Amana Furnace Error Codes: Blinks, Light Colors and Display Codes by Board

Homeowner reading Amana furnace error codes through the sight glass of a basement gas furnace

Amana furnace error codes depend on the control board. On a single red LED, 3 blinks means the pressure switch never closed and 4 means an open limit. On a three color board, green and slow amber are normal status. On a display, EE0 is an ignition lockout and “1 dL” is IdL, normal idle.

Which Amana chart applies: one red LED, a three color LED or a display?

Look through the sight glass in the blower door before touching anything, because the same count means different faults on different boards. Amana’s service manuals print the warning on the chart itself: the “LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch” (RS6612016).

Blower door ON: look through the sight glass. What do you see? One red LED blinks, steady or off Three colors green, amber, red Letters and digits 3 character display AMSS9, AMES9, *MS8 Steady on = normal 1 to 8 blinks = fault Rapid = polarity Off = no power RS6612012, RS6612016 AMEC96 or AMES96*U Green = status Amber 1, 2 = heating Red = fault count Legends differ: plate! RS6612013, RS6612017 AM9S9x, AMVC96 IdL (“1 dL”) = idle EE0 to EE9 = faults E10, E11 = ground, rollout RS6612022R1, RS6612023 Dark LED or blank display on every board: 115 V power, 24 V power, the 3 A board fuse, then the board
How to pick the right Amana chart. Model families and legends from Amana and Goodman service manuals RS6612012, RS6612016, RS6612013, RS6612017, RS6612022R1 and RS6612023; the 3 A fuse is from the RS6612016 chart.

The model number on the rating plate settles it. In Amana’s nomenclature the first character is the brand: “A- Amana® G- Goodman®” (RS6612012). If the plate is unreadable, our serial number decoding guide shows where the label sits.

On single-LED Amana boards the fault is the number of red blinks between pauses.
On single-LED Amana boards the fault is the number of red blinks between pauses. AI illustration.

What do 2, 3, 4, 6 and 7 blinks mean on each Amana board?

Three blinks on a single red LED is the pressure switch failing to close; three red blinks on an AMEC96 is the same fault; EE3 on a display is an open limit, not a pressure switch.

Fault (Amana’s wording) Single red LED AMEC96 red LED Display Safe owner check Technician job
Lockout, ignition retries (3 total) 1 blink 7 (retries), 8 (recycles) EE0 Gas service on, filter clean Flame current, igniter, gas pressure
Pressure switch stuck closed 2 blinks 2 EE1 None Switch contacts, shorted wiring
Pressure switch not closed 3 blinks 3 EE2 Vent and intake ends clear Hose, drain, inducer, set point
Primary or auxiliary limit open 4 blinks 4; 11 if open over 5 minutes EE3 Filter, closed registers Temperature rise, blower speed
Flame sensed with no call for heat 5 blinks 1 EE4 Stop: leave it off Flame sense short, slow gas valve
Rollout limit open 6 blinks 4, or 5 after 15 minutes E11 Stop: do not reset Burners, flue, gas pressure
Control board fuse open 6 blinks (AMES9) 5 EE5 None Short in 24 V wiring, 3 A fuse
Low flame sense signal 7 blinks Rapid amber EE6 None; furnace may still run Clean and position sensor
Igniter circuit or poor ground 8 blinks 12 (igniter relay) EEL or EE7 None Igniter wiring, unit ground
Reversed 115 V polarity Rapid 9 EEA Stop: line voltage Hot and neutral at board
Gas valve powered with no call Not defined 10 EEC Stop: leave it off Gas valve circuit, board

Compiled by The HVAC Brief from RS6612012 (AMSS9), RS6612016 (AMES9), IO-359J (*MS8, *MH8), RS6612013 (AMEC96), RS6612022R1 (AM9S92, AM9S96) and RS6612023 (AMVC96 *BB). EEL is the AM9S code, EE7 the AMVC96 *BB code. On AMSS9, 6 blinks is rollout only. The owner and technician columns are our reading of Amana’s corrective actions.

Seven blinks is the trap. On an AMSS9 or AMES9 it is a low flame signal, and Amana lists the symptom as “Normal furnace operation”, so the furnace keeps heating while it warns. On an AMEC96, seven red flashes is a hard lockout. The flame sensor is the first suspect for 1 or 7 blinks.

