Original data and independent reporting for the HVAC trade

What Is a Chiller? How HVAC Chillers Work, Types, Cost and Sizing

Technician inspecting a water-cooled centrifugal chiller in a commercial mechanical room, showing what a chiller is in a building HVAC system

What is a chiller? A chiller is a refrigeration machine that cools water, typically to 42°F to 45°F, then sends it to coils that cool a building’s air. It is the central cooling plant of large commercial buildings, not a household appliance, and EIA puts typical installed cost at $560 to $1,250 a ton in 2022 dollars, depending on type.

Key Takeaways

  • A chiller is “a refrigeration system that cools water,” per the DOE FEMP O&M Best Practices Guide.
  • Buildings with central chillers were 3.4% of US commercial buildings in 2018 but held 18.5% of the floorspace, by our tabulation of EIA’s 2018 CBECS microdata.
  • 41.0% of commercial buildings over 200,000 square feet used chillers in 2018, in the same CBECS tabulation.
  • Federal buyers must get a 300 to 399 ton water-cooled centrifugal chiller at 0.544 kW per ton or better at full load, per DOE FEMP.
  • Since January 1, 2025, new comfort-cooling chillers may not use an HFC refrigerant with a GWP of 700 or greater, under 40 CFR 84.54.
  • A magnetic-bearing centrifugal chiller cut electricity 42.3% against a rotary-screw unit in a 2012 PNNL test for GSA.
  • Typical installed cost runs $560 to $590 a ton for water-cooled centrifugal chillers and $820 to $1,250 for air-cooled screw units, in 2022 dollars, per EIA’s March 2023 equipment study.

What is a chiller in HVAC?

In HVAC, a chiller is the heart of a chilled-water system. It removes heat from water, and pumps carry that water to coils in air handlers and fan coils. The chiller never touches room air.

Chillers are sized in tons, and one ton is 12,000 Btu per hour of heat removal, the same unit used in sizing home air conditioners. The difference is scale: PNNL’s guide for DOE puts typical centrifugal chillers at 100 to 10,000 tons.

So chillers cluster in big buildings. Our weighted tabulation of EIA’s 2018 Commercial Buildings Energy Consumption Survey (CBECS) finds them in about 202,000 of 5.9 million commercial buildings, holding close to a fifth of floorspace, a clear line in how commercial HVAC differs from residential.

3.4%of US commercial buildings used central chillers, 2018Source: EIA 2018 CBECS microdata, HVAC Brief tabulation
18.5%of US commercial floorspace sat in buildings with chillers, 2018Source: EIA 2018 CBECS microdata, HVAC Brief tabulation
41.0%of buildings over 200,000 sq ft used chillers, 2018Source: EIA 2018 CBECS microdata, HVAC Brief tabulation
42°F to 45°Ftypical chilled water supply setpointSource: PNNL for DOE FEMP, O&M Best Practices Guide 3.0 (2010)

What are chillers used for?

Mostly for comfort cooling in large buildings, with the chilled water piped to air handlers and fan coils. The federal refrigerant rule in 40 CFR 84.54(a)(10) lists the other jobs by name, because each gets its own compliance date:

  • Comfort cooling: large commercial buildings; 41.0% of commercial buildings over 200,000 square feet used chillers in 2018, by our CBECS tabulation. New units have faced the GWP 700 limit since January 1, 2025.
  • Ice rinks: a separate category in the rule, also dated January 1, 2025.
  • Industrial process cooling: chillers that cool a fluid for machines or products, dated January 1, 2026 where the fluid leaving the chiller is warmer than -22°F (-30°C), and January 1, 2028 for -58°F to -22°F.
  • Semiconductor manufacturing: process chillers holding 100 pounds of refrigerant or less get until January 1, 2030.

Server rooms and data centers often draw on a building’s chilled water too, which is why chiller plant choices show up in data center efficiency ratios.

How does a chiller work?

