American Standard furnace error codes depend on the control board. On LED boards, 2 red flashes means lockout, 3 a pressure switch fault and 4 an open limit. Gold and Silver S8 and S9 furnaces show E codes such as E2.1, and the Platinum 95 sends numbers like ERR 22 to a communicating thermostat.
Which American Standard furnace do you have, and which code table fits it?
Match the first characters of the rating plate model number below. American Standard’s furnace lineup page lists 15 model families, and their codes are printed in Trane literature because the brands share boards: Trane’s model lists say “First letter may be “A” or “T””, and the guides give one Tyler, Texas address for both.
| American Standard family | Model starts with | Board shows | Guide with the codes |
|---|---|---|---|
| Platinum 95 | AUHM, ADHM | Red, green and amber LEDs, text display, ERR numbers on the thermostat | 18-CD30D1-21-EN |
| Gold S9X2, Silver S9X1, S9B1; Gold S8X2, Silver S8X1, S8B1 | S9X2, S9X1, S9B1, S8X2, S8X1, S8B1 | 7-segment display, E codes | 18-CE12D1-1D-EN, 18-CE16D1-1C-EN |
| Gold S9V2-VS | S9V2 ending VS | 7-segment status words only | 18-CE03D1-1F-EN |
| Platinum 80 | AUD2, ADD2 with ACV | Green and red LEDs, 1 to 10 flashes | 18-CH76D1-1A-EN |
| Older models | AUX, ADX | Green and red LEDs, 1 to 9 flashes | 18-CH111D1-1A-EN |
| Older models | AUD2, ADD2 with A9; AUD, ADD with R9 | Green, amber and red LEDs, 1 to 12 flashes | 18-CH61D1-4A-EN |
| Gold 80V, Gold S9V2 (PS), Platinum S8V2-C, L8V1, L8X1, L9X1 | AUD2/ADD2 with A9V or B9V, others | Not verified | None we opened |
Compiled by The HVAC Brief from American Standard’s furnace page and the seven guides under Sources. CH-numbered guides are replacement control kits; the label on the blower door wins.
Because S8 and S9 model numbers are sold under both nameplates, the full E-code list lives on our Trane furnace error codes page, and the ownership split is in our HVAC brand ownership table. This page adds the Platinum 95 and Platinum 80 codes, matched to American Standard model numbers.
What do Platinum 95 codes like ERR 22, ERR 26 and ERR 87 mean?
On the modulating Platinum 95, ERR 22 is a one-hour soft lockout after failed ignition or lost flame, ERR 26 a high temperature limit and ERR 87 an open flame rollout switch. Each fault shows three ways: red LED flashes, a text message on the display behind the blower door, and an alert number on the communicating thermostat.
| Red LED | Display text | Thermostat | Maker’s description | Owner check; technician job |
|---|---|---|---|---|
| 2 flashes | RECYCLE LO, RETRY LO | ERR 22 | 10 recycles or 3 ignition attempts: 1 hr lockout | Gas handle open, vents clear; igniter, gas pressure |
| 3 flashes | PS1, PS2 or PS3 OPEN or CLOSED | N/A (alert 1) | Pressure switch failure | Snow at vents, drain; switch, tubing, inducer |
| 4 flashes | HIGH LIMIT, AUX LIMIT | ERR 26 | Heat exchanger too hot; low airflow or fan failure | Filter, registers; blower |
| 4 flashes | ROLLOUT OPEN | ERR 87 | Open flame rollout | Stop: technician only |
| 5 flashes | FLAME ERROR | ERR 34 | Flame detected, should not be present | Stop: shut the gas |
| 6 flashes | POLARITY ERR, GND FAULT | N/A (alerts 33, 88) | Reverse polarity; no earth ground | Stop: line voltage |
| 6 flashes | IGNITER ERR, TRIAC ERR | ERR 10 | Ignition means fault | None; igniter circuit |
| 7 flashes or solid | EXT GV ERR, INT GV ERR | ERR 93 | Gas valve fault | Stop: shut the gas |
| 8 flashes | LO FLAME SNS | N/A (alert 4) | Flame current low, still allows operation | None; flame sensor |
| 9 flashes | IND LIMIT | ERR 26 | Flue gas temperature too high | Filter; inducer limit |
| Solid on | CNTRL FAULT | ERR 18 | Internal control failure | None; control board |
Compiled by The HVAC Brief from guide 18-CD30D1-21-EN, Table 24 (*UHM and *DHM). “Thermostat” is the guide’s Control Display column. The check and job column is ours.
