Lennox Furnace Error Codes: Flashes, E-Codes and Alerts for Every Control Generation

Technician checking the control board on a Lennox gas furnace to read the furnace error codes

Lennox furnace error codes come in three generations. Older boards flash a red and a green LED in patterns, mid-generation boards flash one red LED 1 to 13 times, and current boards show E-codes such as E223 or E270 on a seven-segment display. Communicating Lennox thermostats report the same faults as numbered alerts.

Which Lennox control do you have: two LEDs, one red LED or a letter display?

Look through the blower door window first. A red and a green light mean the 2011 era table; one red light beside a small button means the flash-count table; a black window showing letters means the display table. Unlike the short and long flashes behind Carrier furnace error codes, no Lennox generation uses two-digit flash codes.

Look through the blower door window first1. Two LEDs#1#2LED #1 red, LED #2 greenRead as a pair:slow, fast, alternatingExample manual:ML180UH, 2011No code memory listed2. One red LEDLEDbuttonCounts 1 to 13 flashes,3 s pause, then repeatsRecall button: last 10Example manual:ML196UHE, 2024Boards 103217, 1071633. Letter displayE223display, buttonShows E223, E270 etc.plus status lettersA, C, d, H, h, UExample manuals:SL280DFNV, SLP99UHVKML196UHEK, 2026
The three Lennox control faces. Drawn by The HVAC Brief from Lennox manuals 506816-01, 507966-04, 508150-02, 508587-02 and 508569-01.

The model suffix settles it. Lennox’s 2024 ML196UHE manual flashes a single red LED, while the 2026 ML196UHEK manual for the same family shows E-codes on a seven-segment display. The 2011 ML180UH manual uses the red and green pair and warns installers to “Make sure to Identify LED’S Correctly.”

Older Lennox boards report faults by the pattern of two LEDs; newer ones use a small display.
Older Lennox boards report faults by the pattern of two LEDs; newer ones use a small display. AI illustration.

What does each Lennox code mean in each generation?

Lennox gives one fault three names. Start in the column for your control and read across.

Lennox fault wording Two-LED board (ML180UH, 2011) Red LED flashes (ML196UHE) Display code / thermostat alert Safe owner check Technician job
Normal: idle, cooling or fan Both slow, together Slow heartbeat Blinking decimal (.) Nothing Nothing
Normal: call for heat Both fast, together Continuous rapid flash (103217-03) H, blinking during ignition Nothing Nothing
Line polarity reversed Red fast, green slow 1 E111 / alert 111 None: line voltage wiring Swap line and neutral at the supply
Improper earth ground Both fast, alternating 2 E112 / alert 112 None Measure neutral to ground, fix the ground
Low line voltage Both fast, alternating (below 90 volts) 13 E110 / alert 110 Note any brownout Measure supply voltage under load
Low flame signal Red slow, green fast 4 E240 / alert 240 Nothing inside the burner box Read microamps; clean or replace the sensor
Burners failed 5 times: Watchguard Both slow, alternating 5 E270 / alert 270 Gas shut-off valves open; thermostat Heat, OFF, Heat once Gas pressure, ignitor, flame sensor
Limit switch open Red slow, green on 7 E250, then E274 / alert 274 Replace the filter; open supply and return grilles Firing rate, temperature rise, blower
Rollout switch open Red on, green slow 8 E200 / alert 200 Stop. Do not reset Find the rollout cause before any restart
Pressure switch open Red off, green slow 9 E223 or E227 / alert 223 Look for snow or debris at the vent terminations Inches w.c. at the switch, inducer, drain
Pressure switch stuck closed Red off, green slow 11 E224 / alert 224 None Test the switch; check for moisture in it
Flame sensed, gas valve not powered Red slow, green off 12 E241 / alert 241 Stop. Shut off the gas Gas valve leak test

Compiled by The HVAC Brief from Lennox 506816-01 (ML180UH), 507966-04 (ML196UHE, ignition controls 103217-03 and 107163-01), 508150-02 (SL280DFNV) and Alert Code Guide 100017. The two-LED table lists one pattern for pressure switch open and stuck closed.

A slow red light with a steady green light is a limit switch. Lennox says the limit must close within 3 minutes or the unit goes into a 1 hour Watchguard, as the furnace limit switch guide explains. A green light flashing alone is the pressure switch circuit, where Lennox also points condensing models to the drain and cracked hoses.

Which other E-codes appear on SL280DFNV, SLP99UHVK and ML196UHEK displays?

