Rheem furnace error codes depend on the board. On 7-segment displays, 10 is a one-hour lockout, 11 failed ignition, 22 an open main limit, 33 a tripped rollout and 57 a pressure switch stuck open. Older LED boards blink 1 to 5 times; Bluetooth boards blink codes like 045 digit by digit. Ruud shares the books.
Which Rheem board do you have: one LED, one digit, two digits or Bluetooth?
With no call for heat, a single digit reading “0” is a UT Electronic Controls 1194-200 or 1194-250 board on the (-)801T, (-)801P or (-)92T, sold in Rheem’s R921T brochure as PlusOne Diagnostics. Two digits means the (-)97V modulating furnace; a lone LED, an older standard furnace; an alarm LED plus QR label, a Bluetooth furnace.
Unlike the three notations on our Goodman furnace error codes page, Rheem keeps the meaning of 11, 22, 33, 61 and 93 across boards.
What do Rheem furnace codes 10 through 93 mean on the 7-segment display?
They are the fault list in the 801T installation book, 92-24161-144-12, repeated with two water codes in the 92T book, 92-24161-154-14. Letters are normal: C is cooling, F continuous fan, H gas heat.
| Code | Rheem’s wording | Points to | Owner check | Technician’s job |
|---|---|---|---|---|
| 0 | STANDBY | No fault, no call | None | None |
| 10 | 1 HOUR LOCKOUT | Shown with its cause code | Read the second code | Fix the paired fault |
| 11 | FAILED IGNITION | Flame rod, gas off, igniter, carryover | Manual gas valve on? | Rod, igniter, manifold about 3.5 in. w.c. natural |
| 12 | LOW FLAME SENSE | Dirty or poorly grounded rod | None; still heats | Clean rod, check ground |
| 13 | FLAME LOST | Rod, ground, unstable flame | Burner door sealed | Burner seals, door gasket |
| 14 | UNEXPECTED FLAME | Gas valve miswired or stuck open | None. Stop | Wiring, gas valve, control |
| 20 | TWINNING FAULT | Twin signal lost, phasing | Both blower doors on | Twin wiring, transformer phase |
| 22 | MAIN LIMIT OPEN | Low airflow, bad limit, overfiring | Filter, blocked ducts | Static pressure, temperature rise |
| 26 | LINE AND NEUTRAL REVERSED | Polarity or poor ground | None; line voltage | Meter L1, neutral, ground |
| 33 | MRLC (MANUAL RESET LIMIT CONTROL) (AKA ROLL-OUT) OPEN | Venting, flame, heat exchanger | None. Do not reset | Find the rollout cause |
| 55 | PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN | Welded or bypassed switch | None | Replace switch, remove bypass |
| 57 | PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED | Vent, inducer, hoses, wind, altitude | Vent ends outdoors clear? | Vent length, inducer, hoses |
| 58 | WATER SENSE CIRCUIT OPEN | Water sensor wiring (90+) | None | Sensor, P4 wiring |
| 59 | WATER SENSED | Blocked condensate drain or trap (90+) | Drain or trap blocked? | Clear drain, check wiring |
| 61 | BLOWER FAULT, BLOWER UNABLE TO RUN | Motor, PFC choke, model data | None | Motor, choke, memory card |
| 93 | INTERNAL CONTROL FAULT | Voltage on gas valve, failed board | None | Wiring, then control |
Codes 11, 12 and 13 start at the rod; our flame sensor guide covers cleaning and the microamp check. For 22 and 33, the limit and rollout switch page explains why only the rollout has a manual reset. The 801T book words 22 as MAIN LIMIT OR HALC OPEN.
Is Rheem code 2 a real code, or half of 22?
No single 7-segment table lists a code 2; you are seeing half of 20, 22 or 26. Rheem’s 801T book says the board shows the first digit for one second, the second digit for one second, then a half-second pause. So 22 reads “2, 2, pause” and 10 reads “1, 0, pause”.
With two faults, the codes alternate, split by the top segment lit for half a second: four failed ignitions give 10 and 11, a dead blower 61 and 10.

What does a blinking light with 1 to 5 blinks mean on an older Rheem?
It is Rheem’s standard flash code, 1 blink for a soft lockout to 5 for twinning. Rheem’s flash code page says it “Does not include Modulating, LXE, or Two Stage furnaces.”
| Blinks | Rheem’s wording | Rheem’s first checks |
|---|---|---|
| 1 | Soft Lockout (1 hour) | No flame after four ignition trials |
| 2 | Pressure Switch Failure (remains open) | Draft 0.1 inch past switch setting; tube port, vent |
| 3 | Limit Switch Open | Main limit or the rollout switch |
| 4 | Pressure Switch Failure (remains closed) | Welded or stuck contacts |
| 5 | Twinning Circuit Failure | Twinning boards; some electronic thermostats |
Rheem’s gas furnace FAQ says a soft lockout resets if the 115 volt supply, or the thermostat, is off for 5 to 10 seconds. Our pressure switch page covers the 2 blink checks.
What does Rheem furnace blinking 45 mean on a Bluetooth board?
On Rheem’s Bluetooth furnaces, 4 blinks, a pause, then 5 blinks is T045_F, “Inducer Lo Pressure Switch Won’t Close.” The 80+ book (92-24161-173-05, archived copy) says the alarm LED blinks each digit 1 second on, 1 second off, with 3 seconds between digits, three fast blinks for a zero and 10 seconds before repeating.
