Heat Pump Outside Unit Not Running in Winter? 5 Checks in the Order That Matters

Heat pump outside unit not running in winter, silent beside a snowy house wall

If your heat pump outside unit is not running in winter but the house still gets some heat, the indoor electric strips are carrying the load. Check four things in order: the thermostat is not on EM HEAT, 15 minutes have passed, the outdoor breaker and disconnect are on, and the contactor gets 24 volts.

This page covers the case where the whole outdoor unit is silent: no compressor hum, no fan. If the compressor runs and only the fan blade sits still, that is a different fault with its own checks on our page about the heat pump outdoor fan not running. A unit that steams with the fan stopped is defrosting, which Rheem’s 708163B manual calls normal: “the outdoor fan will stop, and the compressor will continue to run.”

Is the outdoor unit off because the thermostat told it to be off?

Often, yes. Rheem’s 708163B owner section says that with the system switch on EM. HT. “the outdoor unit will be locked off, and supplemental heat (typically electric resistance heating) will be used.” Switch the thermostat from EM HEAT to HEAT and set the temperature above the room reading so the thermostat actually calls for heat.

The second thermostat cause is a compressor lockout threshold. Smart thermostats can refuse to run the compressor below a set outdoor temperature and hand the call to the strips. The Bonneville Power Administration’s PTCS support sheet for the ecobee3 lite, ecobee4 and ecobee5 tells installers to open Settings, Installation Settings, Thresholds, “COMPRESSOR MIN TEMPERATURE” and set it to “DISABLED” or ≤5F, and to keep “AUX HEAT MAX OUTDOOR TEMPERATURE” at ≤35F. On a dual fuel system the outdoor unit is meant to stop below the changeover temperature and the furnace takes over, so silence there is by design.

How long should you wait before deciding the heat pump outside unit is not coming on?

Wait 15 minutes. Goodman’s IOG-4002A owner checklist says “Wait 15 minutes. Some devices in the outdoor unit or in programmable thermostats will prevent compressor operation for a while, and then reset automatically.” Every board we read holds the compressor off for about 5 minutes after power returns or a call ends, and some safeties hold far longer:

What holds the outdoor unit off Maker document How long How it clears
Anti-short-cycle timer after a call ends or power returns Rheem 708163B; Copeland 47D40-801; Lennox XP17 506586-01; Carrier 25HNB6 About 5 minutes (Lennox: 300 seconds, not adjustable on non-communicating systems) Automatic
Owner wait recommended before a service call Goodman IOG-4002A 15 minutes Automatic
Low-pressure switch open Rheem 708163B (select models) Opens below 5 psig, closes above 20 psig, then 5-minute delay Automatic once pressure recovers
Low-pressure switch, five-strike lockout Lennox XP17 506586-01 Trips at 25 psig, resets at 40 psig; 5 trips in one call locks out Cycle power to R on the heat pump control, or jumper the field test pins 1 to 2 seconds
Thermal or pressure lockout (codes 81 to 84) Carrier 25HNB6 Infinity 16 4 HRS Timed
Compressor internal overload open Goodman IOG-3038A “Wait at least 2 hours for overload to reset” Automatic as the compressor cools; if still open, compressor fault

Compiled by The HVAC Brief from the Rheem, Goodman, Lennox, Carrier and Copeland documents listed in Sources. Settings vary by series; read the label inside your own unit’s control panel.

Check the outdoor disconnect and the breaker before anything else.
Check the outdoor disconnect and the breaker before anything else. AI illustration.

Is the outdoor breaker or disconnect off, and is it safe to reset it?

Reset it once. The outdoor unit has its own branch circuit in the panel and a disconnect box beside the unit, separate from the air handler that powers the strips, which is why the house stays partly warm with the outdoor breaker tripped. Goodman’s IOG-4002A warns: “If the circuit breaker or fuse should open again within thirty days, contact a qualified servicer,” and that repeated resets “run the risk of severe equipment damage.” A breaker that trips again within minutes points to a shorted compressor or wiring, covered on our page on HVAC breakers tripping.

If the breaker was off for days, give it time. Goodman says units with crankcase heaters “should have high voltage power energized for 24 hours prior to start up,” and Rheem 708163B gives the same 24 hour wait before a function checkout. Carrier’s 25HNB6 diagram says its crankcase heater is energized during the off cycle below 65°F.

