Frigidaire furnace error codes are light patterns on a Nordyne control board, and the meaning depends on the board. Older boards flash one red LED 1 to 5 times; 4 flashes means ignition failure, check ground. The 2024 *SA and *SK manual uses green and red light pairs instead, or 1 to 12 red flashes on an Emerson board.
Which Frigidaire board do you have: one red light, a green and red pair, or up to 12 red flashes?
Read the label inside the furnace door before opening anything, because older boards forget. Nordyne’s G6RA/G6RK service manual says the red light “must be observed before the bottom door is removed since the board does not store the fault condition in its memory.”
Nortek’s January 2024 installation instructions, form 1041595B, cover the *SA upflow and *SK downflow series and print two different charts on page 32: Table 9 for a Nordyne/UTEC board and Table 10 for an Emerson board. Frigidaire’s Essentials series page lists FG7SA and FG7SK at 80% AFUE. So two furnaces with one badge can blink the same count for different faults.

What does each red flash count mean on a Frigidaire furnace, board by board?
Count the flashes between pauses and read only your label’s column. “None” means that Nordyne manual lists no such count; never borrow the next column’s meaning.
| Red LED | Older house boards: G6RA/G6RK, *RA/*RK, G6RC | Manufactured home: M3RL (M1M where it differs) | Emerson board, *SA/*SK (2024) |
|---|---|---|---|
| Steady on | Power on, normal | Power on (M1M: control OK) | Normal operation |
| 1 | Limit circuit open or external load on “W” | Limit circuit open or external load on “W” | System lockout (retries exceeded) |
| 2 | Pressure switch open with inducer on | Pressure switch open with inducer on | Pressure switch stuck closed |
| 3 | Pressure switch closed with inducer off | Pressure switch closed with inducer on (M1M: stuck closed) | Pressure switch stuck open |
| 4 | Ignition failure (check ground) | Ignition failure (check ground) | Open high temperature limit switch |
| 5 | 115 VAC and neutral reversed, or no ground | 115 VAC and neutral reversed, or no ground | Flame sensed over 4.25 seconds with gas valve off |
| 6 | none | none | Open flame rollout switch |
| 7 | none | none | Low flame sense signal (not stored) |
| 8 | none | none | Igniter relay fault |
| 9 | none | none | Twinning fault (not stored) |
| 10 | none | none | Open fuse |
| 11 | none | none | Igniter open |
| 12 | none | none | Inducer relay error |
| Continuous or rapid flash | False flame or gas valve relay shorted | False flame or gas valve relay shorted (M1M: or internal control fault) | Rapid flash: reverse polarity |
| Off | Power off | Power off or deck limit open (M1M: no power) | Control failure or no power; or gas heating lockout |
Two rows cause most misreads. On the older boards 4 flashes is “Ignition Failure (Check Ground)”, while Table 10 of the 2024 Emerson chart gives 4 flashes as “Open High Temperature Limit Switch” and 1 flash as “System Lockout (Retries Exceeded)”. The chart decides whether the technician starts at the furnace limit switch or at the igniter and flame sensor.
Frigidaire furnace blinking green light: what does each green and red pair mean?
A blinking green light is read together with the red LED, never alone. Nordyne’s FG7TC specification sheet describes a “Dedicated light for flame signal strength and 2 lights in combination to indicate all other fault codes” that you read as states, “without counting flashes.”
| Green LED | Red LED | Nortek’s meaning | Part it points to |
|---|---|---|---|
| On | On | Normal operation | None |
| Flash | Off | Open limit switch fault | Limit circuit: airflow, filter, blower |
| Flash | On | Pressure switch open fault | Inducer, pressure hose, vent |
| On | Flash | Pressure switch closed fault | Pressure switch contacts |
| On | Off | Motor fault | Blower or inducer motor circuit |
| Flash | Flash | L1/neutral polarity fault | 115 V supply wiring |
| Alternating flash | 1 hour lockout | Repeated failed ignition | |
| Off | Off | Control fault (no power) | Breaker, switch, board fuse |
Green flashing with red steady is a pressure switch that never closed; green steady with red flashing is one that never opened. The first points at the inducer and vent, the second at the switch, as the furnace pressure switch page explains.