A chiller works like any refrigeration machine, with water as the thing being cooled. Refrigerant absorbs heat from building water in the evaporator, the compressor raises its temperature, and the condenser dumps it outdoors. PNNL’s DOE guide names four parts:

  1. Evaporator. Liquid refrigerant boils on a tube bundle, pulling heat out of the chilled water inside the tubes.
  2. Compressor. It raises the vapor’s pressure, and with it the temperature.
  3. Condenser. Hot refrigerant gives its heat to condenser water or outdoor air.
  4. Expansion valve. Pressure drops back to evaporator level and the cycle repeats.
  5. The water loops. A pump sends the cold water, typically 42°F to 45°F, to air-handler coils; warmed water returns.

The loop runs on a circulating pump, and cooled air reaches rooms through ducts, often metered by variable air volume boxes. Raising the chilled water setpoint 1°F cuts chiller energy 1.7% for centrifugal and 1.2% for reciprocating machines, per PNNL, if coils can still dehumidify.

How a chiller moves heat out of a buildingAir handlersand fan coilscool building airCHILLERCondenserCompressorExpansionvalveEvaporatorrefrigerant loop insideHeat rejectioncooling tower (water-cooled) or outdoorair coil (air-cooled)heat outSolid: chilled water out, 42°F to 45°FDashed: warmer water returns
Components and the 42°F to 45°F setpoint range: PNNL O&M Best Practices Guide, Release 3.0, for DOE FEMP (2010).

How does a chilled-water plant connect the chiller, pumps, coils and tower?

Through two water loops. A chilled-water pump moves water from the chiller’s evaporator to the air handler coils and back; a condenser-water pump moves water from the chiller’s condenser to the cooling tower and back. An air-cooled chiller drops the second loop and rejects heat through its own fans.

Chilled-water plant: two water loopsNavy: chilled waterAHU coilcools room airCooling towerrejects heatby evaporationRed: condenser waterCHILLERCondenserrefrigerant circuitEvaporatorChilled-water pumpCondenser-waterpump44°F54°F85°Fto towerRating point (AHRI 550/590, per Carrier): chilled waterleaves at 44°F at 2.4 gpm per ton; condenser waterenters at 85°F at 3.0 gpm per ton. 54°F return isour arithmetic: 24 ÷ 2.4 = a 10°F rise.
HVAC chiller diagram of a water-cooled plant. Rating temperatures and flows: Carrier 30MP product data, citing AHRI Standard 550/590 standard rating conditions. Return temperature is our arithmetic from tons = GPM × ΔT ÷ 24 (Daikin Applied CAT 617-2). Diagram: The HVAC Brief.

In a real plant the pumps, valves and controls multiply: PNNL’s guide for DOE counts tower fans and both sets of pumps in the cost of making chilled water, which is why a chiller’s own kW per ton never tells the whole story.

How many GPM per ton does a chiller need? Tonnage calculator

At the AHRI 550/590 rating point a chiller moves 2.4 GPM of water per ton, leaving at 44°F, which works out to a 10°F rise across the evaporator. For water, tons = GPM × ΔT ÷ 24, the formula Daikin Applied prints in its chiller catalogs; solve it for any one of the three.

Chiller tonnage, GPM and ΔT calculator

Pick what to solve, fill in the other two. Water: tons = GPM × ΔT ÷ 24. Glycol adds Daikin Applied’s published flow factor.

Formula: Daikin Applied CAT 617-2 (tons = gpm × ΔT ÷ 24, water only). Glycol flow factors: Daikin Applied CAT 617-2, Tables 2 and 3, for its WGS chillers; glycol is outside AHRI certification. 1 ton = 12,000 Btu/h = 3.517 kW.

ΔT (°F) Water, GPM per ton Water, GPM for 100 tons 30% propylene glycol, GPM per ton
6 4.00 400 4.23
8 3.00 300 3.17
10 2.40 240 2.54
12 2.00 200 2.11
14 1.71 171 1.81
16 1.50 150 1.59

HVAC Brief calculation: GPM per ton = 24 ÷ ΔT, from Daikin Applied CAT 617-2 (water only). The glycol column multiplies by Daikin’s 1.057 flow factor for 30% propylene glycol in the same catalog, which Daikin publishes for its WGS chillers and which sits outside AHRI certification.