Three blinks is the most common no heat call in winter. Amana’s RS6612012 says if the pressure switch “does not close within 5 minutes, the control will go into a 1-hour lockout”, and lists a disconnected hose, a bad switch or “restricted air intake or flue piping”. Snow over the two PVC terminations outside is the owner check; our pressure switch guide covers the hose and drain tests.

Four blinks means the limit switch opened from heat. Amana names “dirty filter or resistance in duct work, faulty limit, faulty blower, or blower speed set to low” in RS6612016, so a filter swap and opening closed registers come before any parts.

Is a blinking green, amber or orange light on an Amana furnace a fault?

Usually not. Only two Amana boards in the manuals we read have green and amber LEDs, the AMEC96 and the Ultra Low NOx AMES96*U, and on both green reports status. Amber (what most owners call orange or yellow) reports heating on the AMEC96 and a few faults on the AMES96*U.

Light AMEC96 (RS6612013) AMES96*U (RS6612017)
Green steady Waiting for a call Standby, no thermostat requests
Green 1 / 2 / 3 Low cool / high cool / not listed Call for heat / cool / continuous fan
Green rapid Fan only (24 V on G) Clearing error history
Amber 1 / 2 Normal low / high stage heat Low flame sense / ID plug failure
Amber 3 W2 call present without W1 Control fuse open
Amber 4 Y call present without G Not listed
Amber rapid Low flame sense current Field test mode
Red steady Control board internal fault Control fault, hard lockout

Compiled by The HVAC Brief from the RS6612013 troubleshooting chart and the RS6612017 wiring diagram legend.

Amber 3 and amber 4 on an AMEC96 are thermostat wiring faults, not furnace faults: Amana’s fix is the thermostat or “improperly connected thermostat wires”. One internal inconsistency to know: the RS6612013 sequence of operation says standby shows “a slow green flash”, while its chart lists green “Solid ON”. Both mean waiting for the thermostat.

On the AMES96*U, one amber flash is a measured threshold. RS6612017 says the controls run 3 to 10 microamps of flame current, “1-3 uAmps is considered low and will flash 1 amber light”, and below 1 microamp the unit shuts down.

What do EE0, EE3 and “1 dL” mean on an Amana display?

“1 dL” is IdL on a seven segment display, and Amana’s chart lists it as “Normal operation”. EE0 is the ignition lockout, EE3 an open primary limit, and E11 an open rollout switch. The EE numbers run one behind the single LED blink counts for the first seven faults.

Blink count minus one = EE number (first seven faults) Blinks Display Fault 12345678 EE0EE1EE2EE3EE4EE5EE6EEL LockoutSwitchclosedSwitchopenLimitopenStrayflameFuseopenLowflameIgniterground 6 blinks also means open rollout; the display gives rollout its own code, E11. AMVC96 *BB prints igniter as EE7; AM9S92 and AM9S96 print EEL.
HVAC Brief crosswalk of the IO-359J and RS6612016 single LED legends against the RS6612022R1 and RS6612023 display charts.

Display furnaces add codes no LED board has. RS6612023 for the AMVC96 *BB lists EEF as “Aux switch (condensate switch) open” with “High water level in the evaporation coil”, EEd as an auxiliary limit open in the blower compartment, EE8 and EE9 for the high stage pressure switch and Eb codes for the blower. EEF is the one an owner can act on: check the coil drain pan and trap.

To read stored faults on an AM9S92 or AM9S96, press the left or right switch “until L 6 F is displayed”, then the center switch. Holding the center switch 5 to 30 seconds erases them, per RS6612022R1. RS6612014R1 confirms the earlier AMVC96 *BA also shows lockout as EE0. No Amana document we opened defines 7P1 or 9H, and none treats “1 dL” as a fault.

Are Amana furnace error codes the same as Goodman’s?

Yes, for every shared chassis. The service manual covers both brands in one document: RS6612013 is titled for “Goodman® Brand GMEC96 & Amana® Brand AMEC96”, and RS6612022R1 covers GM9S96 and AM9S96 together. Same board, same chart, so our Goodman furnace error codes page applies to the matching Goodman model. Both brands sit under one parent, set out in our HVAC brand ownership table.

