Original data and independent reporting for the HVAC trade

·

LG Mini Split Error Codes: CH Codes and Blink Counts by Product Line

Homeowner counting blinking indicator lights to read lg mini split error codes on a wall unit

LG mini split error codes are CH numbers: CH05 and CH53 mean the indoor and outdoor units stopped communicating, CH38 means low refrigerant, CH07 means heads on one multi zone outdoor unit are set to opposing modes, and CH10 or CH67 is a locked fan. Wall units without a screen blink the number on two LEDs, one LED per digit.

What does each LG CH code mean on a single zone wall unit?

Codes 1 to 12 are indoor faults and 21 to 67 outdoor faults, in LG’s wording from Table 27 of the LS243HLV3 family manual and Table 22 of the LS090HSV4 installation manual. The last group come only from LG’s US help library guide, written “for all models”.

Code LG’s wording Owner check, then technician job
Indoor unit (LS243HLV3 Table 27)
CH01, 02, 06, 12 Return air (01), inlet pipe (02), outlet pipe (06) or middle pipe (12) thermistor open or shorted One power cycle; tech measures and replaces the sensor
CH04 Float switch error (optional) Confirm the condensate line drains; tech tests the float
CH05 Communication failure from indoor unit to outdoor unit Confirm outdoor power; tech checks cable and boards
CH09 Indoor unit EEPROM error One power cycle; tech diagnoses the indoor board
CH10 Indoor unit BLDC motor fan lock Power off, look for debris at the blower; tech tests the motor
Outdoor unit (LS243HLV3 Table 27, LS090HSV4 Table 22)
CH21 DC peak (IPM fault) None; tech checks inverter module and compressor
CH22, 23, 25 CT2 error, AC input too high (22); DC link low voltage (23); AC Low / High Volt (25) Note breaker trips or outages; tech measures supply voltage and amps
CH26 DC compressor position error (not providing rotation) None; tech checks windings and inverter output
CH27, 28, 29 PSC fault (27); compressor DC voltage too high (28); inverter compressor amperage too high (29) Clear the outdoor coil; tech checks board, amps, charge
CH31, 40 CT thermistor current too low (31); CT sensor open or shorted (40) None; outdoor board circuit
CH32 Discharge pipe overheat Clear the outdoor coil; tech checks charge and sensor
CH41, 44, 45, 46, 48, 65 Discharge pipe, outdoor air, condenser middle, suction line, liquid line or heat sink thermistor open or shorted One power cycle; tech replaces the named sensor
CH53 Communication failure from outdoor unit to indoor unit As CH05
CH60 Outdoor unit PCB EEPROM check sum error One power cycle; outdoor board
CH61, 62 Condenser coil temperature too high (61); heat sink too hot (62) Clear clutter outdoors, clean the filter if heating
CH63 Condenser coil pipe thermistor temperature is too low None; tech checks sensor and charge
CH67 Outdoor BLDC fan motor lock error Remove debris or snow at the fan
LG US help library only (all LG AC types)
CH07 Heads set to different modes (multi split) Set every head to heat, or every head to cool or dry
CH38 (F4) Low on refrigerant (gas) One power cycle; tech leak searches
CH54 After a power outage or electrical work Reset the breaker
CH66, 90, 91, 92 Communication line, piping or test run problem Call the installer
CH93, 237, 247 Communication; 237 and 247 mean no power at the outdoor unit Check the outdoor breaker and disconnect

Compiled by The HVAC Brief from LG’s LS243HLV3 and LS090HSV4 manuals, LG Canada’s LED table and LG’s two US help pages. With two faults, LG says “the lower error code number is displayed first”, so a fixed CH05 can be followed by a CH53 or CH61 that was waiting behind it.

On LG units the green and red LEDs blink out the two digits of the code.
On LG units the green and red LEDs blink out the two digits of the code. AI illustration.

Which LED is the tens digit when an LG mini split is blinking codes?

LG’s documents disagree. The US manual for the LS243HLV3 family gives “21 = LED1 (Green light) 2x blink, LED2 (Red light) 1x blink”, so its first LED carries the tens digit. LG’s India help page says the opposite: “The first LED indicates the ones digit of the error code.”

LG’s Canada error code page states the India rule, then breaks it in its own example: it calls three blinks on the second LED followed by five on the first a CH53, which its stated rule would read as 35. Its LED table also gives one pattern to both code 6 and code 60, and another to both 12 and 21.