Whole outdoor unit silent in heat mode 1. Thermostat on HEAT, not EM HEAT, setpoint above room temperature? No: EM HEAT locks the outdoor unit off (Rheem 708163B) 2. Waited 15 minutes? Compressor lockout temperature disabled? No: 5 minute delay is normal; BPA sheet: ≤5F or DISABLED 3. Outdoor breaker on and disconnect pulled in? No: reset once; trips again means a short, call service 4. Technician: 24 V at the contactor coil (Y to C)? No: Y wire, transformer, pressure switch or board lockout (read the LED) 5. 24 V present: contactor closed and 240 V across its load side? No: failed contactor coil or burned contacts Yes, power reaches the motors: a hum with no spin points to a capacitor or stuck compressor; dead silence points to an open overload (Goodman: wait 2 hours) yes yes yes yes yes
Steps 1 to 3 are owner checks; steps 4 and 5 are line voltage work for a technician. Sources: Rheem 708163B, Goodman IOG-4002A and IOG-3038A, BPA PTCS ecobee support sheet.

Does the contactor get 24 volts when the thermostat calls for heat?

This is a technician’s test, because the same box carries 240 volts. Goodman’s IOG-3038A troubleshooting chart, under “Unit will not run,” says to “Check for 24 volts at contactor coil” and replace the contactor “if contacts are open.” With 24 volts present and the contactor still open, the coil or the contacts have failed; our HVAC contactor page covers how they burn and pit. With no 24 volts, the fault is upstream: the Y wire from the thermostat, the indoor transformer, an open pressure switch or a defrost board that has locked the compressor out.

Goodman’s IOG-4002A analysis guide marks five possible causes for “Comp. and Cond. Fan will not start”: blown fuse, shorted or broken wires, faulty thermostat, faulty transformer and faulty compressor contactor. Power failure and loose connections sit under “System will not start.” A capacitor is not on that list. A failed run capacitor shows up differently: the contactor closes and a motor hums without starting, the pattern our HVAC capacitor explainer describes.

Which board LED codes mean the outdoor unit has locked itself out?

Board LEDs only show with power on, so reading them behind the panel is a technician job. Carrier and Lennox documents define codes that mean the outdoor unit is being held off:

Unit Code Meaning in the maker document
Carrier 25HNB6 Infinity 16 32 Low Pressure Switch Trip
Carrier 25HNB6 Infinity 16 47 No 230v with call to run
Carrier 25HNB6 Infinity 16 74 Contactor Open (No 230v to Comp)
Carrier 25HNB6 Infinity 16 83 Low pressure lockout (4 HRS)
Lennox XP17 (A175 control) DS11 green off, DS14 red on Low pressure switch lockout (icomfort alert 411)
Lennox XP17 (A175 control) DS11 green on, DS14 red off High pressure switch lockout (icomfort alert 413)

Compiled by The HVAC Brief from Carrier wiring diagram 338054-101 for the 25HNB6 and Lennox XP17 instructions 506586-01. Carrier reads short flashes as the first digit and long flashes as the second. Other series use other codes; we found no Trane or Goodman document defining outdoor lockout codes for this symptom and do not guess at them.

A low-pressure lockout in winter usually means lost refrigerant charge or a coil packed with ice. Lennox’s XP17 flowchart ignores the low-pressure switch when outdoor ambient is 15°F or below, so on that series a deep-cold lockout is less likely to be the low-pressure switch. Anything that opens the refrigerant circuit is technician work under the EPA’s 40 CFR 82.161 certification rule.

Can it be too cold outside for the heat pump outdoor unit to run?

Not by the hardware alone, in the documents we read. None of the Rheem, Goodman, Lennox or Carrier manuals sets an outdoor temperature below which the compressor stops in heat mode. The cutoff comes from controls you or the installer set: the thermostat’s compressor minimum, a dual fuel changeover, or an outdoor thermostat. Rheem’s optional outdoor thermostat controls the strips, not the compressor: it “prevents the electrical auxiliary heat (if used) from operating above a desired set point,” adjustable from 45°F to 0°F with a factory setting of 40°F. Rated low-temperature capacity is covered on our page on whether heat pumps work in cold weather.

The indoor electric heat strips can keep the house warm while the outdoor unit sits idle.
The indoor electric heat strips can keep the house warm while the outdoor unit sits idle. AI illustration.

Why is the house still warm if the outside unit is not running?

