Goodman Furnace Error Codes: Every Flash and Display Code by Control Board

Technician checking a furnace control board in a basement while tracing Goodman furnace error codes

Goodman furnace error codes change with the control board: 3 flashes on a single red LED is a pressure switch stuck open, 10 red flashes on a GMEC96 is gas valve current with no call for heat, and EE3 on a display is an open limit. 9H and F02 are not faults.

Which Goodman board shows 4 flashes, E3 or EE3 for the same fault?

All three are the same limit fault in different notation. RS6612014R1 explains the display change: an active alarm is reported “starting with” E, then the two digit alarm code, so the older E3 reads EE3 and b4 reads Eb4.

Fault Single red LED GMEC96 red LED Older dual display Three character display
Ignition lockout 1 flash 7 (retries), 8 (recycles) E0 EE0
Low pressure switch stuck closed 2 flashes 2 E1 EE1
Low pressure switch open 3 flashes 3 E2 EE2
Open limit 4 flashes 4 or 11 E3 EE3
Flame with no call for heat 5 flashes 1 E4 EE4
Open rollout switch 6 flashes 4 or 5 E3 E11
Open control fuse 6 flashes* 5 E5 EE5
Low flame signal 7 flashes Rapid amber E6 EE6
Igniter or ground problem 8 flashes* 9, 12 E7 EE7 or EEL
Reversed polarity Rapid flash 9 EA EEA
High pressure switch stuck closed None None E8 EE8
High pressure switch open 9 flashes** 3 double E9 EE9
Gas valve on when it should be off None 10 None EEC
Internal control fault LED off Solid red Display off EEE

Compiled by The HVAC Brief from RS6612012, RS6612016, IO-359J, RS6610004, RS6612013, RS6612014R1, RS6612015, RS6612020, RS6612022R1, RS6612023 and IOG-2038E. *The GMSS9 chart lists 6 as rollout only and stops at 7. **GMV8, GCV9, GMV9 only.

Do you have a red LED, a tri-color LED or a display?

Check through the sight glass in the blower door, because numbers do not carry across boards: 7 flashes is a low flame signal on a GMES9, an ignition lockout on a GMEC96, and EE7 is an igniter problem. Trane furnaces split the same way between LED boards and display boards, as the Trane furnace error codes show.

What is the board showing?Board family and where to readOne red LED that blinksGMS8, GMH8, GMES9, GMSS9Use the flash count tableGreen, amber and red LEDsGMEC96, AMEC96, *MES96*UUse the 10 flash sectionTwo characters: E3, b4, OPOlder GMVC, GCVC dual displayUse the E columnThree characters: EE3, Eb4, IdLGM9S, GM9C, *R9T96, GMVC96 *BAUse the EE columnNothing lit at allNo 115 V, no 24 V or open fuseCheck breaker and door first
An asterisk stands for the brand letter. Sources: RS6612016, RS6612013, RS6610004, RS6612022R1, IOG-2038E.
On a single red LED board, the flash count points to circuits like the pressure switch, not to a part that has already failed.
On a single red LED board, the flash count points to circuits like the pressure switch, not to a part that has already failed. AI illustration.

What do 2 blinks, 3 blinks and other flash counts mean on a single red LED?

Two blinks mean the pressure switch is stuck closed; three blinks mean it never closed after the inducer started. Counts come from RS6612012 (GMSS9), RS6612016 (GMES9) and IO-359J (GMS8, GMH8, GDS8, GDH8, GHS8, GME8). A steady light is normal operation in all three, not the thermostat fault several ranking pages describe.

Flashes Goodman’s meaning Owner can check, power off Technician tests
Steady on Normal operation Nothing Nothing
Off Control failure or no power Breaker, switch, door seated 115 V at board, 24 V at transformer
1 Lockout, 3 ignition tries failed Filter; gas service on Flame current (1 to 4 microamps), igniter, gas pressure
2 Pressure switch stuck closed Nothing Ohm the switch, wires off
3 Pressure switch stuck open Vent and intake ends clear Hose, inducer, drain, switch set point
4 Open high limit Filter; registers open Temperature rise, blower speed
5 Flame sense without gas valve Stop: leave it off Sense circuit short, slow gas valve
6 Open rollout or open fuse Stop: do not reset Burners, flue, low voltage short
7 Low flame signal Book service Sensor position, gas pressure
8 Check igniter or improper ground Nothing Igniter wiring, ground to panel
Rapid Reversed 115 VAC polarity Stop: line voltage Hot and neutral at board

Compiled by The HVAC Brief from those manuals; the owner column is our reading of Goodman’s corrective actions.