The 24 is shorthand. Longhand, tons = GPM × ΔT × 500 ÷ 12,000, where 500 is about 8.33 pounds per gallon × 60 minutes × 1 Btu per pound per °F, and 12,000 Btu per hour is one ton; 12,000 ÷ 500 = 24 (our arithmetic). The rating point itself comes from Carrier’s 30MP product data: evaporator leaving water 44°F at 2.4 gpm per ton, condenser entering water 85°F at 3.0 gpm per ton. The metric edition, AHRI 551/591-2026 (SI), instead fixes 12.00°C entering and 7.00°C leaving, about 53.6°F and 44.6°F, and lets the flow follow from those temperatures.

Two limits from the same product data: Carrier treats 5 gpm per ton, or a rise under 5°F, as the practical maximum evaporator flow because pressure drop climbs, and each model has its own minimum flow table. Glycol needs more flow for the same tons: Daikin’s factors run from 1.016 for 10% propylene glycol to 1.182 for 50% ethylene glycol.

An air-cooled chiller rejects heat to outdoor air through its own condenser fans, with no cooling tower.
An air-cooled chiller rejects heat to outdoor air through its own condenser fans, with no cooling tower. AI illustration.

Air-cooled vs water-cooled chiller: what is the difference?

An air-cooled chiller rejects heat through a finned coil and fans, like a giant rooftop condenser. A water-cooled chiller rejects heat into condenser water, which a cooling tower then cools by evaporation.

Type Where heat goes FEMP full-load level Share of chiller buildings, 2018 Share of chiller-building floorspace
Air-cooled Outdoor air, via fans and coil 10.964 EER at 150 tons and up (about 1.09 kW/ton) 56.0% 35.4%
Water-cooled Condenser water, then a cooling tower 0.566 kW/ton, centrifugal, 150 to 299 tons 44.5% 67.4%
Absorption Condenser water; driven by heat, usually steam Not covered by FEMP; about 1.6 Btu of heat per Btu removed 2.2% 4.1%

Sources: DOE FEMP Tables 2.1 and 3.1 (October 2024); kW/ton is 12 divided by EER, our arithmetic. Shares: our weighted EIA 2018 CBECS tabulation; buildings can report several types. Absorption: PNNL-19634.

Water-cooled machines win on the chiller’s own meter, roughly half the kW per ton of air-cooled ones in FEMP’s tables. That leaves out tower fans and pumps, which PNNL says belong in the cost of chilled water. Trane, a maker, says water-cooled units run quieter and air-cooled ones are easier to maintain. In data centers those plant choices show up in power usage effectiveness, the ratio of total facility energy to IT energy.

Water-cooled chillers sit in fewer buildings but cover two thirds of chiller floorspace, because they go into the largest ones. Server rooms in those buildings often tap the same chilled water through computer room air handlers, one of the options weighed in server room cooling. EIA separately reports that cooling towers served 3% of commercial buildings and 17% of floorspace in 2018.

What are the main types of chillers?

Types of chillers are named mainly by compressor: centrifugal, screw, scroll, reciprocating and the newer magnetic-bearing centrifugal. Absorption chillers run on heat instead. FEMP’s tables sort electric water-cooled units into two groups, centrifugal and positive displacement.

Chiller type How it works Where it fits Source
Centrifugal Spinning impeller, then a diffuser Typically 100 to 10,000 tons PNNL-19634
Screw (helical rotary) Two mating helical rotors squeeze the gas Historically dominated 100 to 300 tons PNNL-19634; PNNL for GSA
Reciprocating Pistons; positive displacement Almost always fixed-speed motors PNNL-19634
Scroll Orbiting scroll, positive displacement One of Trane’s three chiller compressor types (maker claim) Trane glossary
Magnetic-bearing centrifugal Oil-free shaft levitated on magnetic bearings, built-in variable speed drive Down to 60 tons PNNL for GSA
Absorption Heat drives a lithium bromide-water or ammonia-water cycle Sites with a steam or hot water supply PNNL-19634

The magnetic-bearing design has federal field data. In a PNNL assessment for GSA’s Green Proving Ground, a 150-ton chiller with Danfoss Turbocor compressors replaced a rotary-screw chiller at a federal courthouse in Pine Bluff, Arkansas. Weather-normalized use fell from 294,794 to 170,181 kWh per year, a 42.3% cut.