Rollout, gas valve and flame-sensed-with-no-call codes are shut-off-and-call codes, not reset-and-retry.
Rollout, gas valve and flame-sensed-with-no-call codes are shut-off-and-call codes, not reset-and-retry. AI illustration.

Which Amana codes mean shut it off, and which can you reset?

A lockout (1 blink, 7 or 8 red on an AMEC96, or EE0) can be reset. Amana lists three ways in RS6612013: wait for the one hour automatic reset (our furnace reset guide compares makers), interrupt 115 volt power for 1 to 20 seconds, or drop the thermostat setting for 1 to 20 seconds.

Do not reset 5 or 6 blinks on a single LED, red 1, 10 or a rapid red, EE4, EEC or E11. Those are flame where there should be none, a rollout, a gas valve powered out of turn or reversed 115 V polarity. If you smell gas, Amana’s manuals say: “Do not touch any electric switch”; leave and call the gas supplier from outside. A dark LED starts at the 3 A fuse, not a new control board: RS6612016 says to replace the board “only” after “all other checks from the Troubleshooting Chart have been verified.”

Frequently asked questions

Why is my Amana furnace blinking a red light?

On a single red LED board the blink count is the fault: 1 is a lockout, 3 a pressure switch that did not close, 4 an open limit. A steady red light is normal on AMSS9 and AMES9 furnaces, per RS6612016, but on an AMEC96 a steady red is a control board internal fault, and RS6612013 says to replace the board.

What does Amana furnace code 7 mean?

It depends on the board. Seven blinks on a single red LED is a low flame sense signal while the furnace keeps running. Seven red flashes on an AMEC96 is a lockout from “excessive retries” with no flame proven. On an AMES96*U, red 7 is a shorted gas valve circuit. On an AMVC96 *BB display, EE7 is an igniter circuit problem.

Is there an Amana furnace error codes list PDF?

Not one list for every model. Each Amana series has its own chart inside a Goodman Manufacturing service manual: RS6612012 for AMSS9, RS6612016 for AMES9, RS6612013 for AMEC96, RS6612022R1 for AM9S92 and AM9S96, and RS6612023 for AMVC96 *BB.

How do I see past fault codes on an Amana AMEC96?

Press the LAST ERROR button for more than 1/5 second and less than 5 seconds; the LED flashes up to five stored codes, newest first. Two green flashes mean memory is empty. Holding the button 5 to 10 seconds clears the memory, confirmed by three green flashes, according to RS6612013.

How we researched this

In November 2026 we read eight Amana and Goodman service and installation manuals covering AMSS9, AMES9, AMES96*U, AMEC96, AM9S92, AM9S96, AMVC96 and the *MS8 family, rendering chart pages as images where codes print as graphics. The three ranking code sites we opened cite no maker document and were excluded; one lists a steady light as “No signal from the thermostat”, which Amana’s own chart calls normal operation. Older Amana furnaces built before the current Goodman platforms were not covered by any manual we opened, so their codes are not listed here.

Sources

  1. Goodman Manufacturing. “GMSS9*/GCSS9*/AMSS9*/ACSS9* Service Instructions, RS6612012.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612012.pdf. Accessed November 2026.
  2. Goodman Manufacturing. “GMES9*/GCES9*/AMES9*/ACES9* Service Instructions, RS6612016.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612016.pdf. Accessed November 2026.
  3. Goodman Manufacturing. “*M(H,S)8 Installation Instructions, IO-359J.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/IO-359J.pdf. Accessed November 2026.
  4. Goodman Manufacturing. “Goodman Brand GMEC96 and Amana Brand AMEC96 Service Instructions, RS6612013.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612013.pdf. Accessed November 2026.
  5. Goodman Manufacturing. “*MES96*U Service Instructions, RS6612017.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612017.pdf. Accessed November 2026.
  6. Goodman Manufacturing. “GM9S92/GM9S96/AM9S92/AM9S96 Service and Troubleshooting, RS6612022R1.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612022R1.pdf. Accessed November 2026.
  7. Goodman Manufacturing. “ACVC96*BB/AMVC96*BB/GCVC96*BB/GMVC96*BB Service and Troubleshooting, RS6612023.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612023.pdf. Accessed November 2026.
  8. Goodman Manufacturing. “ACVC96*BA/AMVC96*BA Service Instructions, RS6612014R1.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612014R1.pdf. Accessed November 2026.