Same blinks, two LG readingsSchematic of one display cycle; the LG documents we read give no timingLED1 (green)LED2 (red)2 blinks3 blinkspause, then the cycle repeatstimeUS install manual ruleLED1 = tens digitReads as CH23DC link voltage too lowCanada and India help textLED1 = ones digitReads as CH32Discharge pipe too hotBoth readings are defined LG codes, so the count alone cannot settle it.
The blink count is identical; the meaning flips with the digit rule. Sources: LG LS243HLV3 installation manual, Table 27 example; LG India and LG Canada help library pages. Drawing by The HVAC Brief.

We ran all 31 codes in the LS243HLV3 table through both rules: twelve sit in six pairs where swapping the LEDs turns one defined code into another.

Blinks seen (LED1, LED2) If LED1 is tens (US manual) If LED1 is ones (Canada, India text) Tie breaker
1, none CH10: indoor fan motor lock CH01: return air thermistor Is the indoor fan turning?
4, none CH40: CT sensor fault CH04: float switch (optional) No float fitted means CH40
6, none CH60: outdoor EEPROM error CH06: indoor outlet pipe thermistor Outdoor board LEDs also blinking means an outdoor code
2, 1 CH21: DC peak, IPM fault CH12: indoor middle pipe thermistor Outdoor board LEDs also blinking means CH21
2, 3 CH23: DC link low voltage CH32: discharge pipe overheat Both outdoor; read the outdoor board or the service manual
2, 6 CH26: compressor not rotating CH62: heat sink too hot Both outdoor; read the outdoor board or the service manual

HVAC Brief calculation: each Table 27 code converted to a blink pair under one rule and read back under the other. The tie breaker rests on the LS090HSV4 manual: indoor codes “will not display at the outdoor unit.”

Does an LG mini split blinking 5 times or 7 times mean CH05 and CH07?

Five blinks on one LED with the other dark is CH05 under either rule, because neither single zone table defines a code 50. LG India gives the same example: “if the power light flashes 5 times consecutively, pauses, and repeats, it indicates an error code 05.”

Neither single zone table defines code 7 or 70. CH07 exists, but LG’s CH07 article calls it a multi split code: it appears “whenever any of the indoor units is set to different Cool/Heat operation modes than the others” on one outdoor unit. The fix is a setting: LG’s US guide says to “set them all to either heating or cooling/dehumidification.” On a single zone unit, seven blinks has no LG meaning we could find; Mitsubishi blink counts and other brands’ tables do not transfer.

Before calling CH38 a leak, a technician checks power, sensors and pressures.
Before calling CH38 a leak, a technician checks power, sensors and pressures. AI illustration.

Is LG CH38 always a refrigerant leak, and what does a technician check first?

No. LG’s US guide says “CH38 / F4 errors indicate that the air conditioner is low on refrigerant (gas)”, but LG’s second US troubleshooting page groups CH32, CH33, CH36 and CH38 as a refrigerant or compressor problem “which may result from a temporary power issue.” That is why LG’s first step is a 5 minute power cycle, not a recharge.

LG’s CT09F service manual flow for “CH 38 (Refrigerant leakage error)” notes “This error occurs only in some models” and checks installation (bent pipe, closed service valve), four temperature sensors and the expansion valve before asking “Isn’t refrigerant insufficient?”

Stop at the power cycle. If CH38 returns, finding and repairing the leak takes gauges, a leak search method and a technician holding EPA Section 608 certification. After a new install, LG sends you to the installer; our page on a freon leak indoors covers the room air question.

CH05 or CH53 right after install versus months later: is it the wiring or the power?

A CH53 or CH05 “immediately after installing a new product” sends LG Canada to the installer to check that “the communication cables are wired properly with no misconnections”; the same code months later is treated as “a temporary error due to unstable electricity supply”, cleared by resetting the breaker “about 5 minutes later.”

Check the outdoor breaker and disconnect first: LG’s US page says CH93 on “models released after 2021” can mean the outdoor unit is not receiving power, and that CH237 and CH247 “indicate a communication error caused by a lack of power to the outdoor unit.” Our guide to an AC that quits after a power outage covers the restart order.

A repeating code means line voltage work at the outdoor terminal block and boards, and LG’s CT09F manual tells technicians to “start the checking 3 minutes after power cut off”: that is the owner’s stop line. New installs that throw CH66 or CH90 to CH92 point at installation and test run steps

What do LG error codes 35 and CH 228 mean, and which systems use three digits?

