A heat pump blowing cold air in heat mode is often working: Carrier’s owner’s manual puts normal supply air at about 95 to 105°F, far below a furnace. Air colder than the room points to defrost (under 15 minutes), the thermostat’s fan, mode or O/B setting, a silent outdoor unit, low charge or a stuck reversing valve.
How warm should heat pump air be at 47°F, 17°F and 5°F outside?
Roughly 84 to 98°F for the two 3 ton systems we worked through, falling as it gets colder outside. Carrier’s 25VNA owner’s manual (OM25VNA-02) says a heat pump “delivers a constant flow of air at around 95°F (35°C) to about 105°F (41°C), compared to sudden blasts of hot air provided by a typical furnace.” Carrier’s own troubleshooting page gives a lower band, around 85 to 100°F, against roughly 120 to 140°F from a gas furnace.
We took the rated heating output of two real outdoor units from the ENERGY STAR certified heat pump dataset and turned capacity into a temperature rise with the sensible heat relation that Lennox prints in its XP17 installation instructions (506586-01): CFM equals Btu/h divided by 1.08 times the temperature rise. Airflow is 1,200 CFM, Goodman’s “400 CFM per ton” rule of thumb for a 3 ton system, and return air is 70°F.
| Outdoor temperature | Goodman GSZH503610, single stage: rated output | Goodman: supply air | Carrier 27VNA036, variable speed: rated output | Carrier: supply air |
|---|---|---|---|---|
| 47°F | 34,400 Btu/h | 96.5°F (rise 26.5°F) | 35,600 Btu/h | 97.5°F (rise 27.5°F) |
| 17°F | 20,000 Btu/h | 85.4°F (rise 15.4°F) | 30,600 Btu/h | 93.6°F (rise 23.6°F) |
| 5°F | 17,600 Btu/h | 83.6°F (rise 13.6°F) | 25,200 Btu/h | 89.4°F (rise 19.4°F) |
| 47°F, charge 30% low | about 26,800 Btu/h (NIST: capacity down 22%) | 90.7°F (rise 20.7°F) | not modeled | not modeled |
A single stage unit at 5°F still heats, but its air is only about 14°F warmer than the room. A 30% refrigerant undercharge, which NIST Technical Note 1848 measured as a 22% capacity loss at 47°F, only drops the Goodman’s air by about 6°F. A hand cannot feel that; a thermometer can. Variable speed blowers slow at part load, so real air can run warmer. Why the house still holds temperature is the balance point math in our page on a heat pump running constantly.

Is the supply air colder than the room, or only cooler than you expected?
After 10 minutes in HEAT, read the air at a supply register near the air handler and at the return grille, then subtract. Below zero means the system is cooling; about zero means only the blower is running; a positive rise well short of the table above means low capacity; a rise near the table means it works and simply feels cool next to a furnace.
Is it a defrost cycle if cold air lasts under 15 minutes and the outdoor unit steams?
Almost certainly. Goodman’s A/GPHH3 installation instructions (IOG-3038A) describe it plainly: defrost “is accomplished by reversing the heat pump to the cooling cycle”, the outdoor fan stops, and “the indoor blower continues to run and the supplementary heaters are energized.” Goodman’s board starts counting at a coil sensor of about 30 ± 5°F, uses 30, 60 or 90 minute intervals, and ends defrost at about 60°F or with a twelve minute override.
Cold air past 15 minutes is not defrost on any of the boards we read. If every defrost blows genuinely cold air, the supplementary heat is not coming on: a tripped air handler breaker (Carrier notes the indoor and outdoor units have separate breakers), a failed heater element or sequencer, or a system installed without strips. The full sequence is in our heat pump defrost cycle guide; a fan that stays stopped afterwards belongs to the outdoor fan diagnosis.
Which thermostat settings make a heat pump blow cold air in heat mode?