Old numbers carry over: A011_F is Failed Ignition, A061_F the blower, A093_F an internal fault. The 90+ book (92-24161-177-02) adds T059_F for water. Neither book defines the A and T prefixes or says whether a leading zero flashes.
| What you are watching | One pass | Watch at least |
|---|---|---|
| Bluetooth LED, T045_F | 31 s (35.2 s if a leading zero flashes) | 70 s |
| Bluetooth LED, A113_F | 26 s | 52 s |
| Single 7-segment, one fault | 2.5 s | 10 s |
| Dual 7-segment (-)97V | 1.5 s | 6 s |
A 45 points at the low pressure switch, hose and inducer motor. Full troubleshooting sits in Rheem’s contractor app, which connects only with the doors on and the furnace powered.
Which extra codes does a Rheem modulating furnace add?
The (-)97V book, 92-24161-151-11, has a 46-entry list ranked by priority so the most critical code shows first. It warns that if a code is not on the list, the display may be upside down.
| Code | Rheem’s wording, (-)97V dual display |
|---|---|
| 23 | Auxiliary Limit Switch Open |
| 30 | Open Fuse |
| 34 | IDM Overcurrent |
| 44 / 55 | Low / High Pressure Switch Closed, Should be Open |
| 45 / 46 | Low Pressure Switch Open, Inducer On High / Low Speed |
| 57 | High Pressure Switch Open, Inducer on High Speed |
| 68 / 71 | No Blower Communications / Inducer Fault |
| d1 | No Model Data |
Why is the yellow, green or red light blinking on a Rheem board?
The amber LED on 801T, 801P and 92T boards is flame status, not a fault: steady on normal flame, one to four times per second on weak flame, rapid on unexpected flame.
On the (-)97V, a red TX and a green RX LED show communications, lit “in an undefined pattern” when other communicating parts are connected, which is normal. No Rheem book we opened gives meaning to an orange light or a green or red blink count on other boards.
How do you read a Rheem code before a power cycle clears it?
Note the code before touching the breaker or doors. Rheem says a lockout clears when power is cycled, and on 7-segment boards when the heat call is off for more than 2 but less than 20 seconds.
History survives. On power reset, the 801T and 92T boards replay the three most recent faults less than a week old; the buffer clears after a week or when SW4 is toggled three times within 30 seconds. The (-)97V keeps six faults for 168 powered hours in its FL menu. Our furnace reset guide covers when a reset is reasonable.

Which Rheem codes mean stop rather than reset?
Stop at 14, 26, 33, 55 and 93. Rheem calls 14 “an extremely critical fault”; 33 signals a “very serious problem”; 55 can mean a switch “welded closed or purposely bypassed”; 26 is line voltage; 93 “cannot be reset by cycling the heat call.”
Rheem says not to reset safety controls without corrective action. A 59 sends the technician to the trap, as with a furnace leaking water; a 93 or repeat 61 ends at the control board or motor, tested with a meter.
Frequently asked questions
What does code 0 mean on a Rheem furnace?
A steady “0” is standby on Rheem 7-segment boards: no fault and no thermostat call. The (-)97V book adds that 0 also shows during the heat or cool blower off delay. A 0 that follows a 1 or a 2 is the second digit of 10 or 20.
What does it mean when a Rheem furnace is blinking twice?
On older single-LED Rheem boards, 2 blinks means the pressure switch remains open. Rheem’s FAQ has the technician confirm inducer suction at least 0.1 inch beyond the switch closing setting, then check the tube port on the inducer housing, the vent pipe, inducer speed and the heat exchanger.
Are Ruud furnace error codes the same as Rheem?
For the same series, yes. Rheem prints series names with a blank first letter, such as (-)801T and (-)92T, and the 801P book sends parts buyers to myrheem.com and myruud.com in one sentence: one book, one code table. Match the series in your model number to the book.
What does Rheem furnace code 11 mean after cleaning the flame sensor?
Code 11 is FAILED IGNITION, and Rheem lists five causes: flame rod, gas valve off, igniter, control board, and flame not carrying across the burners. With a clean rod, a technician checks manifold pressure during ignition, about 3.5 inches w.c. on natural gas, and watches each burner light.
Where is the Rheem furnace error code list PDF?
It is in the installation instructions shipped with the furnace, under Diagnostics and Fault Codes, with the form number on the cover: 92-24161-144 for 801T, 92-24161-154 for 92T, 92-24161-151 for 97V. Rheem’s public product pages we checked carry brochures and spec sheets, not these books.
How we researched this
In November 2026 we read seven Rheem installation books (92-24161-144-12, 142-00, 154-07, 154-14, 151-11, 173-05, 177-02) and two Rheem PTS pages, decoding pages printed in a shifted font. We found no R96V book, so it is not covered. Aggregator sites were not cited.
Sources
- Rheem. “Standard Gas Furnace Diagnostic Codes.” https://my.rheem.com/pts/Topics/GF_Flash_Code.asp. Accessed November 2026.
- Rheem. “Gas Furnace Technical FAQ.” https://my.rheem.com/pts/FAQ/FAQ_Gas_Furnace.asp. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-144-12.” https://abrwholesalers.com/media/assets/product/documents/Rheem/R801T/InstallationInstructions_92-24161-144-12_Rev12.pdf. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-142-00.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r801p_en_ii.pdf. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-154-14.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r921t_en_ii.pdf. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-151-11.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r97mv_en_ii.pdf. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-173-05 (archived copy).” https://web.archive.org/web/20260923041132/https://airmanagementsupply.com/documents/rheem-ruud_R802V_UH_installation_instructions.pdf. Accessed November 2026.
- Rheem. “Installation Instructions 92-24161-177-02.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r962v_en_ii.pdf. Accessed November 2026.
- Rheem. “R921T Gas Furnace brochure.” https://files.myrheem.com/webpartners/ProductDocuments/CE8DAF5C-AB0F-443E-9CDE-D97DE03A0218.pdf. Accessed November 2026.