Rheem Furnace Error Codes: Every Display, Blink and Bluetooth Code by Board

Technician reading the control board display on a gas furnace while checking Rheem furnace error codes

Rheem furnace error codes depend on the board. On 7-segment displays, 10 is a one-hour lockout, 11 failed ignition, 22 an open main limit, 33 a tripped rollout and 57 a pressure switch stuck open. Older LED boards blink 1 to 5 times; Bluetooth boards blink codes like 045 digit by digit. Ruud shares the books.

Which Rheem board do you have: one LED, one digit, two digits or Bluetooth?

With no call for heat, a single digit reading “0” is a UT Electronic Controls 1194-200 or 1194-250 board on the (-)801T, (-)801P or (-)92T, sold in Rheem’s R921T brochure as PlusOne Diagnostics. Two digits means the (-)97V modulating furnace; a lone LED, an older standard furnace; an alarm LED plus QR label, a Bluetooth furnace.

What does the control board showwith no call for heat?One LED, no digitsOlder standardfurnace boardCount 1 to 5blinksRheem PTS tableOne digit, shows 0UT 1194 board:801T, 801P, 92TCodes 10 to 93,one digit at a time92-24161-144, 154Two digits(-)97V modulating,dual displayAdds 23 to 99,d1, Cl, h, H92-24161-151-11Alarm LED + QRBluetooth board,80+ and 90+A or T code, LEDblinks each digit92-24161-173, 177Amber LED on a 7-segment board = flame status, not a fault
Which Rheem code table applies. Sources: Rheem PTS page; Rheem 92-24161-144-12, 92-24161-151-11, 92-24161-173-05.

Unlike the three notations on our Goodman furnace error codes page, Rheem keeps the meaning of 11, 22, 33, 61 and 93 across boards.

What do Rheem furnace codes 10 through 93 mean on the 7-segment display?

They are the fault list in the 801T installation book, 92-24161-144-12, repeated with two water codes in the 92T book, 92-24161-154-14. Letters are normal: C is cooling, F continuous fan, H gas heat.

Compiled by The HVAC Brief from Rheem 92-24161-144-12 ((-)801T, (-)801C, (-)(-)80MSX, (-)(-)80MSC), 92-24161-142-00 ((-)801S, (-)801P) and 92-24161-154-14 ((-)92T, (-)(-)92MSX). 58 and 59 appear only in the 90+ book.
Code Rheem’s wording Points to Owner check Technician’s job
0 STANDBY No fault, no call None None
10 1 HOUR LOCKOUT Shown with its cause code Read the second code Fix the paired fault
11 FAILED IGNITION Flame rod, gas off, igniter, carryover Manual gas valve on? Rod, igniter, manifold about 3.5 in. w.c. natural
12 LOW FLAME SENSE Dirty or poorly grounded rod None; still heats Clean rod, check ground
13 FLAME LOST Rod, ground, unstable flame Burner door sealed Burner seals, door gasket
14 UNEXPECTED FLAME Gas valve miswired or stuck open None. Stop Wiring, gas valve, control
20 TWINNING FAULT Twin signal lost, phasing Both blower doors on Twin wiring, transformer phase
22 MAIN LIMIT OPEN Low airflow, bad limit, overfiring Filter, blocked ducts Static pressure, temperature rise
26 LINE AND NEUTRAL REVERSED Polarity or poor ground None; line voltage Meter L1, neutral, ground
33 MRLC (MANUAL RESET LIMIT CONTROL) (AKA ROLL-OUT) OPEN Venting, flame, heat exchanger None. Do not reset Find the rollout cause
55 PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN Welded or bypassed switch None Replace switch, remove bypass
57 PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED Vent, inducer, hoses, wind, altitude Vent ends outdoors clear? Vent length, inducer, hoses
58 WATER SENSE CIRCUIT OPEN Water sensor wiring (90+) None Sensor, P4 wiring
59 WATER SENSED Blocked condensate drain or trap (90+) Drain or trap blocked? Clear drain, check wiring
61 BLOWER FAULT, BLOWER UNABLE TO RUN Motor, PFC choke, model data None Motor, choke, memory card
93 INTERNAL CONTROL FAULT Voltage on gas valve, failed board None Wiring, then control

Codes 11, 12 and 13 start at the rod; our flame sensor guide covers cleaning and the microamp check. For 22 and 33, the limit and rollout switch page explains why only the rollout has a manual reset. The 801T book words 22 as MAIN LIMIT OR HALC OPEN.

Is Rheem code 2 a real code, or half of 22?