Lennox display boards add codes the flash boards never had; the third column shows which manual carries each.

Code Lennox wording In manual What it points to
E115 Low 24V N, P, K 24-volt range is 18 to 30 volts; a larger VA transformer may be needed
E203 Appliance capacity / size is NOT programmed N, P Unit size code must be set; three bars then E203 at power-up
E204 Gas valve mis-wired N, P, K Gas valve wiring, not an ignition lockout
E207 Hot surface ignitor sensed open N, P Ignitor resistance
E290 Ignitor circuit fault N, P, K Ignitor resistance; 1-hour soft lockout
E292 Indoor blower motor unable to start N, P Seized bearing or stuck wheel; 1-hour soft lockout
E294 Combustion air inducer over current N, P Inducer bearings, wiring and amps
E370 Interlock switch sensed open for 2 minutes N Blower door or interlock switch
E150 Refrigerant Leak detected P, K Leak sensor at the indoor coil; cannot clear while a leak is sensed

Compiled by The HVAC Brief from Lennox 508150-02 (N: SL280DFNV, 2024), 508587-02 (P: SLP99UHVK, 2025) and 508569-01 (K: ML196UHEK, 2026).

Watch the numbers that sound alike. E204 is “Gas valve mis-wired” in all three display tables. E223 is “Low pressure switch failed open” and E225 “High pressure switch failed open” on the two-stage SL280DFNV and SLP99UHVK. One top-ranked code site calls E204 an ignition lockout and E225 a rollout trip. E294 is a current fault at the inducer motor.

What does a blinking A, C, H or d mean on a Lennox furnace display?

Letters are status, not faults. The SL280DFNV table defines A as the blower cfm setting, C as a cooling stage, d as dehumidification, h as a heat pump stage and H as gas heat, “Blinking during ignition.” A decimal point blinking at 1 Hertz is idle; on the ML196UHEK A reads “Continuous Fan only mode.” Two horizontal bars mean soft disable, a device the communicating thermostat does not recognize; three bars then E203 at power-up mean the unit size code is not set.

Why is a Lennox furnace blinking red 5 times, or red continuously?

Five red flashes is Watchguard: the burner failed to light and used up its retries, which control 107163-01 labels a “1 hour lockout.” The ML196UHE sequence runs a 15 second prepurge, a 20 second ignitor warm-up and a 4 second trial, then four more tries before locking the gas valve out for 60 minutes. Thermostat Heat, OFF, Heat interrupts it.

Normal sequenceIf this step fails1. Thermostat calls for heat,inducer starts11 flashes / E224switch closed before inducer ran2. Pressure switch must closeto prove draft9 flashes / E223, E227switch open or opened in run3. 15 s prepurge, then theignitor gets 20 s to warmE207 / E290ignitor open or circuit fault4. Gas valve opens for a4 s trial for ignition3, then 5 flashes / E270no flame; 5 tries, 60 min lockout5. Flame sensor proves flame,burners run4, 7 or 8 flashesE240 low signal, E250 limit, E200 rollout
Sequence from Lennox ML196UHE manual 507966-04; flash counts from control 103217-03, E-codes from SL280DFNV manual 508150-02. Compiled by The HVAC Brief.

A continuous red light has two meanings. On control 103217-03, “Continuous Rapid Flash” is a normal call for heat. On control 107163-01 a solid red LED means “Board Fault Detected.” Each fault code is a burst of half-second flashes followed by 3 seconds dark.

Several codes that searchers pair with furnaces are outdoor unit alerts in Lennox's own guide.
Several codes that searchers pair with furnaces are outdoor unit alerts in Lennox's own guide. AI illustration.

What do Lennox thermostat alert codes 38, 274, 411, 413 and 434 mean?

Communicating Lennox thermostats show numbers from the Alert Code Guide 100017, and the furnace ones match the display E-codes without the E. Alert 274 is “GF Primary Limit Switch Open” for more than three minutes. Alert 38, “Not Heating when Requested,” means heat would not start for 45 minutes; the system goes off-line for 60 minutes, then retries.

The 400 series alerts belong to the outdoor unit. 411 and 413 are low and high pressure switch lockouts after five opens, and 434 is a lost link to the inverter, which flashes code 53. 412 is an open high pressure switch and 432 is “DC Link High,” not the flame failure and communication fault one top result lists.

How do you recall and clear Lennox codes, and when should you stop?