Does a flashing yellow flame light mean the flame sensor is dirty?
It means the board sees a weak flame signal, and a coated sensor is the first suspect. The G6, *RA/*RK, M3RL and UTEC charts call a continuously flashing yellow light “Low Flame Sensor Signal”. The G6RA/G6RK service manual sets the thresholds: the light “will come on solid with a flame signal of 1uA or more”, blinks at a weak signal, and goes out at “.5 uA or less.”
On the 2024 Emerson chart the same condition is 7 red flashes, not stored. Nortek’s troubleshooting list asks “Is the flame sensor coated?” and says to remove and clean it with steel wool. The furnace flame sensor guide covers the microamp test.
Why does an older Frigidaire flash 4 times, and where in the start-up does each code trip?
Four flashes on an older board means five ignition tries failed. Nordyne’s 708291B instructions for the *RA and *RK series say the board must prove flame 5 seconds after the gas valve opens; “on the fifth try for ignition, the furnace control is locked and the red LED will blink 4 times repetitively.” The G6RA/G6RK service manual allows 6 seconds.
Ground also drives the 5 flash code, “115 VAC & Neutral Reversed or no Ground.” Nortek’s 2024 manual says incoming neutral goes to the white wire and hot to the black; proving that takes a meter on 115 volt wiring, a job for a technician or electrician.

How do you reset a Frigidaire furnace code, and which codes mean stop?
For a lockout, turn the thermostat off or below room temperature for at least ten seconds; 708291B says the furnace otherwise “will attempt another ignition sequence in 1 hour.” Nortek’s 2024 manual says the *SA/*SK furnace “will lock out after 5 failed attempts for ignition and will try again every hour if the call for heat remains.” Our how to reset a furnace guide lists when to stop.
Read the code first. The Emerson board keeps codes 1 to 6, 8 and 10 to 12 “stored in memory (auto-erased after 14 days)”, per the wiring diagram in 1041595B; codes 7 and 9 are not stored. The older boards store nothing, so read the furnace control board lights before the bottom door comes off.
Stop and close the furnace gas valve for a continuous red flash on an older board (“False Flame or Gas Valve Relay Shorted”; G6 Table 6: both fans keep running) and for 5 flashes on the Emerson board, flame sensed over 4.25 seconds with the gas valve off. Six Emerson flashes is an open flame rollout switch. Nortek calls the rollout switch manually reset and says: “DO NOT install jumper wires across these switches.” If you smell gas, leave first: see furnace smells like gas.
A JustAnswer thread ranking for this query told an owner with 1 flash to touch a limit switch’s two wires together. Nordyne’s Table 6 says 1 flash keeps the blower and inducer running until the limit closes: find the airflow problem instead.
Do Intertherm, Miller, Philco, Maytag and Westinghouse furnaces read the same chart?
Often, but the door label is still the authority. Nordyne called itself the “manufacturer of Intertherm and Miller products” in its G5RC user’s manual, and a 2013 distributor catalog gives the Philco KG7 and Frigidaire FG7 the same “Diagnostic lights” text and sells kits for Frigidaire “G6” furnaces. The FG7SC, FG7SD, FG8SA and FG8SD sheets linked from Frigidaire’s Essentials page carry “© Nordyne, LLC 2024”, and our who makes HVAC brands table traces Maytag, Gibson and Intertherm to the same maker.
Manufactured homes diverge most: the M3RL condensing furnace adds “Deck Limit Open” to its off state, and the M1B uses 1 and 2 flashes for an inducer centrifugal switch. The mobile home furnace guide covers HUD rules, and Coleman furnace error codes cover the other common closet brand. We opened no Broan, Gibson or Tappan furnace manual, so whether those boards match is unconfirmed.
Frequently asked questions
Is there a Frigidaire furnace error codes PDF?