No single 7-segment table lists a code 2; you are seeing half of 20, 22 or 26. Rheem’s 801T book says the board shows the first digit for one second, the second digit for one second, then a half-second pause. So 22 reads “2, 2, pause” and 10 reads “1, 0, pause”.

With two faults, the codes alternate, split by the top segment lit for half a second: four failed ignitions give 10 and 11, a dead blower 61 and 10.

Older Rheem boards report faults with a single LED that blinks a count.
Older Rheem boards report faults with a single LED that blinks a count. AI illustration.

What does a blinking light with 1 to 5 blinks mean on an older Rheem?

It is Rheem’s standard flash code, 1 blink for a soft lockout to 5 for twinning. Rheem’s flash code page says it “Does not include Modulating, LXE, or Two Stage furnaces.”

Compiled by The HVAC Brief from Rheem’s PTS flash code and gas furnace FAQ pages.
Blinks Rheem’s wording Rheem’s first checks
1 Soft Lockout (1 hour) No flame after four ignition trials
2 Pressure Switch Failure (remains open) Draft 0.1 inch past switch setting; tube port, vent
3 Limit Switch Open Main limit or the rollout switch
4 Pressure Switch Failure (remains closed) Welded or stuck contacts
5 Twinning Circuit Failure Twinning boards; some electronic thermostats

Rheem’s gas furnace FAQ says a soft lockout resets if the 115 volt supply, or the thermostat, is off for 5 to 10 seconds. Our pressure switch page covers the 2 blink checks.

What does Rheem furnace blinking 45 mean on a Bluetooth board?

On Rheem’s Bluetooth furnaces, 4 blinks, a pause, then 5 blinks is T045_F, “Inducer Lo Pressure Switch Won’t Close.” The 80+ book (92-24161-173-05, archived copy) says the alarm LED blinks each digit 1 second on, 1 second off, with 3 seconds between digits, three fast blinks for a zero and 10 seconds before repeating.

Bluetooth alarm LED, fault 045 (one pass, about 31 s)3 s10 s, then repeat4 blinks: 1 s on, 1 s off5 blinksSingle 7-segment display, fault 57 (one pass, 2.5 s)57571 s1 s0.5 sRead 5 then 7as code 57,not 5 and 7Bar widths to scale within each row; rows use different scales
Timing from Rheem 92-24161-173-05 and 92-24161-144-12; drawn by The HVAC Brief.

Old numbers carry over: A011_F is Failed Ignition, A061_F the blower, A093_F an internal fault. The 90+ book (92-24161-177-02) adds T059_F for water. Neither book defines the A and T prefixes or says whether a leading zero flashes.

HVAC Brief calculation: blinks x 2 s, plus 3 s per digit gap and 10 s before repeat (92-24161-173-05); zero digit 1.2 s. Display timings from 92-24161-144-12 and 92-24161-151-11.
What you are watching One pass Watch at least
Bluetooth LED, T045_F 31 s (35.2 s if a leading zero flashes) 70 s
Bluetooth LED, A113_F 26 s 52 s
Single 7-segment, one fault 2.5 s 10 s
Dual 7-segment (-)97V 1.5 s 6 s

A 45 points at the low pressure switch, hose and inducer motor. Full troubleshooting sits in Rheem’s contractor app, which connects only with the doors on and the furnace powered.

Which extra codes does a Rheem modulating furnace add?

The (-)97V book, 92-24161-151-11, has a 46-entry list ranked by priority so the most critical code shows first. It warns that if a code is not on the list, the display may be upside down.

Compiled by The HVAC Brief from Rheem 92-24161-151-11, fault priority list 92-104632-05-00.
Code Rheem’s wording, (-)97V dual display
23 Auxiliary Limit Switch Open
30 Open Fuse
34 IDM Overcurrent
44 / 55 Low / High Pressure Switch Closed, Should be Open
45 / 46 Low Pressure Switch Open, Inducer On High / Low Speed
57 High Pressure Switch Open, Inducer on High Speed
68 / 71 No Blower Communications / Inducer Fault
d1 No Model Data

Why is the yellow, green or red light blinking on a Rheem board?

The amber LED on 801T, 801P and 92T boards is flame status, not a fault: steady on normal flame, one to four times per second on weak flame, rapid on unexpected flame.

On the (-)97V, a red TX and a green RX LED show communications, lit “in an undefined pattern” when other communicating parts are connected, which is normal. No Rheem book we opened gives meaning to an orange light or a green or red blink count on other boards.

How do you read a Rheem code before a power cycle clears it?