On the ML196UHE red LED controls, press and release the button to replay the last 10 codes, newest first; hold it longer than 5 seconds to clear them. Lennox says they are stored “including when power is shut off.” The 2011 ML180UH table lists no memory, so read that board before cutting power. On display boards, hold the button: release on E for the most recent 10 codes, on F for flame current, which the ML196UHEK rates normal above 1.5 microamps and drop out below 0.4 (our flame sensor guide explains the reading). SL280DFNV logs E370 after the door interlock is open 2 minutes, so a code taken with the door off may be your own.

Lennox’s owner checklist covers the thermostat, panels in place, the disconnect, fuses and breakers, the filter, gas on at the meter and the manual shut-off valves. Stop and shut off the gas for a rollout code (E200, 8 flashes) or flame without the gas valve energized (E241, 12 flashes), and for any gas smell. A technician meters the ignitor: one top result quotes 40 to 90 ohms for Lennox nitride ignitors, but the only Lennox figure we found, in service literature 100161, is 39 to 70 ohms for the ML180UHEK. Our guides to resetting a furnace and the furnace control board cover the next steps.

Frequently asked questions

How do I reset the blower motor on a Lennox furnace?

None of the Lennox manuals we read describes a blower reset button. On SL280DFNV and SLP99UHVK displays, E292 means the blower motor is unable to start, from a seized bearing or stuck wheel; it triggers a 1-hour soft lockout and clears after the circulator successfully starts. E295, motor over temperature, clears after the blower demand is satisfied.

Why is my Lennox furnace blinking a green light?

On two-LED Lennox boards such as the 2011 ML180UH, green is LED #2 and must be read with the red LED #1. Green slow with red off means the pressure prove switch is open or the vent is blocked. Green slow with red on means the rollout switch is open. Both flashing slowly together is normal.

What is Lennox furnace code 3228?

No Lennox document we opened defines a code 3228: it is absent from the SL280DFNV, SLP99UHVK and ML196UHEK furnace tables and from Lennox Alert Code Guide 100017. The seven-segment display does show numbers that are not faults: after an A, C or H, the SL280DFNV table says the cfm setting is displayed.

How we researched this

Researched November 6, 2026. We read the diagnostic tables in seven Lennox documents from lennox.com: installation instructions 506816-01 (ML180UH, 2011), 507966-04 (ML196UHE, 2024), 508150-02 (SL280DFNV, 2024), 508587-02 (SLP99UHVK, 2025) and 508569-01 (ML196UHEK, 2026), service literature 100161 (ML180UHEK) and Alert Code Guide 100017 (3/2023). Every code shown appears in one of those documents; display code lists were compared line by line. Third-party code sites were excluded: two top results give E204, E223, E225, 411, 412 and 432 meanings that contradict Lennox. The LennoxPros Error Code Lookup (login), an SLP98UHV mirror (offline) and the G61MPV manual (bot wall) could not be opened, so SLP98, EL296 and G61 boards are not covered separately.

Sources

  1. Lennox Industries. “SL280DFNV Installation Instructions, 508150-02, 04/2024.” https://www.lennox.com/dA/78477aadd3/508150-02a.pdf. Accessed November 2026.
  2. Lennox Industries. “SLP99UHVK Installation Instructions, 508587-02, 10/2025.” https://www.lennox.com/dA/725597ff88/508587-02.pdf. Accessed November 2026.
  3. Lennox Industries. “ML196UHEK Installation Instructions, 508569-01, 05/2026.” https://www.lennox.com/dA/505848b344/508569-01.pdf. Accessed November 2026.
  4. Lennox Industries. “ML196UHE Installation Instructions, 507966-04, 04/2024.” https://www.lennox.com/dA/2a12f2b40e/507966-04g.pdf. Accessed November 2026.
  5. Lennox Industries. “ML180UH Installation Instructions, 506816-01, 06/2011.” https://www.lennox.com/dA/c7cd7e796f/Lennox_ML180UH_IOM.pdf. Accessed November 2026.
  6. Lennox Industries. “Unit Information: ML180UHEK, 100161.” https://www.lennox.com/dA/65a4ebdb88/100161.pdf. Accessed November 2026.
  7. Lennox Industries. “Residential Communicating Systems Alert Code Guide (V2), 100017.” https://www.lennox.com/dA/d89d9db1dd/100017c.pdf. Accessed November 2026.

Comments

One response to “Lennox Furnace Error Codes: Flashes, E-Codes and Alerts for Every Control Generation”

  1. […] Lennox 507966-04 and Goodman RS6612022R1. Other brands number the same fault differently; check the Lennox flash code table or your brand’s […]

Leave a Reply