Senville mini split error codes on AURA (SENA) and LETO (SENL) units are four characters: EH for indoor faults, EC for outdoor sensors and fans, EL 01 for lost communication, EL 0C for low refrigerant and PC for protection trips. dF, CL, FP, FC, AP and CP are status displays, not faults. Some displays use older codes: E1, EC, F5, P4.
Every row comes from Senville’s AURA and LETO reference guides (modified April 7, 2025), per-code help articles and owner’s manual.
What does each Senville AURA and LETO indoor code mean, and what can you check?
AURA and LETO wall units share one indoor code set. Bracketed codes are the two-character versions Senville’s earlier articles pair with each. Older Fujitsu lines are less consistent and reuse the same numbers for different faults, which is why the Fujitsu mini split error codes start by matching the series.
| Code | Senville’s wording | Circuit or part | Owner check | Technician job |
|---|---|---|---|---|
| EH 00 (E0), EH 0A | Indoor EEPROM errors | Indoor main PCB | Power off 2 minutes | Replace indoor PCB |
| EL 01 (E1, 8.8, 88) | Indoor and outdoor communication error | Interconnect wiring, either PCB | Power off 2 minutes | DC volts, outdoor terminals 2 and 3 |
| EH 02 (E2) | Zero-crossing signal detection error | Supply wiring, indoor PCB | Stable power? | Indoor PCB |
| EH 03 (E3) | Indoor fan speed out of control | Blower motor | Wheel turns freely? | Connector volts, bearings |
| EH 0b | Main to display board communication | Display board | Remote still works? | Display or main board |
| EH 60, EH 61 | Room sensor T1; pipe sensor T2 | Indoor thermistors | Power off 2 minutes | Resistance test, replace |
| FH CC, EH C1, EH C2, EH C3, EC C1 | Leak sensor faults; leak detected (EC C1: other zone) | Leak sensor | Ventilate; stop resetting | Leak check |
| EC 51 (F4) | Outdoor EEPROM error | Outdoor PCB | Power off 2 minutes | Replace outdoor PCB |
| EC 52, EC 53, EC 54, EC 56 | Sensors T3, T4, TP, T2B | Thermistors (0.06 V to 4.94 V) | Power off 2 minutes | Resistance test |
| EC 07 (F5) | Outdoor fan speed out of control | Outdoor fan motor | Clear leaves, snow | U, V, W ohms must match |
| EL 0C (EC) | System lacks refrigerant | Charge; T1 and T2 placement | Power off 15 minutes | Leak search, gauges |
| PC 00 (P0), PC 04 (P4) | IPM protection; compressor drive error | Inverter, compressor | Clear outdoor coil | Winding tests |
| PC 01 (P1) | Voltage protection | Supply, reactor | Nameplate: 110 V or 220 V | Reactor near zero ohms |
| PC 02 (P2) | Compressor or IPM over-temperature | Airflow, overload protector | Power off 10 minutes | OLP, high pressure switch |
| PC 03, PC 08 | Pressure protection; overcurrent | Switches, fan, charge | Outdoor fan running? | Gauges, current |
Compiled by The HVAC Brief from Senville’s AURA and LETO reference guides and per-code articles on help.senville.com, November 2026.
Both guides misprint the display board fault as “EH 0”; Senville’s own article titles it EH 0b. Codeless leaks and iced coils are in the mini split repair guide; MRCOOL mini split error codes use the same families.

Is dF on a Senville AURA an error, and which other displays are not faults?
No. dF is defrost; Senville’s dF article says it lasts 5 to 15 minutes (the owner’s manual: 4 to 10 minutes); call support if it passes 30 minutes. Defrost is one of several blinks that are not faults at all, which is why a blinking mini split after a power cut or during heat mode usually needs no repair.
| Display | Senville’s meaning | Action |
|---|---|---|
| CL / F | Filter cleaning reminder (15 seconds after power on) / replacement reminder | Clean or replace filters |
| FP | Heating with the room under 8°C | None |
| FC / AP / CP | Forced cooling / Wi-Fi pairing / remote switched unit off | Check settings |
-- |
Multi zone mode conflict | Set all heads to one mode |
| PC 0L (LP) | Outdoor sensor below −35°C for 10 seconds (−40°C with compressor on) | Resumes above −32°C |
Senville’s FP article describes FP as Freeze Protection holding “10°C (46°F)”. That is a conversion slip: 10°C is 50°F; 46°F matches the guides’ 8°C. On multi zone systems Senville gives HEAT precedence, so a head set to COOL stops and shows the dashes. PC 0L explains some “AURA not heating” nights; LETO is rated only to about 5°F, and heat pumps in cold weather covers the capacity loss.