Part load explains most of it: the plant ran one chiller below 33% load for more than half the cooling season. It is one building monitored for six months in 2012, a demonstration, not a fleet average. Holding part-load efficiency in practice is a controls job, done by the building automation system that stages chillers and resets setpoints.

How efficient is a chiller? kW per ton and IPLV, worked out

Chiller efficiency is quoted in kW per ton, electric input per ton of cooling, so lower is better. IPLV, the integrated part-load value, is “a weighted average efficiency at specific partial load factors under rated conditions,” per the PNNL report for GSA. Both are tested under AHRI 550/590.

DOE’s commercial equipment rules in 10 CFR part 431 set no efficiency standard for comfort chillers. Minimums come from ASHRAE Standard 90.1 where an energy code adopts it. FEMP sets a higher federal purchasing bar at the 25th percentile of the most efficient products, paired with ASHRAE 90.1-2022 Path A or Path B minimums.

Water-cooled centrifugal, capacity Full load, kW/ton IPLV, kW/ton
Under 150 tons 0.610 0.550
150 to 299 tons 0.566 0.550
300 to 399 tons 0.544 0.520
400 to 599 tons 0.541 0.500
600 tons and up 0.501 0.500

Source: DOE FEMP, Table 3.1, full-load-optimized water-cooled electric chillers, updated October 2024. A chiller must meet both columns.

What the gap is worth, in FEMP’s example at 2,000 hours a year:

  1. A 300-ton chiller at 0.544 kW/ton draws 163.2 kW at full load, or 326,400 kWh a year.
  2. A less efficient 0.687 kW/ton model draws 206.1 kW, or 412,200 kWh a year.
  3. The difference is 85,800 kWh a year, about $8,500 at FEMP’s 9.9 cents per kWh.
  4. Over a 23-year life, discounted, FEMP puts the savings at $128,037.
Chillers: six numbers from the federal record0.544kW/ton FEMP level, 300 to399 ton centrifugal (DOE)412,200kWh a year at 0.687 kW/ton,vs 326,400 at 0.544 (DOE)$128,03723-year energy savings,300-ton example (DOE FEMP)42.3%less electricity, magnetic-bearing vs screw (PNNL/GSA)18.5%of US commercial floorspacein chiller buildings (EIA 2018)GWP 700refrigerant limit for newcomfort chillers (40 CFR 84.54)
Sources: DOE FEMP, Purchasing Energy-Efficient Electric Chillers, Tables 3.1 and 5 (October 2024); PNNL for GSA Green Proving Ground (November 2012); EIA 2018 CBECS microdata, HVAC Brief tabulation; 40 CFR 84.54 (eCFR, current October 2026).

How much does a chiller cost?

EIA’s equipment study puts the typical installed cost of a new commercial chiller at $560 to $1,250 per ton in 2022 dollars. Water-cooled centrifugal machines cost least per ton; air-cooled screw and scroll units cost more per ton but need no cooling tower. The figures were prepared by Guidehouse and Leidos as inputs for EIA’s energy model, so treat them as a planning range, not a quote.

Chiller type, typical size Equipment, $/ton Installed, typical, $/ton Installed, high efficiency, $/ton Maintenance, $/ton a year Average life
Water-cooled centrifugal, 400 to 600 tons 500 560 to 590 740 to 760 30 to 40 25 years
Air-cooled screw, 100 to 300 tons 770 to 1,130 820 to 1,250 920 to 1,350 20 to 50 20 years
Air-cooled scroll, 50 to 140 tons 530 to 1,060 860 to 1,170 960 to 1,270 40 to 60 20 years

Compiled by The HVAC Brief from EIA, Updated Buildings Sector Appliance and Equipment Costs and Efficiencies (March 2023), 2022 “Typical” and “High” columns, in 2022 dollars. EIA notes that its ranges span typical values for each parameter.

