what changes is where a code appears and what the owner may do. Rinnai is the opposite case, where the same three digit number means a failed ignition on an I-Series boiler and a failed supply sensor on an M-Series, as the Rinnai boiler error codes show. The NCB-H user’s manual sends most sensor and board codes to Navien Technical Support at 1-800-519-8794; the NHB-H installation manual and NFC-H charts name the technician’s first check.
| Code | Navien’s wording | Listed in | Owner step in the manual | Technician checks |
|---|---|---|---|---|
| E001 | Heat exchanger overheat | All but NCB-E | Reset from the front panel | Check system flow |
| E003 | Ignition failure | All six | Make sure the main gas valve is open | Check gas supply valve and igniter |
| E004 | False flame | All six | Check the power cord is grounded | Check electric ground |
| E012 | Flame loss | All six | Clean the intake air filter; check the cord ground | Check gas, venting and condensate trap |
| E016 | Heat exchanger overheat | All six | Off at least 30 minutes, restart; flush the heat exchanger | Check flow, clean system filters |
| E030, E031 | Exhaust overheat; burner overheat | E030: All six; E031: NCB-H, NFC-H, NFB-C | Call support | Check flow and filters; E031: burner temperature fuse |
| E046, E047 | Heat exchanger and exhaust thermistors | All six | Call support | Check thermistor connector |
| E060 | Abnormal dual venturi | All six | Call support | Check dual venturi |
| E109 | Abnormal fan motor | All six | Clean the intake air filter | Check fan and venting |
| E110 | Exhaust blockage | All six | Clear the exhaust pipe; clean the intake air filter | Check exhaust venting |
| E205, E218, E278, E279 | Heating supply, return and external sensors | E205, E218: All six; E278, E279: All but NCB-E | Call support | Check sensor connections |
| E302 | Low water pressure | NCB700, NHB-H, NFB-C | Check water pressure, then manual reset | Check water pressure |
| E351 | Abnormal auto feeder valve | NCB-E, NCB-H, NFC-H | Call support | Check valve and supply water |
| E352, E353 | High water pressure; pressure sensor | All six | Call support | Check water pressure and sensor |
| E407, E421, E434, E439, E441, E445 | Hot water side sensors, flow and valves | E407, E421, E439: NCB-E, NCB-H, NCB700, NFC-H; E434, E441, E445: NCB-H, NCB700, NFC-H | Call support | Check the named sensor or valve |
| E515, E517, E594, E615 | PCB, DIP switch, EEPROM, memory | All six | E515: check cord ground, reset | Check PCB connections and DIP switches |
| E736, E740 | Cascade link; outdoor sensor missing | All six | E740: check outdoor sensor wiring | Check cable and sensor connections |
| E762 | Vent pipe not fully inserted | NCB-H, NCB700, NHB-H, NFC-H | Call support | Insert pipe 2-3/4 in (70 mm) into the collar |
| E773, E788 | Wrong gas type detected or set | E773: NCB-H, NCB700, NFC-H; E788: NCB-H, NCB700, NHB-H, NFC-H | E788: match gas to DIP switch | Check gas conversion and DIP switch |
| E777 | Low water cutoff activated | All six | Check LWCO wiring and water level | Check supply water |
| E782, E784, E786 | Front panel and zone controller faults | E782: All six; E784: All but NCB-E; E786: NCB-H, NCB700, NHB-H, NFC-H | Call support | Check panel connections and wiring |
The NCB-E chart calls E046 “limit control” and E110 “abnormal air pressure”. Only the NFB-C chart says how codes clear: E003 and E012 by manual or power-on reset, E004 by itself, and E774 or E775 means the control hit its reset limit.

Navien boiler code 302 or E351: why low pressure shows two different codes
On a Navien NCB700, NHB-H or NFB-C, code 302 means low water pressure and needs a manual reset after refilling. The NCB-E and NCB-H do not list E302: their pressure sensor triggers automatic make-up water, and the NCB-E installation manual says E351 appears if that refill is not completed after 5 minutes.
Trip points differ: 7.3 psig on the NCB-E and NCB-H internal cutoff, 6 psi by default on the NCB700 and NHB-H. Repeated E302 or E351 means lost water; the NHB-H manual warns make-up water can lead to heat exchanger failure. Our boiler pressure guide covers relief valve and expansion tank checks; E777 is a separate external low water cutoff.
Is Navien code 003 or 012 a gas problem you can clear yourself?
Only the first step: for E003 (ignition failure) the NCB-H manual says make sure the main gas supply valve is open; for E012 (flame loss), clean the intake air filter and check the cord is grounded.
Past that it is technician work, starting with an inlet gas pressure reading: the NCB-H installation manual lists 3.5 to 10.5 in WC for natural gas and 8.0 to 13.5 in WC for propane. Inside that band, check the igniter, flame rod and condensate trap. If you smell gas, do not reset: Navien says leave switches alone and call the gas supplier from a neighbor’s phone.
Why does Navien code 110 keep coming back, and where is the air intake filter?
Usually a dirty intake filter: Navien’s NCB-H manual says a clogged filter stops the boiler with “Error Code 110” and sets cleaning every 3 to 4 months (NHB-H: as needed or at annual maintenance).
Navien’s NCB-H steps: press Power, unplug, unfasten the 4 latches on the front cover, remove the screw holding the filter at the top left of the boiler, and rinse it in clean running water. Opening the cover powered risks electric shock, the NCB-E manual warns.
If E110 returns with a clean filter, check the vent and, per the NCB700 chart, the condensate drain outlet. A blocked or loose vent can spill flue gas, so test your carbon monoxide alarms before running the boiler again.