Three: the fan on ON, the system on COOL, and the O/B changeover set backwards. Rheem’s heat pump user’s information (708163B) says that with the fan switch on ON “the indoor blower will start immediately, and will run continually until the fan switch is reset to AUTO”, in any system position, including OFF. Between heating calls it moves unheated room air.
The O/B setting decides whether the thermostat energizes the reversing valve in cooling or in heating. Honeywell Home’s RTH8500WF support article says: “Most commonly, O/B is energized in Cooling (O on cool). For Rheem or Ruud brand heat pumps, the O/B must energize on heating (B on Heat).” Set wrong, the system cools on a heat call and heats on a cool call. The terminal letters are decoded in our thermostat wiring guide.
Why is the heat pump blowing cold air after a power outage, with the outdoor unit silent?
Because the indoor blower can run while the outdoor unit, which makes the heat, sits idle. Rheem 708163B says the outdoor unit “contains a protective timer circuit which holds the unit off for approximately five minutes following a previous operation, or the interruption of the main electrical power.” Wait 5 minutes after power returns before judging.
If the outdoor unit stays silent longer, Goodman’s troubleshooting chart lists the causes for “Unit will not run”: power off or a loose connection, a defective contactor (check for 24 volts at its coil), blown fuses or a tripped breaker, a defective transformer, an open high or low pressure control (610 psig and 22 psig on that series), or open compressor overload contacts, where Goodman says to “wait at least 2 hours for overload to reset”. Rheem says EM HEAT locks the outdoor unit off and runs the supplementary heat, so warm air on EM HEAT puts the fault outdoors. It costs more to run, as our auxiliary versus emergency heat page shows.

Air only a little warm: low refrigerant, low airflow or a reversing valve?
A short rise with the outdoor unit running is a capacity problem. NIST TN 1848 found a 30% undercharge cut heating capacity an average of 22% at 47°F, about 6°F off the supply air in our table. Low airflow from a clogged filter or closed registers starves the indoor coil; Goodman’s chart gives “approximately 400 CFM per ton” as the check value and warns never to run “below 300 CFM per ton”.
A reversing valve stuck in cooling gives cold air nonstop; one not seating fully gives weak heat. The technician reads suction and discharge pressures and checks for 24 volts at the valve coil, as covered in our reversing valve explainer. Anything that opens the refrigerant circuit is technician only: 40 CFR 82.161 requires anyone who could “violate the integrity of the refrigerant circuit” to pass an EPA certification exam.
Why does a Fujitsu or other mini split blow cold air in heat mode?
Mostly by design. Fujitsu’s wall mounted operating manual (part no. 9387602104), filed by Fujitsu General Canada under the ASUG09/12LMAS models, says that at the start of heating “the indoor unit fan rotates at very low speed for 3-5 minutes” to warm up. When the room is above the set temperature, “the outdoor unit stops and the indoor unit fan rotates at very low speed”, which moves unheated air. During defrost the indoor unit stops “for maximum of 15 minutes” while an indicator lamp blinks. After a blackout, auto restart resumes the previous mode.
Cold air outside those windows, with no blinking defrost lamp, means a fault; match any blink pattern against our Fujitsu mini split error code table.
Is cold air blowing out of the outside unit in winter normal?
Yes. In heat mode the outdoor coil is the evaporator: Goodman’s instructions explain that “the temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air.” Warm outdoor air in winter means the unit is cooling. Why it runs with the heat on is in our page on the outdoor unit in heating season; the furnace version is furnace blowing cold air.
Frequently asked questions
Why is my heat pump blowing cold air in summer?
In COOL mode that is the job. The question is whether it is cold enough. Goodman’s troubleshooting chart lists improper airflow, with about 400 CFM per ton as the check value, and incorrect refrigerant charge among the causes of insufficient cooling. Air that is warm in COOL mode points to the O/B setting or the reversing valve instead.
Why is my heat pump blowing hot air in cool mode?
