York furnace error codes are LED flash counts on the control board, read through the sight glass in the blower door. On York single and two-stage furnaces, 3 red flashes means the pressure switch is open, 4 red an open limit, 7 red no flame after three tries. 5, 6 and 12 red flashes change meaning by board.
| Flash pattern | York’s wording | Likely part | Owner check | Technician job |
|---|---|---|---|---|
| LED off | No power to board or blown board fuse | Supply, 3-amp fuse (TM8Y) | Breaker on, door seated | Find the short |
| Slow green or amber | Normal: standby (green) or call for heat (amber) | None | None | None |
| Continuous amber | Flame sense below 1.5 microamps (TM9Y 0.35, TM8Y 0.28) | Flame sensor, gas flow | None | Microamps at test pad |
| 4 amber | Y signal without G signal | Thermostat G wire | Still heats and cools | Land the G wire |
| Steady on, any color | Control failure | Board (TM9Y: fuse first) | Cycle power once | Replace board |
| 1 red | Flame sensed with no call for heat | Leaking gas valve | Stop: close gas | Valve test |
| 2 red | Pressure switch closed when it should be open | Switch, miswiring | None | Contacts, wiring |
| 3 red | Pressure switch open when it should be closed | Inducer, vent, hose | Vent ends clear | Inducer, manometer |
| 4 red | Main limit switch open | Filter, ducts, blower | Filter, registers | Temperature rise |
| 5 red | Rollout open (TG8S, TG9S, TM9E, TM8X); limit open over 15 minutes (TM8V, TM9V, TM8Y) | Rollout switch | Stop: no reset | Combustion air, heat exchanger |
| 6 red | Pressure switch opened four times in one call | Inducer, vent | Vent ends clear | Inducer, vent, switch |
| 7 red | No flame in three trials for ignition | Gas, ignitor, sensor | Gas valve switch ON | Gas pressure, ignitor |
| 8 red | Flame lost five times (four recycles) | Gas pressure, sensor | None | Gas pressure, valve |
| 9 red | Reversed polarity, grounding or transformer wires | House wiring | Stop: 115V | Polarity, ground |
| 10 red | Gas valve energized with no call for heat | Gas valve | Stop: close gas | Valve, wiring |
| 11 red | Limit open over five minutes: blower failure | Blower motor or wheel | None | Motor test |
| 12 red | Loose or missing model ID plug (TM9V) | ID plug | None | Reseat plug |
| 13 red | Second stage pressure switch open (TM8V, TM9V, TM9Y, TM8Y) | Vent, inducer, hoses | Vent ends clear | Manometer |
Those rows cover the TG and TM furnaces in the TG8S, TM9V and TM9Y manuals. The modulating YP9C keeps 1, 2, 3, 7, 8, 9 and 11 red but rewrites 4 amber and 5, 6, 10 and 12 red. No York document we found defines 14 red or higher.
How do you read a York furnace code before the door switch cuts power?
Count the flashes through the clear view port in the blower door while the furnace has power. The TM8Y manual says an interlock switch “interrupts all power at the unit when the panel covering the blower compartment is removed”, so pulling the door wipes the live code.
On TG and TM boards each flash is on for 1/3 second and off for 1/3 second, then a 2 second pause, repeating while the fault lasts. We calculated the cycle from that timing: 3 red repeats about every 4 seconds, 7 red every 6.7 seconds and 11 red every 9.3 seconds, so watch two pauses before trusting the count.
If the light was cleared, the board kept a history. York’s manuals say the control stores up to five error codes and the memory “will be retained even if power to the furnace is lost.” With no heat, cool or fan call active, a press of LAST ERROR plays them back newest first; two green flashes mean the memory is empty. Holding it over five seconds erases it, so photograph a control board history first.
Does a York furnace blinking red 3 times mean the same as 7 times?
No. Three red is an airflow failure before ignition; seven red is a failure to light. On 3 red the pressure switch never closed, and York lists the inducer, a blocked vent, the hose, wiring or the switch. The TM8Y manual adds “use manometer to verify vent pressure”, the test that separates a weak inducer from a bad switch.
Seven red means three trials for ignition produced no flame, then a one-hour soft lockout. York’s first check, the gas valve switch in the ON position, is an owner check; gas pressure, the ignitor and the sensor are technician work. Coleman house furnaces use a similar red flash scheme, but on Coleman manufactured home furnaces the green light blinks the fault, as the Coleman furnace error codes explain.

Why do 5, 6, 12 and 13 red flashes differ between York boards?
York changed boards several times, and the table changed with them. Johnson Controls service tip ST-045-09 says the UTEC board replaced White-Rodgers Emerson boards in August 2009, at serial prefix W0H9, on all single and two-stage furnaces, a date marker our serial number lookup lacked for York.
| Pattern | Emerson, before Aug 2009 | UTEC, 2009 | TG8S, TG9S | TM8V, TM9V | TM9Y, TM8Y | YP9C modulating |
|---|---|---|---|---|---|---|
| 4 amber | Y without G | Y without G | Y without G | Y without G | Y without G | Circulating air restriction |
| 5 red | Rollout or open fuse | Open rollout | Rollout open | Limit open over 15 minutes | TM9Y: either; TM8Y: limit | Rollout or condensate pressure switch |
| 6 red | Pressure switch cycle lockout | Pressure switch cycle lockout | Opened four times | Same | Same | Gas valve communication error |
| 12 red | Ignitor failure | Open HIS | Not listed | TM9V: ID plug | Not listed | ID plug missing or loose |
| 13 red | 3 double red instead | 3 double red instead | Not listed | High-fire pressure switch | Second stage pressure switch | Not listed |
| Twinning fault | Rapid red | Rapid red | Continuous green | Not to be twinned | TM8Y: continuous red | Not listed |
| Low flame warning | Rapid amber | Rapid amber | 1.5 microamps | 1.5 microamps | 0.35 (TM9Y), 0.28 (TM8Y) | 1.5 microamps |
The modulating line moved too. The 2010 YP8C manual calls 6 red a current failure on the modulating gas valve; the 2017 YP9C calls it a gas valve communication error.
What does a York furnace blinking amber, orange or green light mean?
Amber is York’s name for the orange or yellow light, and slow amber is normal heating. Fast or continuous amber is a weak flame signal. Four amber is a wiring notice on TG and TM furnaces but an airflow restriction on the YP9C, where five amber flags a blocked vent or clogged condensate drain and one, two and three amber are normal states.
Slow green is standby. Two green flashes mean an empty LAST ERROR memory; three confirm it was cleared. Continuous green on the TG8S and TG9S is a twinning fault, and rapid green on the YP9C is a factory speed-up mode that York says to stop by cycling power. Our flame sensor guide covers the amber fix.