Worked example, our arithmetic: a 500-ton water-cooled centrifugal chiller at $560 to $590 a ton comes to $280,000 to $295,000 installed, in 2022 dollars. EIA’s centrifugal table describes the chiller; its note says water-cooled ratings leave out the cooling tower’s energy, and the table does not say the tower is in the price, so budget the cooling tower, condenser pumps and piping as separate lines. Prices have moved since 2022, as our HVAC equipment price index tracks.

Chiller vs AC, and chiller vs cooling tower: how do they differ?

An air conditioner cools air directly, with refrigerant boiling inside the coil the air passes over. A chiller adds a water loop: refrigerant cools water, and the water cools the air. That last step is the wet coil process plotted on a psychrometric chart, where air crossing a cold coil drops in both temperature and moisture. A cooling tower is not a chiller at all; it removes the heat a water-cooled chiller rejects. On a boat, a marine air conditioner skips both and dumps condenser heat straight into the water under the hull.

The water loop lets one central plant serve many air handlers through pipes. Most commercial buildings skip it: by our CBECS tabulation, packaged central units served 43.3% of commercial buildings in 2018, against 3.4% for chillers. VRF systems pipe refrigerant instead.

Process chiller vs HVAC chiller: what is the difference?

An HVAC chiller cools water for air conditioning coils and is rated at 44°F leaving water; a process chiller cools a fluid that cools a machine or a product, often colder, and usually arrives as one package with its own tank and pump. Federal refrigerant rules treat them as separate categories with separate dates.

Feature HVAC (comfort) chiller Process chiller
What it cools Water for air handler and fan coil coils A fluid loop serving machines or products
Leaving fluid temperature 44°F at the AHRI 550/590 rating point (Carrier 30MP) 20°F to 80°F standard range; glycol required below 48°F (Advantage portable line)
Typical size 50 to 600 tons in EIA’s cost tables 5 to 40 tons in Advantage’s portable line
Pump and tank Separate plant pumps for chilled and condenser water Built-in insulated reservoir tank and coolant pump (Advantage)
Federal GWP 700 limit for new units January 1, 2025 January 1, 2026 (leaving fluid warmer than -22°F); January 1, 2028 (-58°F to -22°F)

Compiled by The HVAC Brief from Carrier 30MP-4PD, Advantage Engineering portable chiller manual (I.O.M. 123, 2019), EIA (March 2023) and 40 CFR 84.54. One maker’s portable line is an example, not the whole process market.

The temperature difference drives the rest. In Daikin’s WGS catalog, leaving temperatures below 40°F require a glycol solution, and Daikin notes that glycol in the evaporator reduces the unit’s performance; Carrier’s 30MP data includes a brine rating at 15°F chilled fluid with 30% propylene glycol. A comfort chiller selected at 44°F is not automatically a process chiller at 20°F.

Refrigerant choice for new chillers is now set by federal GWP limits.
Refrigerant choice for new chillers is now set by federal GWP limits. AI illustration.

Which refrigerants can a new chiller use?

Since January 1, 2025, a new comfort-cooling chiller may not use a regulated HFC, or a blend containing one, with a global warming potential of 700 or greater. EPA’s Technology Transitions rule applies it to making, importing and installing chillers, under 40 CFR 84.54(a)(10)(i) and (c)(3).

What this rules out

HFC-134a carries an exchange value of 1,430 in Appendix A to part 84, about twice the limit. Paragraph (b) allows already-made restricted products to be sold for three years. Industrial process chillers follow later dates, starting January 1, 2026. The limits target new equipment, but paragraph (e) treats increasing an existing system’s cooling capacity as a new installation.