Which codes appear only on LETO outdoor boards, multi zone and central systems?
Senville keeps separate folders for LETO outdoor boards, multi zone and SENDC central systems; these codes are not in the AURA guide.
| Line | Code | Senville’s wording | Limit stated |
|---|---|---|---|
| LETO outdoor, multi zone | PC 30 / PC 31 | High / low pressure | Above 4.4 MPa / below 0.13 MPa |
| LETO outdoor | PC 0A | Condenser high temperature | Trips at 65°C, restarts below 52°C |
| Multi zone | EC 57, EC 5A / EC 5C | Pipe and enthalpy sensors / pressure sensor | Outside 0.06 V to 4.94 V / below 0.5 V |
| Multi zone | EL 01 | Communication error | No feedback for 110 seconds, four times |
| Central | EH 0E | Water-level alarm | Switch voltage not 5 V |
| Central | FL 09 | New and old platform mismatch | Mixed generations |
Compiled by The HVAC Brief from Senville’s LETO Outdoor, Multi Zone and Central code folders (29 articles each).
The PC 30 article calls PC 30 high pressure, but the AURA multi zone owner’s manual (SENA/18HF/MOQ to SENA/48HF/MOQ) prints “PC 30 Low pressure protection” and PC 31 as high. Gauges settle which side tripped.

Does PC 03, P6 or EL 0C mean a Senville is low on refrigerant?
PC 03 trips above 4.4 MPa or below 0.13 MPa, not only on low charge; Senville lists poor ventilation, blockage and fan failure beside wrong charge.
| Senville limit | Code | US units |
|---|---|---|
| 4.4 MPa | PC 03, PC 30 high pressure | 638 psi |
| 0.13 MPa | PC 03, PC 31 low pressure | 18.9 psi |
| 65°C / 52°C | PC 0A trip / restart | 149°F / 125.6°F |
| −35°C / −32°C | PC 0L stop / resume | −31°F / −25.6°F |
HVAC Brief calculation: 1 MPa = 145.04 psi; °F = °C × 9/5 + 32. Senville does not say whether its MPa limits are gauge or absolute.
For P6, Senville says cut the breaker for at least 30 minutes. Its technician test: after 15 minutes of maximum heat the larger outdoor pipe should reach about 105°F (40°C), with heating pressure near 400 psi; a refrigerant pressure chart shows why those move with outdoor temperature.
EL 0C is inferred from repeated compressor shutdowns and odd temperatures. EH C1 is measured: refrigerant above 10 to 20% of LFL for over 10 seconds. Senville lists R454B for AURA IGG and LETO ILL units, explained in what R-454B is.
Under 40 CFR 82.161, anyone who could open the refrigerant circuit must pass an EPA certification exam. After an EH C1 alarm, air the room out and leave the unit off until a technician runs leak detection.
How do I reset a Senville mini split, and how long should the power stay off?
Cut the breaker for the time Senville gives, then restart with the remote. Photograph the display and model label first: Senville support asks for both, and no Senville document we read describes a recallable fault history.
| Situation | Power-off time |
|---|---|
| Most LETO and AURA codes, including EL 01, EC 07, PC 03 | 2 minutes |
| P2 / PC 02 | 10 minutes |
| EC / EL 0C | 15 minutes |
| P6, or a reset with no code | At least 30 minutes |
| dF showing | Do not reset |
Compiled by The HVAC Brief from Senville help articles and owner’s manual.
A blinking light after an outage is not a code: the owner’s manual says “the Operation light on the indoor unit will flash” when power returns, and ON/OFF on the remote restarts it. See AC not working after a power outage.
Senville documents describe no reset button; the button under the front panel is the manual power button, which Senville’s won’t-turn-on article uses to test the remote. If the breaker trips again, Senville says stop and call a licensed electrician or HVAC technician.
Why does a new Senville install show E1 or 88 on first start?
Start with the interconnect wiring. Senville’s E1 article says terminals 1, 2, 3 and G must carry the same colors at both terminal blocks. On an LG system the same lost link shows as one of the CH communication codes among the LG mini split error codes. Its technician test reads DC volts between outdoor ports 2 and 3: normal alternates between −25 V and 25 V; only positive values mean the outdoor PCB, a constant reading the indoor PCB. Senville reserves these live tests for a certified contractor.
Recent multi zone AURA outdoor units self-correct wiring: above 5°C (41°F), wait 2 minutes after power-up, press the outdoor check switch, and “CE” clears in 5 to 10 minutes. Self-installers should read the DIY mini split rules first.
Frequently asked questions
How do I find my Senville AURA model number?