Which York codes clear themselves, and which need a power cycle?
Codes 6, 7 and 8 red are one-hour soft lockouts that retry on their own, which York says protects an unoccupied house through a gas interruption. Five limit trips in one call also gives 4 red and a one-hour lockout. Codes 5 and 11 are hard lockouts that need power cycled after the repair, as our furnace reset guide describes.
Stop line: 1 and 10 red mean gas reached the valve or burners without a call, 5 red is a tripped flame rollout switch, and 9 red is 115V polarity or grounding. York’s manuals say to “never bypass any safety control”, including the limit switch behind 4 and 11 red.
Do Coleman, Luxaire and Champion furnaces use these York codes?
Some do, by shared manual rather than brand rule: the YP9C manual covers four model prefixes, YP9C, CP9C, LP9C and TP9C, under one flash table. Johnson Controls’ July 23, 2024 filing lists York, Coleman, Champion, Luxaire, Guardian and Evcon among the brands of the residential business it agreed to sell to Bosch for $8.1 billion; our brand ownership table tracks it. Otherwise, match the rating plate model to its manual, as our Trane furnace error codes page does.
Frequently asked questions
What does York furnace code 1 mean?
One red flash means the board sensed flame with no call for heat, and it turns on both the inducer and the supply air blower. York’s manuals point to a leaking or slow-closing gas valve. That is a gas fault, not a reset job: close the furnace gas valve and call for service.
What is York furnace code 11?
Eleven red flashes means the main limit opened and stayed open for more than five minutes. York names a failed blower motor or blower wheel as the usual cause. It is a hard lockout, so power must be cycled after the repair. On the TM9V the window is five to 15 minutes; past 15, the code becomes 5 red.
How do you reset a York furnace flame sensor?
The sensor has no reset. York’s manuals say to check and clean the flame sensor when the LED shows continuous or rapid amber, and give normal flame current as approximately 3.7 microamps DC. The warning starts at 1.5 microamps on most boards and at 0.28 on the TM8Y, so a technician confirms the fix with a meter at the test pad.
Why is my York furnace blinking a red light with no pause?
Red flashing with no 2 second pause is not a counted code. On the Emerson and UTEC boards rapid red is a twinning error, and the TM8Y manual lists continuous red for the same fault. York’s 2017 user manual tells owners that rapid red flashes mean a problem and to contact a dealer.
How we researched this
On November 6, 2026 we read the flash code sections of nine 2016 to 2017 Johnson Controls manuals on yorknow.com, the 2017 user manual, service tip ST-045-09 and six distributor-hosted 2010 to 2011 manuals, and extracted every flash definition by script for comparison. We excluded third-party code sites: none cited a York document, and several call 1 red an ignition failure. We found no York document for electric furnaces or two-character displays.
Sources
- Johnson Controls. “Installation Manual, TG8S*MP, TGLS*MP, 998491-UIM-C-0616.” https://www.yorknow.com/pub/media/documentation/TG8S_Install.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, TG9S Series, 1083287-UIM-H-0817.” https://www.yorknow.com/pub/media/documentation/TG9S_Install.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, TM9V*C Series, 5402851-UIM-A-0917.” https://www.yorknow.com/pub/media/documentation/TM9V_Install.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, TM9Y Series, 5052617-UIM-G-0817.” https://www.yorknow.com/pub/media/documentation/TM9Y_Install.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, TM8Y, 5052632-UIM-D-0217.” https://www.yorknow.com/pub/media/documentation/TM8Y_Install.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, YP9C/CP9C/LP9C/TP9C Series, 5402901-UIM-A-0917.” https://www.yorknow.com/pub/media/documentation/YP9C_Install.pdf Accessed November 2026.
- Johnson Controls. “User’s Information Manual, Residential Multi-position Gas Furnaces, 1010352-UUM-I-0917.” https://www.yorknow.com/pub/media/documentation/ResFurnaceUserManual.pdf Accessed November 2026.
- Unitary Products Group. “Service Tips ST-045-09: UTEC Integrated Furnace Control Boards.” September 2, 2009. https://upgnet.com/site/source1/pdf/st-045-09_york_utec_furnace_boards.pdf Accessed November 2026.
- Johnson Controls. “Installation Manual, TPLC, YPLC, CPLC, LPLC, 535678-UIM-B-0210.” Distributor-hosted copy. https://yorkwest.net/pdfs/yp8cinstall.pdf Accessed November 2026.
- Johnson Controls. “Form 8-K, Exhibit 99.1: Johnson Controls to Sell Residential and Light Commercial HVAC Businesses.” July 23, 2024. https://www.sec.gov/Archives/edgar/data/833444/000083344424000044/ex991.htm Accessed November 2026.

Leave a Reply