Neither appears in LG’s single zone wall unit tables. Code 35 comes from LG’s Multi V 5 service manual, a commercial VRF system, as “Outdoor unit low side pressure” shown as 351, 352 or 353 for the master, slave 1 or slave 2 unit. It trips below 400 kPa (58.02 psi) in cooling or 230 kPa (33.36 psi) in heating for 1 minute, shutting down after “three consecutive times.”

No LG document we opened defines CH 228. In the Multi V 5 tables we read, the last of three digits is a unit number from 1 to 3. For CH 228, photograph the rating label and request that model’s service manual; LG posts them on www.lghvac.com.

How long should an LG mini split stay off for a reset, and when do you stop?

Five minutes at the breaker: LG’s US guide says to “wait for 5 minutes, then restore power” (its Canada CH07 article uses 3 minutes). CH61 “will not automatically clear”, so it always needs that power cycle.

Reset once per code. LG warns “Do not disassemble the air conditioner or replace internal parts yourself” and to stop using the unit if the code persists. Unlike Daikin, which recalls codes through the remote, LG’s North American heads blink them on the indicator LEDs, per LG Canada.

Frequently asked questions

What does an LG mini split blinking green light mean?

On the LS243HLV3 family, LG labels LED1 green and LED2 red, and its example reads 2 green blinks plus 1 red blink as code 21, a DC peak (IPM) fault. Count both colors and check both readings, because LG’s help pages put the ones digit on the first LED.

What does CH mean in an LG mini split error code?

CH is LG’s prefix for every fault number, so CH05 is code 5. LG India says floor standing displays show a three digit code as CH, then 2, then 37 for CH237, and cassette display panels alternate CH and the number every 0.5 seconds.

How do you read LG mini split blinking codes without missing a blink?

Film them: LG India advises recording a video with your phone. On ceiling cassettes LG uses blink spacing for each digit: a long interval marks the hundreds digit, a medium interval the tens digit and a short interval the ones digit.

How we researched this

On November 7, 2026 we read LG’s LS243HLV3 Table 27 and LS090HSV4 Table 22 (via ManualsLib), LG Canada’s error code table and CH07 article, LG’s two US help pages, LG India’s guide to reading codes, the CT09F CH38 flow and the Multi V 5 entry for error 35. We excluded contractor blogs and aggregators, one of which listed CH06 as an indoor fan fault, and any code no LG document defines. The blink pair table is our calculation. We did not test equipment.

Sources

  1. LG Electronics. “LS243HLV3 installation manual, Table 27.” https://www.manualslib.com/manual/2277152/Lg-Ls243hlv3.html?page=74 Accessed November 2026.
  2. LG Electronics. “LS090HSV4 installation manual, Table 22.” https://www.manualslib.com/manual/888574/Lg-Ls090hsv4.html?page=52 Accessed November 2026.
  3. LG Canada. “Single / Multi-Split Air Conditioner Error Codes.” https://www.lg.com/ca_en/support/product-support/troubleshoot/help-library/cs-CT30000386-20153289364119/ Accessed November 2026.
  4. LG Canada. “CH07 error code [air conditioner].” https://www.lg.com/ca_en/support/product-support/troubleshoot/help-library/cs-CT32001121-20153141980769/ Accessed November 2026.
  5. LG USA. “[LG Air Conditioner] Guide to Error Codes.” https://www.lg.com/us/support/help-library/lg-air-conditioner-guide-to-error-codes-%2D20155047719306 Accessed November 2026.
  6. LG USA. “How to Troubleshoot Error Codes CH05 … 93 on Your LG Air Conditioner.” https://www.lg.com/us/support/help-library/how-to-troubleshoot-error-codes-ch05-53-e0-ch32-33-36-38-f4-ch66-90-91-92-and-93-on-your-lg-air-conditioner-%2D20155402834134 Accessed November 2026.
  7. LG India. “How to read error codes.” https://www.lg.com/in/support/product-support/troubleshoot/help-library/cs-CT00022939-20155117728312/ Accessed November 2026.
  8. LG Electronics. “CT09F service manual, CH 38.” https://www.manualslib.com/manual/2325107/Lg-Ct09f.html?page=123 Accessed November 2026.
  9. LG Electronics U.S.A. “Multi V 5 service manual, Error No. 35.” https://www.manualslib.com/manual/1483751/Lg-Multi-V5.html?page=157 Accessed November 2026.

Comments