ERR 26 covers both 4 and 9 flashes, so count the LED before blaming the limit switch. An ERR 22 lockout ends after the hour and hides its cause, but the Platinum 95 guide has the board flash the last 4 alerts at power-up, newest first, 2 seconds apart.

What does an American Standard furnace blinking 2, 3 or 4 times mean?
On every green and red board we opened, 2 flashes is a lockout, 3 a pressure switch fault and 4 an open limit. The older three-LED board is the exception: 2 flashes there means the pressure switch is stuck closed.
| Red flashes | Platinum 80 (ACV) | AUX, ADX | Platinum 95 | Three-LED (A9, R9) |
|---|---|---|---|---|
| 1 | Normal, every 20 seconds | Normal, every 20 seconds | Normal, every 20 seconds | Flame sensed when none should be |
| 2 | Lockout, retries or recycles | Lockout, retries or recycles | Retry; ERR 22 lockout | Pressure switch stuck closed |
| 3 | Pressure switch fault | Pressure switch fault | Pressure switch failure | 1st stage pressure switch stuck open |
| 4 | Open limit switch | Open limit switch | High limit or rollout | Open limit switch |
| 9 | Open inducer limit | Igniter relay fault | Inducer limit | Grounding or reversed polarity |
Compiled by The HVAC Brief from 18-CH76D1-1A-EN, 18-CH111D1-1A-EN, 18-CD30D1-21-EN and 18-CH61D1-4A-EN.
A 3 flash code points at the draft side: blocked PVC terminations, a full condensate trap, cracked tubing or a weak inducer motor; our furnace pressure switch guide covers the technician’s vacuum test. A 4 flash code usually traces to airflow, which the limit switch page explains.
Is code 1dL, COF, ARF or 7P1 an error on an S8 or S9 furnace?
No. All four are status readouts on the 7-segment display. Guide 18-CE12D1 defines IdL as Idle, no demand for cooling, heating or fan (the capital I reads like a 1) and COF as a demand for continuous fan. On the S9V2-VS, guide 18-CE03D1 prints aRF for airflow, followed by airflow times 10: 080 is 800 requested cfm.
The display alternates mode and airflow every 2 seconds. Guide 18-CE12D1’s example pairs COF with Tp1, and its key reads “TP1-9 = Tap selected for airflow”; we read 7P1 as Tp1 in seven segments, blower tap 1. Real faults start with E, such as E2.1 (3 failed ignitions, one hour lockout), E3.2 (open pressure switch) or E04 (open limit).
Does American Standard code 3 or code 4 mean flashes or a thermostat number?
Usually flashes. Code 3 is a pressure switch problem in every table we opened: 3 flashes, E3.1 to E3.4, or the Platinum 95’s PS1 to PS3 messages. Code 4 is an open limit as 4 flashes or E04, but the Platinum 95’s alert 4 is a low flame signal, which its guide does not send to the thermostat. A low flame signal usually means a coated rod; the flame sensor guide covers cleaning.
What does a blinking green light or a solid red light mean?
A blinking green light is normal: slow means no call for heat, fast means a call for heat, per guides 18-CH76D1 and 18-CH111D1. Green and red both solid means internal control failure; both off means the fuse is open. On the Platinum 95, solid red is ERR 93 or ERR 18, the green BM LED stays on with power, and the amber COM LED flashes a device count. Three-LED amber flashes are status: 1 first stage heat, 2 second stage, 3 W2 with no W1. Board testing is covered in our furnace control board guide.
Where in the Platinum 95 start-up does each code trip?
Each code maps to one step. The board proves the pressure switches open, runs the inducer at 65% to close PS1 and PS2, warms the igniter about 20 seconds, then opens the gas valve for a 5 second trial for ignition in both communicating and 24V modes.
While running, a pressure switch open more than 3.5 seconds makes the inducer speed up; not closed within 12 to 15 seconds, the board drops from high to medium or medium to low heat for 10 minutes; at low heat it shuts down and waits 30 seconds.