How do you reset a Navien boiler without wiping the code you need?
Record the code, then reset. On the NCB-H, NCB700 and NHB-H, Menu then “4. Error History” lists 10 recent errors, so the pattern survives a reset.
The NCB-H and NHB-H restart on their own after a power failure, so a code after the power returns is a real fault. On the NCB-E, a level 2 or higher error also stops a connected air handler.
Do Navien tankless water heater codes and UK Navien codes mean the same thing?
Not always. The NPE-2 water heater manual reuses most numbers, with these exceptions.
| Code | On Navien boilers | On NPE-2 water heaters |
|---|---|---|
| E046 | Heat exchanger thermistor (NCB-E: limit control) | Limit control |
| E030 | Exhaust overheat | Shuts down when flue temperature exceeds 149 °F (65 °C) |
| E302, E351 | Low pressure, auto feeder | Not listed |
| E438 | Not listed | Circulation pump (with an air handler installed) |
| E760 | Not listed | Flushing or service alarm |
Most pages ranking today cover UK-market Navien boilers and lead with 02E, 10E and E787, codes absent from all six US manuals. Compare Weil-McLain boiler error codes or our tankless water heater guide.
Frequently asked questions
How do I reset my Navien water heater?
On Navien NPE-A2 and NPE-S2 condensing water heaters, press the Back button on the front panel. The NPE-2 user’s manual notes the heater keeps its settings through a power outage, and sends most sensor and board codes that return after a reset to Navien Technical Support at 1-800-519-8794.
How does a Navien combi boiler work?
A Navien combi such as the NCB-H runs a space heating loop and makes domestic hot water on demand, hot water first: the NCB-H manual says that when the unit is heating for DHW, the heating side does not work. Our combi boiler explainer covers flow rates and federal efficiency rules.
Where are the filters on a Navien NPE-240A?
The NPE-2 manual, which covers the NPE-240A2, has you drain the heater before pulling the cold water inlet filter and, on A2 models only, the recirculation inlet filter at the bottom. The air intake filter sits at the top left behind the front cover; Navien says to clean it every 3 to 4 months.
Can you tell a Navien boiler’s age by serial number?
Not from Navien’s documents: none of the ten manuals we read decodes a serial number. Warranty runs from the date of original installation (NCB-E manual), so keep the invoice. Our HVAC serial number lookup lists brands whose date codes we could verify.
What does a blinking red light on a Navien boiler mean?
On the NCB-H, NCB700 and NHB-H, a front panel flashing red with a flashing error icon is a level 1 error. Navien says the boiler keeps operating, the error clears automatically once the problem is resolved, and pressing the Power button clears it if the cause is gone.
How we researched this
On November 6, 2026 we downloaded the ten Navien manuals listed below and compiled rows only from their error charts. We checked the NCB-E and NCB-H charts against page images because the PDF text layer misaligns multi-line cells. Excluded: UK-market codes found only on third-party pages, and the NFB-H, NFB700 and first-generation NPE-A manuals, which we did not open.
Sources
- Navien. “NCB-E Condensing Combi-Boilers User’s Information Manual.” https://www.navieninc.com/downloads/ncb-e-manuals-user-information-manual-en. Accessed November 2026.
- Navien. “NCB-E Condensing Combi-Boilers Installation and Operation Manual.” https://www.navieninc.com/downloads/ncb-e-manuals-installation-manual-en. Accessed November 2026.
- Navien. “NCB-H Condensing Combi-Boilers User’s Information Manual.” https://www.navieninc.com/downloads/ncb-h-user-s-information-manual-en. Accessed November 2026.
- Navien. “NCB-H Condensing Combi-Boilers Installation and Operation Manual.” https://www.navieninc.com/downloads/ncb-h-installation-and-operation-manual-en. Accessed November 2026.
- Navien. “NCB700 Condensing Combi-Boilers Installation and Operation Manual.” https://www.navieninc.com/downloads/ncb700-installation-and-operation-manual. Accessed November 2026.
- Navien. “NHB-H Condensing Boilers Installation and Operation Manual.” https://www.navieninc.com/downloads/nhb-h-installation-operational-manual-en. Accessed November 2026.
- Navien. “NHB-H Condensing Boilers User’s Information Manual.” https://www.navieninc.com/downloads/nhb-h-user-s-information-manual-en. Accessed November 2026.
- Navien. “NFC-H Condensing Combi-Boilers User’s Information Manual.” https://www.navieninc.com/downloads/nfc-h-user-s-information-manual-en. Accessed November 2026.
- Navien. “NFB Condensing Boilers (NFB-301C, NFB-399C) User’s Information Manual.” https://www.navieninc.com/downloads/nfb-c-user-information-manual-en. Accessed November 2026.
- Navien. “NPE Condensing Water Heaters (NPE-A2, NPE-S2) User’s Information Manual.” https://www.navieninc.com/downloads/npe-2-user-s-information-manual-en. Accessed November 2026.

Leave a Reply