The parts behind the codes have their own pages: the flame sensor for 1 or 7 flashes, the limit switch for 4 and the igniter for 8. RS6610004 adds a ninth count on older GMV8, GCV9 and GMV9 furnaces: the high stage pressure switch not closing.

The Ultra-Low NOx *MES96*U legend differs: red 6 is auxiliary limit open, red 7 is gas valve circuit shorted, and amber 3 is control fuse open.

What do 10 flashes mean on a Goodman furnace?

Ten repeating red flashes on a GMEC96 or AMEC96 mean gas valve current detected with no call for heat, per RS6612013. The technician verifies the valve is not getting voltage from a short; if the valve wiring is correct, Goodman says to replace the control board. Leave the furnace off until then. Amana sells the same chassis under its own badge, and the Amana furnace error codes match each Amana board to the Goodman chart it shares.

Red flashes Goodman’s fault description
1 Flame sensed when no flame should be present
2 Pressure switch stuck closed
3 Low fire pressure switch stuck open
4 Open limit circuit: main, aux or rollout
5 Limit and rollout open 15 minutes, or open fuse
6 Pressure switch opened 5 times in one heating cycle
7 Lockout: flame not proven during ignition trial
8 Lockout: flame lost after being proven
9 Improper grounding or reverse polarity
10 Gas valve current detected with no call for heat
11 Open limit circuit for more than 5 minutes
12 Control board igniter relay not energizing igniter
Solid Control board internal fault
Rapid Twinning error
3 double Second stage pressure switch stuck open

Compiled by The HVAC Brief from RS6612013.

Amber mostly reports normal running here: one or two amber flashes are low and high stage heat. Three amber (W2 without W1) and four amber (Y without G) point at thermostat wiring.

Which Goodman display codes go beyond EE0 through EEA?

Newer boards add condensate, relay, blower and R-32 codes. RS6612023 (GMVC96 *BB) and IOG-2038E (*R9T96) define them, RS6612022R1 (GM9S) carries a shorter set, and only EEF and EEd have an owner check: the drain pan and the filter.

Code Goodman’s meaning
EEF Condensate switch open, high water in the evaporator coil
EEd Auxiliary limit open in the blower compartment
EEb Control not energizing the gas valve when it should
EEn Igniter open
EEJ Inducer relay error
EEH Twinning error
E10 Grounding fault, poor neutral
E12, E13 Redundant relay open, stuck closed
EbL, EbU Blower motor current too low, too high
Ed8 ODS setting does not match the outdoor unit
EAL R-32 sensor detected a refrigerant leak
EAF, EAS, EAr R-32 sensor lost, sensor fault, A2L relay issue

Compiled by The HVAC Brief from RS6612023 page 57, IOG-2038E pages 49 to 52 and RS6612022R1 page 30. On EEb, IOG-2038E says not to replace the gas valve.

Blower and data codes (Eb and Ed on three character displays)

b0 motor not running. b1 communication lost. b2 horsepower mismatch. b3 motor limiting. b4 current trip or lost rotor. b5 locked rotor. b6 voltage or temperature trip. b7 incomplete parameters. b9 low airflow. d0 no shared data. d4 invalid memory card data.

Are 9H, F02 and 7P1 Goodman furnace error codes?

No. A lowercase g on a seven segment display looks like a 9, and IOG-2038E prints the same status as gH: the furnace is in gas heat. F02 is a blower speed number, and RS6612022R1 lists it as the default heating speed on GM9S boards. No Goodman document we read defines 7P1, so we will not guess at it.

Display What it means
9H or gH Gas heat, single stage
9H1, 9H2 Gas heat, low stage, high stage
IdL or OP Idle; normal operation on older displays
F01, F02 Blower speed numbers in a setup menu
L6F, F10 Menus holding the last 6 or last 10 faults

Sources: RS6612022R1, RS6612020, RS6612023, RS6610004, IOG-2038E.

A clogged filter can cause limit trips, so it is the first thing to check before anyone resets a lockout.
A clogged filter can cause limit trips, so it is the first thing to check before anyone resets a lockout. AI illustration.

How do you read a Goodman code before the door switch wipes it?

Read it through the sight glass with the door on. RS6612016 warns that “failure to hold the door switch closed while removing the blower compartment door will result in the loss of the stored failure code.”