Note the code before touching the breaker or doors. Rheem says a lockout clears when power is cycled, and on 7-segment boards when the heat call is off for more than 2 but less than 20 seconds.

History survives. On power reset, the 801T and 92T boards replay the three most recent faults less than a week old; the buffer clears after a week or when SW4 is toggled three times within 30 seconds. The (-)97V keeps six faults for 168 powered hours in its FL menu. Our furnace reset guide covers when a reset is reasonable.

Codes that mean stop call for a technician's diagnosis rather than another reset.
Codes that mean stop call for a technician's diagnosis rather than another reset. AI illustration.

Which Rheem codes mean stop rather than reset?

Stop at 14, 26, 33, 55 and 93. Rheem calls 14 “an extremely critical fault”; 33 signals a “very serious problem”; 55 can mean a switch “welded closed or purposely bypassed”; 26 is line voltage; 93 “cannot be reset by cycling the heat call.”

Rheem says not to reset safety controls without corrective action. A 59 sends the technician to the trap, as with a furnace leaking water; a 93 or repeat 61 ends at the control board or motor, tested with a meter.

Frequently asked questions

What does code 0 mean on a Rheem furnace?

A steady “0” is standby on Rheem 7-segment boards: no fault and no thermostat call. The (-)97V book adds that 0 also shows during the heat or cool blower off delay. A 0 that follows a 1 or a 2 is the second digit of 10 or 20.

What does it mean when a Rheem furnace is blinking twice?

On older single-LED Rheem boards, 2 blinks means the pressure switch remains open. Rheem’s FAQ has the technician confirm inducer suction at least 0.1 inch beyond the switch closing setting, then check the tube port on the inducer housing, the vent pipe, inducer speed and the heat exchanger.

Are Ruud furnace error codes the same as Rheem?

For the same series, yes. Rheem prints series names with a blank first letter, such as (-)801T and (-)92T, and the 801P book sends parts buyers to myrheem.com and myruud.com in one sentence: one book, one code table. Match the series in your model number to the book.

What does Rheem furnace code 11 mean after cleaning the flame sensor?

Code 11 is FAILED IGNITION, and Rheem lists five causes: flame rod, gas valve off, igniter, control board, and flame not carrying across the burners. With a clean rod, a technician checks manifold pressure during ignition, about 3.5 inches w.c. on natural gas, and watches each burner light.

Where is the Rheem furnace error code list PDF?

It is in the installation instructions shipped with the furnace, under Diagnostics and Fault Codes, with the form number on the cover: 92-24161-144 for 801T, 92-24161-154 for 92T, 92-24161-151 for 97V. Rheem’s public product pages we checked carry brochures and spec sheets, not these books.

How we researched this

In November 2026 we read seven Rheem installation books (92-24161-144-12, 142-00, 154-07, 154-14, 151-11, 173-05, 177-02) and two Rheem PTS pages, decoding pages printed in a shifted font. We found no R96V book, so it is not covered. Aggregator sites were not cited.

Sources

  1. Rheem. “Standard Gas Furnace Diagnostic Codes.” https://my.rheem.com/pts/Topics/GF_Flash_Code.asp. Accessed November 2026.
  2. Rheem. “Gas Furnace Technical FAQ.” https://my.rheem.com/pts/FAQ/FAQ_Gas_Furnace.asp. Accessed November 2026.
  3. Rheem. “Installation Instructions 92-24161-144-12.” https://abrwholesalers.com/media/assets/product/documents/Rheem/R801T/InstallationInstructions_92-24161-144-12_Rev12.pdf. Accessed November 2026.
  4. Rheem. “Installation Instructions 92-24161-142-00.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r801p_en_ii.pdf. Accessed November 2026.
  5. Rheem. “Installation Instructions 92-24161-154-14.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r921t_en_ii.pdf. Accessed November 2026.
  6. Rheem. “Installation Instructions 92-24161-151-11.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r97mv_en_ii.pdf. Accessed November 2026.
  7. Rheem. “Installation Instructions 92-24161-173-05 (archived copy).” https://web.archive.org/web/20260923041132/https://airmanagementsupply.com/documents/rheem-ruud_R802V_UH_installation_instructions.pdf. Accessed November 2026.
  8. Rheem. “Installation Instructions 92-24161-177-02.” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r962v_en_ii.pdf. Accessed November 2026.
  9. Rheem. “R921T Gas Furnace brochure.” https://files.myrheem.com/webpartners/ProductDocuments/CE8DAF5C-AB0F-443E-9CDE-D97DE03A0218.pdf. Accessed November 2026.