The use limits sit on top of the production cuts in the HFC phasedown schedule, which tighten supply for older chillers. Our refrigerant explainer covers the basics.

How we researched this

Research date: October 2026. We opened twelve sources and cite nine. CBECS shares are our weighted tabulation of EIA’s 2018 public-use microdata (6,436 sampled buildings), not EIA-published estimates; we computed no standard errors. Regulation text is the eCFR as of October 1, 2026. FEMP’s worked example calls its 300-ton chiller air-cooled, but its table uses water-cooled centrifugal kW/ton figures, which we follow.

Updated November 12, 2026: installed costs now come from EIA’s March 2023 equipment study (2022 dollars; a modelling input, not a price survey). AHRI 550/590 (I-P) still blocked our fetches, so the rating point is quoted from Carrier’s 30MP product data, and we read the free SI edition, AHRI 551/591-2026. The calculator formula and glycol factors are Daikin Applied’s, from catalog CAT 617-2; process chiller figures come from one Advantage Engineering manual. Excluded: contractor and vendor blogs, Wikipedia, and wine and beverage chillers. Maker statements are labeled as claims. No Reddit material was used.

Frequently asked questions

Is a chiller a fridge or a freezer?

Neither, in HVAC. A building chiller cools water for air conditioning, typically to 42°F to 45°F according to PNNL’s O&M guide for DOE, which is above freezing. A refrigerator’s chiller drawer or a beverage chiller is a different appliance sharing the name.

Is HVAC and a chiller the same thing?

No. HVAC is the whole heating, ventilating and air conditioning system; a chiller is one piece of cooling equipment that some HVAC systems use. Most commercial buildings have none: by our tabulation of EIA’s 2018 CBECS microdata, packaged units served 43.3% of commercial buildings and central chillers 3.4%. Schools follow the same pattern: packaged rooftop units cool about half of cooled K-12 buildings, while electric chillers are the main cooling in 12%, per our school HVAC statistics.

What is a chiller plant?

A chiller plant is the chillers plus everything that supports them: chilled-water pumps, condenser-water pumps, cooling towers and controls. PNNL’s DOE guide warns that tower fans and both sets of pumps belong in the cost of producing chilled water, not just the chiller’s own power draw.

Does a chiller need a cooling tower?

Only a water-cooled chiller does. An air-cooled chiller rejects heat to outdoor air through its own fans and coil. EIA reports that cooling towers served 3% of US commercial buildings, but 17% of commercial floorspace, in 2018, because they concentrate in the largest buildings.

How long does a chiller last?

There is no federal survey of chiller lifespans, but federal models assume 20 to 25 years: EIA’s 2023 equipment study uses 25 years for water-cooled centrifugal chillers and 20 for air-cooled screw and scroll units, and DOE FEMP assumes 23 years in its cost math. Trane, a manufacturer, says water-cooled chillers can last longer than air-cooled ones when properly maintained; treat that as a maker claim.

What maintenance does a chiller need?

PNNL’s O&M guide for DOE lists removing scale and fouling from heat transfer tubes, purging air from the condenser and keeping condenser water flow and filters clear. Each widens the temperature lift the compressor must overcome. Most of this is commercial service contract work, not a do-it-yourself job.