Because the air handler’s electric strips are heating it, and they need no outdoor unit at all. Rheem 708163B warns that “sustained use of electric resistance heat in place of the heat pump will result in an increase in electric utility costs,” and our auxiliary heat vs emergency heat page works through the cost. Rheem describes EM HEAT as “a back-up heating mode to be used only if there is a suspected problem with the outdoor unit,” so once you know the outdoor unit is down, switching to EM HEAT until the repair is the intended use.

Frequently asked questions

Why is the outside heat pump unit not running but the inside is?

The indoor blower and strips run on the air handler’s own circuit, so they keep going when the outdoor unit has no power or no signal. Rheem’s 708163B manual says EM HEAT locks the outdoor unit off on purpose. If the thermostat is on HEAT, check the outdoor breaker and disconnect, wait 15 minutes as Goodman advises, then have a technician check for 24 volts at the contactor coil.

Trane heat pump outside unit not running: what should I check?

Start with the same owner checks: HEAT mode, breaker, disconnect, a 15 minute wait. On older Trane and American Standard timer defrost boards, Trane’s publication 34-4101-07 uses B as the 24 volt common, not C: its service check reads “24VAC between B and Y terminals; if no voltage, check 24V wiring or indoor room thermostat.” A technician reads that voltage before replacing anything.

Can the outside unit of a heat pump freeze up?

Yes, and a light coat of frost is normal. Rheem’s 708163B says the coil “will develop a coating of snow and ice” in cold weather and the unit defrosts itself, with the compressor running and the fan stopped. A unit sealed in solid ice can trip a low pressure safety; Lennox’s XP17 flowchart counts those trips toward a five-strike lockout. Our heat pump defrost cycle page covers what normal defrost looks like.

Why is the heat pump outside unit not running when the AC is on?

The power and control checks are the same in cooling: thermostat mode, breaker, disconnect, the 5 minute delay, then 24 volts at the contactor. One cooling-only cause appears in Goodman’s IOG-3038A chart: on units with a low ambient control, it “should be open below 65°F outdoor temperature,” so a unit asked to cool on a cold day may stay off by design.

How we researched this

On November 26, 2026 we read the owner and service sections of Rheem 708163B, Goodman IOG-4002A and IOG-3038A, Lennox XP17 506586-01, the Carrier 25HNB6 wiring diagram, Copeland 47D40-801, Trane 34-4101-07 and BPA’s ecobee PTCS sheet. Forums, video and contractor blogs were excluded as sources; one top-ranking blog wrongly calls a fully silent unit a defrost cycle. The ecobee support article did not load. Timers, codes and pressures apply only to the series named.

Sources

  1. Rheem Manufacturing. “Outdoor Heat Pump User’s Information/Installation Instructions, 13 SEER (708163B).” https://files.rheem.com/LiteratureArchive/708163b.pdf. Accessed November 2026.
  2. Goodman Manufacturing. “Condensing Unit / Heat Pump Installation and Service Reference (IOG-4002A).” https://cdn.shopify.com/s/files/1/0253/0852/8730/files/Goodman_GSZ16_Installation_Manual__1.pdf. Accessed November 2026.
  3. Goodman (Daikin Comfort Technologies). “A/GPHH3 13.4 SEER2 H Series Packaged Heat Pump Installation Instructions (IOG-3038A).” https://pdf.lowes.com/productdocuments/99a0b2f9-433d-48c4-8bfd-27d752e771e7/71067956.pdf. Accessed November 2026.
  4. Lennox Industries. “XP17 Series Heat Pump Installation Instructions (506586-01).” https://www.lennox.com/lib/legacy-res/pdfs/installation_maintenance/lennox_xp17_iom.pdf. Accessed November 2026.
  5. Carrier. “25HNB6 Infinity 16 2-Stage Heat Pump Wiring Diagram (338054-101).” https://www.partstown.com/modelManual/CRR-25HNB6-English_wd.pdf. Accessed November 2026.
  6. Copeland (White-Rodgers). “47D40-801 Demand Defrost Control Instructions.” https://media.copeland.com/d9f5a9d4-30ab-4f1e-8bb7-b16b00f7d2d1/0037-7200-Instructions-47D40-801%20Demand%20Defrost%20Control.pdf. Accessed November 2026.
  7. Trane (American Standard). “Heat Pump Defrost Controls, Pub. No. 34-4101-07.” https://support.trane.com/hc/en-us/article_attachments/4423636411405. Accessed November 2026.