Door on: read the code through the sight glassBreaker115 V supplyDoor switchClosed: door onControl board24 V circuitsLED or displayThe codeDoor off: the switch opens and the board loses powerBreaker115 V supplyDoor switchOpen: door offControl boardNo powerLED or displayCode goneHold the switch closed while removing the door to keep the stored code
Simplified power path. Goodman’s footnote: “LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.” Sources: IO-359J, RS6612016.
Board See stored faults Clear them
Single LED, IO-359J In standby, hold button 2 seconds: last 5 Hold 6 seconds
GMEC96 Press LAST ERROR under 5 seconds Hold 5 to 10 seconds
GM9S, GM9C Side button to L6F, then center Hold center 5 to 30 seconds
*R9T96 Side button to F10, then center Hold center 5 to 30 seconds

Sources: IO-359J, RS6612013, RS6612022R1, RS6612020, IOG-2038E.

Can you reset a Goodman lockout, and when should you stop?

Yes, for a lockout. IO-359J lists a one hour automatic reset, cutting 115 volt power for 1 to 20 seconds, or lowering the thermostat for 1 to 20 seconds. Our furnace reset guide compares makers.

Stop for 5 or 6 flashes, EE4, E11, EEC, 10 red flashes or EAL: rollout, stray flame, a gas valve powered out of turn or leaking refrigerant. RS6612014R1 says “Never by-pass or alter furnace controls.” If you smell gas, Goodman says touch no electrical switch and call the gas supplier from a neighbor’s phone.

Check before buying a control board: on EEE, IOG-2038E says “Do not replace additional components based on this error code.” A dark board starts at the 24 volt transformer. Carrier furnace codes do not translate to Goodman.

Frequently asked questions

Is there a Goodman furnace error codes list PDF?

No single PDF covers every board. Goodman publishes a chart per furnace series: RS6612012 for GMSS9, RS6612016 for GMES9, RS6612013 for GMEC96, RS6612022R1 for GM9S and RS6612023 for GMVC96 *BB. RS6612017 also says to always refer to the wiring diagram on the unit, because wiring is subject to change.

Does a solid red light on a Goodman furnace mean a fault?

On a single red LED board, no: RS6612016 lists steady on as normal operation, with no action needed. On a GMEC96, yes: RS6612013 lists a solid red LED as a control board internal fault and says to replace the control board. On a *MES96*U, steady red is a hard lockout.

What does EE5 mean on a Goodman furnace?

EE5 means an open fuse on the control board, with a short in the low voltage wiring as the listed cause. RS6612023 calls for a 3-amp automotive type replacement. IOG-2038E adds a less obvious cause: the back of the control board touching the mounting panel because the standoffs are missing.

How we researched this

We read twelve Goodman service and installation manuals in November 2026, viewing chart pages as images where codes print as graphics. Contractor blogs and code aggregators were excluded because their flash lists conflict with the manuals. Charts differ by series and revision, so match your rating plate model to its manual.

Sources

  1. Goodman. “GMSS9 Service Instructions, RS6612012.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612012.pdf. Accessed November 2026.
  2. Goodman. “GMES9 Service Instructions, RS6612016.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612016.pdf. Accessed November 2026.
  3. Goodman. “GMS8, GMH8 Installation Instructions, IO-359J.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/IO-359J.pdf. Accessed November 2026.
  4. Goodman. “Service Instructions, RS6610004 (distributor copy).” https://s3.amazonaws.com/s3.supplyhouse.com/product_files/Goodman-GMS951155DXA-Install-Instructions.pdf. Accessed November 2026.
  5. Goodman. “GMEC96 Service Instructions, RS6612013.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612013.pdf. Accessed November 2026.
  6. Goodman. “*MES96*U Service Instructions, RS6612017.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612017.pdf. Accessed November 2026.
  7. Goodman. “GMVC96 *BA Service Instructions, RS6612014r1.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612014R1.pdf. Accessed November 2026.
  8. Goodman. “GMVM97 *BA Service Instructions, RS6612015.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612015.pdf. Accessed November 2026.
  9. Goodman. “GM9S Service and Troubleshooting, RS6612022r1.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612022R1.pdf. Accessed November 2026.
  10. Goodman. “GM9C96 Service and Troubleshooting, RS6612020.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612020.pdf. Accessed November 2026.
  11. Goodman. “GMVC96 *BB Service and Troubleshooting, RS6612023.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612023.pdf. Accessed November 2026.
  12. Goodman. “*R9T96 Installation Instructions, IOG-2038E.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/IOG-2038E.pdf. Accessed November 2026.

Comments

2 responses to “Goodman Furnace Error Codes: Every Flash and Display Code by Control Board”

  1. […] even though Carrier’s group holds all three names. Use your own door label, and do not read Goodman’s codes with this […]

  2. […] the three notations on our Goodman furnace error codes page, Rheem keeps the meaning of 11, 22, 33, 61 and 93 across […]

Leave a Reply

Your email address will not be published. Required fields are marked *