Sources

  1. Pacific Northwest National Laboratory for DOE FEMP. “Operations and Maintenance Best Practices: A Guide to Achieving Operational Efficiency, Release 3.0” (PNNL-19634), section 9.4. https://www.pnnl.gov/main/publications/external/technical_reports/PNNL-19634.pdf. Accessed October 2026.
  2. U.S. Energy Information Administration. “2018 CBECS Survey Data: Microdata.” https://www.eia.gov/consumption/commercial/data/2018/index.php?view=microdata. Accessed October 2026.
  3. U.S. Energy Information Administration. “Cooling towers in commercial buildings.” https://www.eia.gov/consumption/commercial/reports/2018/cooling/. Accessed October 2026.
  4. U.S. Department of Energy, FEMP. “Purchasing Energy-Efficient Electric Chillers.” https://www.energy.gov/eere/femp/purchasing-energy-efficient-water-cooled-electric-chillers. Accessed October 2026.
  5. PNNL for GSA Green Proving Ground. “Variable-speed Oil-free Centrifugal Chiller with Magnetic Bearings Assessment.” https://origin-www.gsa.gov/system/files/GPG_Mag_Lev_FullReport_508_6-17-13.pdf. Accessed October 2026.
  6. eCFR. “40 CFR 84.54, Restrictions on the use of hydrofluorocarbons.” https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/subpart-B/section-84.54. Accessed October 2026.
  7. eCFR. “Appendix A to Part 84, Regulated Substances.” https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84/appendix-Appendix%20A%20to%20Part%2084. Accessed October 2026.
  8. Trane (manufacturer). “What Is a Chiller?” https://www.trane.com/commercial/north-america/us/en/about-us/newsroom/glossary/chillers.html. Accessed October 2026.
  9. eCFR. “10 CFR Part 431” (searched for chiller standards). https://www.ecfr.gov/current/title-10/chapter-II/subchapter-D/part-431. Accessed October 2026.
  10. U.S. Energy Information Administration. “Updated Buildings Sector Appliance and Equipment Costs and Efficiencies” (March 2023), commercial chiller tables. https://www.eia.gov/analysis/studies/buildings/equipcosts/pdf/full.pdf. Accessed November 2026.
  11. Carrier. “AquaSnap 30MPA,MPW015-045 Liquid Chillers with Scroll Compressors, Product Data 30MP-4PD.” https://www.americancoolingandheating.com/wp-content/uploads/carrier-product-data-specifications/30mp-4pd.pdf. Accessed November 2026.
  12. AHRI. “Standard 551/591-2026 (SI), Performance Rating of Water-chilling and Heat Pump Water-heating Packages Using the Vapor Compression Cycle.” https://www.ahrinet.org/sites/default/files/AHRI%20551%20591-2026%20SI.pdf. Accessed November 2026.
  13. Daikin Applied. “Water-Cooled Screw Compressor Chillers, Catalog 617-2.” https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/CAT_617-2_WGS_03.31.2015_DA.pdf/. Accessed November 2026.
  14. Advantage Engineering. “Maximum Series Portable Chillers, 5 to 40 Tons, I.O.M. 123.” https://www.advantageengineering.com/pdf/manuals/advantage_Portable-Chillers-M1-5-40-Tons.pdf. Accessed November 2026.

Comments

7 responses to “What Is a Chiller? How HVAC Chillers Work, Types, Cost and Sizing”

  1. […] airports, offices, hospitals and hotels as common comfort cooling users, usually paired with a water-cooled chiller. It also lists oil refining, steel mills and power plants, where process towers sit beside […]

  2. […] name, two machines. In commercial work, a fan coil runs on water from a chiller plant or boiler. In home catalogs it means the indoor half of a split heat pump or air conditioner. […]

  3. […] AHU usually does not make its own heat or cold. Its coils typically carry chilled water from a chiller plant and hot water or steam from boilers, although some use refrigerant (DX) coils. Trane, a maker, […]

  4. […] A walk-in cooler is an insulated room with its own refrigeration, big enough to walk into. Federally it must be refrigerated above 32°F with under 3,000 square feet of chilled storage, per 10 CFR 431.302. At or below 32°F it is a walk-in freezer. Medical, scientific and research rooms are excluded, and water-cooling central plants are a different machine, the chiller that serves large buildings. […]

  5. […] cooling in high-density racks. Larger rooms on chilled water tie into the building’s chiller plant through computer room air […]

  6. […] air handler is often cooled by a chiller plant or is a rooftop unit. Each box trims that shared air with its own damper, a cousin of the control […]

  7. […] air handler is often cooled by a chiller plant or is a rooftop unit. Each box trims that shared air with its own damper, a cousin of the control […]

Leave a Reply

Your email address will not be published. Required fields are marked *