How do you reset an American Standard furnace, and when should you stop?
Turn the furnace power off and back on: guide 18-CD30D1 says a lockout “may be manually reset” that way. Thermostat-side steps are in our how to reset a furnace guide.
Stop and call a technician for: 5 flashes or ERR 34, 7 flashes, solid red or ERR 93, ROLLOUT OPEN or ERR 87, 6 flashes for polarity or ground, or any gas smell. The Platinum 95 burner box also has a manual reset limit: check the vent and combustion air terminations, and if they are clear, the guide says not to reset it but to call a qualified service professional.
Photograph the LED before opening the blower door, because the door switch cuts power. The Platinum 95 guide warns never to bypass the door switch by any permanent means.
Frequently asked questions
Why is my American Standard furnace blinking a red light 3 times?
Three red flashes means a pressure switch fault on the Platinum 80, AUX and ADX boards and the Platinum 95, whose display adds PS1, PS2 or PS3 OPEN or CLOSED. On the older three-LED board it means the 1st stage pressure switch is stuck open. Check that the PVC vent and intake are clear of snow and the condensate drain flows.
Do American Standard furnaces use the same error codes as Trane?
Yes, model for model. Trane’s guides list each model with a first letter that may be A or T, and American Standard’s furnace page sells the same S8 and S9 model numbers Trane documents. The codes follow the control board, so an AUD2 ACV and a TUD2 ACV share the 10 flash table in guide 18-CH76D1.
How do I see past fault codes on an American Standard furnace?
On S8 and S9 display boards, press Menu until L6F (last 6 faults) appears, then Option to read them. Holding Option for 5 seconds clears the list, so do not. On the Platinum 95, the last 4 alerts flash on the red LED at power-up, and the display has a LAST 4 FAULTS menu.
Why is my American Standard electric furnace not heating?
None of these code tables apply: every one of the 15 families on American Standard’s furnace page is listed as gas-fired, and all the boards here run a gas valve and igniter. An electric unit has no flame or pressure switch to report; our electric furnace guide covers element staging, sizing and circuits.
How we researched this
On 9 November 2026 we read the model families and numbers in the product data of American Standard’s furnace and Platinum 95 pages, downloaded seven guides from Trane’s public eLibrary, matched each model prefix to the guide whose model list names it, and copied code rows only from those guides. Families with no matching guide are marked unverified, not filled from other boards. Ranking roundups (pickhvac.com, hvaclaboratory.com, furnacecodes.com) were excluded because none cites a maker document.
Sources
- American Standard. “Furnaces.” https://www.americanstandardair.com/products/furnaces/ Accessed November 2026.
- American Standard. “Platinum 95 Gas Furnace.” https://www.americanstandardair.com/products/furnaces/platinum-95-furnace/ Accessed November 2026.
- Trane. “Installer’s Guide 18-CD30D1-21-EN (*UHM, *DHM).” https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-CD30D1-21-EN_09152023.pdf Accessed November 2026.
- Trane. “Installer’s Guide 18-CE12D1-1D-EN (S9X1, S9X2, S9B1).” https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-CE12D1-1D-EN_09162020.pdf Accessed November 2026.
- Trane. “Installer’s Guide 18-CE16D1-1C-EN (S8B1, S8X1, S8X2).” https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-CE16D1-1C-EN_05052021.pdf Accessed November 2026.
- Trane. “Installer’s Guide 18-CE03D1-1F-EN (S9V2).” https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-CE03D1-1F-EN_05132020.pdf Accessed November 2026.
- Trane. “Service Installer’s Guide 18-CH76D1-1A-EN (*UD2-ACV, *DD2-ACV).” https://elibrary.tranetechnologies.com/public/trane-history/Literature/Installation/18-CH76D1-1A-EN_07062020 Accessed November 2026.
- Trane. “Service Installer’s Guide 18-CH111D1-1A-EN.” https://elibrary.tranetechnologies.com/public/residential-hvac/Literature/Installation/18-CH111D1-1A-EN_12262023.pdf Accessed November 2026.
- Trane. “Service Installer’s Guide 18-CH61D1-4A-EN.” https://elibrary.tranetechnologies.com/public/trane-history/Literature/Installation/18-CH61D1-4A-EN_07062020 Accessed November 2026.