On the grey label on the right side of the indoor unit, says Senville, and on the order email. SENA means AURA, SENL LETO, SENDC central; an AURA ending in IGG uses R454B. Use the indoor number for codes; the outdoor number differs.
How do I clean a Senville heat pump filter?
Breaker off, lift the front panel, slide out the mesh filters, then vacuum or wash them in warm water with mild soap and air dry. Senville’s filter article says every 30 to 60 days, or 2 to 4 weeks with pets; the owner’s manual says every two weeks.
Why is my Senville AC unit not cooling with no code on the display?
Senville’s checklist: COOL mode set 3 to 5°F below room temperature, clean filters, breaker off 30 minutes, and the outdoor fan spinning within 5 to 10 minutes. If it runs but never cools, Senville suspects low refrigerant or installation, a job for a licensed technician.
Is Senville a good brand?
We do not rate brands, but Senville publishes comparable terms. AURA: 5 years parts, 10 years compressor, up to 28 SEER, heats to about −22°F, multi zone available. LETO: 5 years parts and 5 years compressor, 17 to 21.5 SEER, heats to about 5°F, single zone only.
How we researched this
We read 80 Senville help center articles, the AURA multi zone owner’s manual (retailer-hosted copy of the maker’s PDF) and 40 CFR 82.161. We excluded aggregator and blog code meanings, including unsourced Midea-platform claims, and undefined codes such as E5. Researched November 6, 2026.
Sources
- Senville. “AURA Series Error Code Reference Guide.” https://help.senville.com/support/solutions/articles/151000211417-senville-aura-series-error-code-reference-guide. Accessed November 2026.
- Senville. “LETO Series Error Code Reference Guide.” https://help.senville.com/support/solutions/articles/151000211416-senville-leto-series-error-code-reference-guide. Accessed November 2026.
- Senville. “E1 / EL 01 / 8.8 / 88 Diagnostic.” https://help.senville.com/support/solutions/articles/151000198439-e1-el-01-8-8-88-error-code-diagnostic. Accessed November 2026.
- Senville. “PC 03 Pressure Protection.” https://help.senville.com/support/solutions/articles/151000213145-error-code-pc-03-pressure-protection-low-or-high-pressure-leto-aura-indoor-unit-. Accessed November 2026.
- Senville. “PC 30 System High Pressure Protection.” https://help.senville.com/support/solutions/articles/151000213169-error-code-pc-30-system-high-pressure-protection-leto-outdoor-unit-. Accessed November 2026.
- Senville. “P6 Low Pressure Protection.” https://help.senville.com/support/solutions/articles/151000016890-p6-error-code-low-pressure-protection. Accessed November 2026.
- Senville. “EH C1 Refrigerant Sensor Detects Leakage.” https://help.senville.com/support/solutions/articles/151000213127-error-code-eh-c1-refrigerant-sensor-detects-leakage-leto-aura-indoor-unit-. Accessed November 2026.
- Senville. “DF Defrost Code.” https://help.senville.com/support/solutions/articles/151000226299-understanding-the-df-defrost-code-on-senville-mini-split-systems. Accessed November 2026.
- Senville. “Mini Split Won’t Turn On.” https://help.senville.com/support/solutions/articles/151000211199-my-mini-split-won-t-turn-on-what-should-i-check-. Accessed November 2026.
- Senville. “Owner’s and Installation Manual, SENA/18HF/MOQ to SENA/48HF/MOQ” (retailer-hosted copy). https://www.sylvane.com/cdn/shop/files/owners-manual-senville-aura-48000-btu-dual-zone-mini-split-heat-pump.pdf. Accessed November 2026.
- eCFR. “40 CFR 82.161, Technician certification.” https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.161. Accessed November 2026.
- Senville. “Model Number and Manual.” https://help.senville.com/support/solutions/articles/151000236612-how-do-i-find-my-model-number-and-the-right-manual- . Accessed November 2026.
- Senville. “FP Code: Freeze Protection Mode.” https://help.senville.com/support/solutions/articles/151000016899-fp-code-freeze-protection-mode . Accessed November 2026.
- Senville. “LETO vs AURA.” https://help.senville.com/support/solutions/articles/151000202737-leto-vs-aura-what-is-the-difference-between-the-senville-series- . Accessed November 2026.
- Senville. “Clean Your Mini Split Air Filters.” https://help.senville.com/support/solutions/articles/151000211202-how-to-clean-your-mini-split-air-filters . Accessed November 2026.
- Senville. “Not Cooling or Heating Properly.” https://help.senville.com/support/solutions/articles/151000211198-my-mini-split-is-not-cooling-or-heating-properly-what-should-i-do- . Accessed November 2026.