Yes. Nortek’s installation instructions 1041595B for the *SA and *SK series (36 pages, January 2024) hold the Nordyne/UTEC and Emerson charts in Tables 9 and 10 on page 32. For older *RA and *RK furnaces, Nordyne’s 708291B prints the single red LED chart. The label inside your door is the copy matched to your board.
What are some common Frigidaire error codes?
No maker publishes how often each code appears. On older boards the codes tied to parts that wear or clog are 1 red flash (limit circuit), 2 or 3 flashes (pressure switch), 4 flashes (ignition failure after five tries) and a continuously flashing yellow light for a low flame sensor signal.
What does a solid red light on a Frigidaire furnace mean?
Usually normal. The older Nordyne chart lists “Power On” as steady red, the 2024 Emerson chart lists “Continuous On” as normal operation, and green and red both on is normal on the Nordyne/UTEC board. The exception: on that UTEC board, green flashing beside a steady red light is a pressure switch open fault.
What does it mean when the orange light on my furnace is blinking?
On a Frigidaire, the only lamp on Nordyne’s charts that is neither red nor green is the yellow FLAME light. A continuous flash reads “Low Flame Sensor Signal”; steady means flame present. The G6RA/G6RK service manual says it stays solid at 1 microamp or more and goes out at 0.5 microamp or less.
How we researched this
On November 14, 2026 we read seven Nordyne and Nortek manuals, Frigidaire’s furnace pages and six Nordyne spec sheets (listed below). Every table row comes from those charts; the G6RC chart matched the G6RA/G6RK chart. We excluded forum and lead-gen code lists, which cite no maker document, and the restricted FG7S(A,K) sheet.
Sources
- Nortek Global HVAC. “*SA/*SK Installation Instructions, 1041595B” (01/24), Morley Associates copy. https://www.morleyassociates.com/wp-content/uploads/2024/09/FG7SA-Install-Manual.pdf. Accessed November 2026.
- Nordyne. “*RA/*RK Installation Instructions, 708291B” (03/04). https://files.rheem.com/LiteratureArchive/708291b.pdf. Accessed November 2026.
- Nordyne. “G6RA, G6RK Service Manual” (12/97), archived copy. https://archive.org/download/696e76616c69640a2e2f746573742f/furnace.pdf. Accessed November 2026.
- Nordyne. “G6RC, G6RD, G6RL Installation Instructions, 7079310,” archived copy. https://archive.org/download/manualsonline-id-2ed0ecf7-171f-4ed3-80e8-6614f5e344df/2ed0ecf7-171f-4ed3-80e8-6614f5e344df.pdf. Accessed November 2026.
- Nordyne. “M3RL Installation Instructions, 708219D,” archived copy. https://archive.org/download/manualsonline-id-caabe483-3903-44bb-8245-e1e794947030/caabe483-3903-44bb-8245-e1e794947030.pdf. Accessed November 2026.
- Nordyne. “M1M, M1G, M1B, M1S User Manual,” page 28, ManualsDir copy. https://www.manualsdir.com/manuals/194502/nordyne-m1m-m1g-m1b-m1s.html?page=28. Accessed November 2026.
- Nordyne. “G5RC User’s Information Manual,” archived copy. https://archive.org/download/manualsonline-id-9740a92a-1969-44bf-8a17-ce624b0982fe/9740a92a-1969-44bf-8a17-ce624b0982fe_text.pdf. Accessed November 2026.
- Nordyne. “FG7TC Technical Sales Literature, 472F.” https://assets.nordyne.com/m/3ccdedee00f194ac/original/472F-0523-FG7TC-2Stg-VS-95-Furn-tsl.pdf. Accessed November 2026.
- Frigidaire HVAC. “Essentials Series Gas Furnaces.” https://www.frigidairehvac.com/products/gas-furnaces/essentials-series/. Accessed November 2026.
- Distributor catalog, “Philco KG7” and “Frigidaire FG7” furnace pages (2013), archived copy. https://archive.org/download/manualsonline-id-15136040-e079-454c-8422-406c6ac9b8fd/15136040-e079-454c-8422-406c6ac9b8fd.pdf. Accessed November 2026.

Leave a Reply