Usually the thermostat’s O/B changeover is set backwards. Honeywell Home says most heat pumps energize O/B in cooling, but Rheem and Ruud heat pumps must energize on heating (B on Heat). A reversed setting heats on a cooling call and cools on a heating call. If the setting is right, a technician checks the reversing valve.
Does a heat pump blow cold air in defrost mode?
Cool, briefly, and less so when backup heat works. Goodman’s instructions say that during defrost the indoor blower keeps running and the supplementary heaters are energized, with a twelve minute override ending any cycle. Fujitsu’s ASUG09/12LMAS wall mounted manual says its mini splits instead stop the indoor unit for up to 15 minutes. Cold air beyond 15 minutes is not defrost.
Why is my HVAC blowing cold air when the heat is on?
On a heat pump, first rule out the fan set to ON, defrost and the 5 minute restart timer Rheem builds into its outdoor units. Then measure supply minus return air. Carrier puts normal heat pump supply air at about 85 to 100°F, against 120 to 140°F from a gas furnace, so lukewarm air with a positive rise is often normal operation.
How we researched this
Researched November 19, 2026. We read the ten documents listed under Sources, including 40 CFR 82.161 via the eCFR API. Capacities came from the ENERGY STAR dataset by AHRI reference number; supply temperatures are our calculation (1,200 CFM, 70°F return), not maker figures. Contractor blogs and forums were excluded as sources for any number; repair prices were excluded because no federal source publishes them.
Sources
- Carrier. “Owner’s Manual, 25VNA Infinity Heat Pump (OM25VNA-02).” https://www.partstown.com/modelManual/CRR-OM25VNA-02-English_om.pdf. Accessed November 2026.
- Carrier. “Heat Pump Not Heating? Here’s How to Troubleshoot.” https://www.carrier.com/residential/en/us/products/heat-pumps/heat-pump-not-heating/. Accessed November 2026.
- ENERGY STAR (US EPA). “ENERGY STAR Certified Air Source Heat Pumps” dataset w7cv-9xjt, AHRI 208511690 and 215679803. https://data.energystar.gov/Active-Specifications/ENERGY-STAR-Certified-Air-Source-Heat-Pumps/w7cv-9xjt. Accessed November 2026.
- Lennox. “XP17 Series Installation Instructions (506586-01).” https://www.lennox.com/lib/legacy-res/pdfs/installation_maintenance/lennox_xp17_iom.pdf. Accessed November 2026.
- Goodman. “A/GPHH3 13.4 SEER2 H Series Packaged Heat Pump Installation Instructions (IOG-3038A).” https://pdf.lowes.com/productdocuments/99a0b2f9-433d-48c4-8bfd-27d752e771e7/71067956.pdf. Accessed November 2026.
- Domanski, Henderson, Payne, NIST. “Sensitivity Analysis of Installation Faults on Heat Pump Performance (Technical Note 1848).” https://nvlpubs.nist.gov/nistpubs/TechnicalNotes/NIST.TN.1848.pdf. Accessed November 2026.
- Rheem. “Outdoor Heat Pump User’s Information and Installation Instructions (708163B).” https://files.rheem.com/LiteratureArchive/708163b.pdf. Accessed November 2026.
- Honeywell Home (Resideo). “Why is my RTH8500WF thermostat set to Heating, but I feel Cool or Mild Air?” https://www.honeywellhome.com/blogs/support/why-is-my-rth8500wf-wifi-series-wifi-touchscreen-programmable-thermostat-set-to-heating-but-i-feel. Accessed November 2026.
- Fujitsu General. “Operating Manual, Air Conditioner (Wall Mounted type), part no. 9387602104 (filed under ASUG09/12LMAS).” https://fujitsu-general.com/shared/ca/pdf-fcus-om-asug09-12lmas-01.pdf. Accessed November 2026.
- eCFR. “40 CFR 82.161 Technician certification.” https://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-82/subpart-F/section-82.161. Accessed November 2026.