A garage unit heater not igniting has stopped at one step of a fixed sequence: inducer, pressure switch, spark, gas valve, flame sensor. Watch the first 60 seconds and count the board LED. On Modine Hot Dawg, Reznor UDXC and Mr. Heater Big Maxx units, that count names the failed step.
What should a gas garage unit heater do in the first 60 seconds after the thermostat calls?
Inducer, pressure switch, purge, spark with the gas valve, flame proof, then fan. Modine’s Hot Dawg guide lists that order, ending: “50 to 60 seconds later, the fan motor cycles on.”
All three makers use direct spark ignition, not a hot surface igniter or standing pilot. Under 10 CFR 431.246, a unit heater made on or after August 8, 2008 must have an intermittent ignition device. An older heater with a standing pilot fails more like a furnace pilot light.
Which step failed? Match the LED count to the brand on your heater
Read the code before any reset, because a reset starts the sequence over. The Reznor UDXC board stores the last five fault codes and replays them on its display when power is cycled, per the Reznor UBXC/UDXC manual. Counts are not portable: 3 flashes is a vent fault on a Mr. Heater MHU but an open limit on a Modine HD.
| What you see | Step that failed | Modine Hot Dawg HD (green LED) | Reznor UDXC (display) | Mr. Heater MHU (green LED) |
|---|---|---|---|---|
| Nothing runs, LED dark | Power, 24 V transformer or board fuse | Green light off; check 24 VAC at Sec and Com, then the fuse | Off: internal fault or power failure | Steady off: loss of power, check 3 A fuse |
| Inducer never starts | Exhaust motor or board output | 1 flash, no power exhauster | No code listed; manual’s “venter motor will not start” chart | 3 flashes |
| Inducer runs, no spark | Pressure switch not closed in 30 seconds | 1 flash | 3 | 3 flashes |
| Will not start, inducer off | Pressure switch closed before inducer | 2 flashes | 4 | 3 flashes |
| Sparks or clicks, no flame, then quits | Gas, igniter or valve | 4 flashes after five tries | L | 2 flashes |
| Lights, goes out within about 10 seconds | Flame sensing or reversed polarity | 4 flashes | L, or 7 for reversed polarity | 2 flashes (under 0.6 microamps) |
| Burns a few minutes, then shuts off | High limit or rollout switch | 3 flashes, or 6 flashes if the fan fails | 5 | 4 flashes |
| Flame present with valve off | Valve leaking through | Yellow flame LED flashes fast | 6 | 5 flashes |
Inducer runs but it never sparks: is the pressure switch or the vent at fault?
Usually the vent or the switch tubing. Modine’s first cause for 1 flash with the exhauster running is a blocked tube or vent “not allowing for a proper vacuum to pull pressure switch contacts closed” within 30 seconds; Reznor’s chart says to remove obstructions from the vent. Drifted snow over a sidewall cap does it the way a furnace vent blocked by snow does.
For the MHU 3 flash code, Mr. Heater says to pull the switch tubing off the exhaust fan hose barb and push a thin object through the barb “PLUS at least another 1/2 inch” into the housing. If tube and vent are clear, a technician meters the switch, as our furnace pressure switch page shows; a motor that hums without spinning is an inducer motor failure.
Condensate is the cold garage suspect. Mr. Heater requires a condensate tee and drain within the first 5 ft of an upward sloped vent and warns it may freeze if the unit sits off below freezing.

It clicks and sparks but the burner never lights: is it the gas supply?
Usually. Modine’s “sparks but doesn’t ignite” branch lists the gas valve switch left off, no 24 VAC to the valve, excessive inlet pressure, and low or no gas pressure (“purge lines”). The unit cycles five times, then shows 4 flashes.
A technician measures inlet pressure at the tap with the heater firing and checks that no regulator locks up above 14 in. w.c., an item on Modine’s board checklist.
| Maker and series | Natural gas inlet | Propane inlet | Ignition tries before lockout | Automatic retry |
|---|---|---|---|---|
| Modine Hot Dawg HD/HDB (6-583.11) | 6 to 7 in. w.c. | 11 to 14 in. w.c. | 4 tries per manual; the guide says it cycles five times | After at least 1 hour |
| Reznor UBXC/UDXC (08-24) | 5 to 14 in. w.c. | 11 to 14 in. w.c. | 4 (initial try plus three retries) | After 1 hour |
| Mr. Heater MHU50/80/125 | Minimum 5.0 in. w.c. firing | Regulator 11 to 14 in. w.c. | 3 trials of 10 seconds | After 60 minutes |
A propane heater that quit when the tank ran dry needs the leak check covered in furnace not working after a propane refill. Switching fuels takes the maker’s kit: Mr. Heater requires a changeover kit, and Modine points to its propane kits (Manual 75-515) though it uses the same burner for both gases.
No spark at all: igniter, spark gap or a missing ground?
Look for a cracked ceramic, a wrong gap, or a broken ground. Modine notes that with no spark, raw gas flows for about six seconds per try, so do not keep resetting a heater that never snaps. Reznor sets the gap at 1/8 inch; Mr. Heater gives 0.110 to 0.140 inch.
Reznor’s no spark list adds a spark cable or electrode shorted to ground, an ungrounded burner or board, and the 3 A board fuse, and says the brown ground wire must stay on the igniter. Our furnace igniter page covers hot surface parts, which these heaters do not use.
It lights, then goes out after a few seconds: flame sensor or polarity?
Usually. Modine lists reversed polarity first for “sparks and shuts down after 10 seconds,” then a loose sensor wire, then a dirty sensor cleaned with emery cloth. Reznor shows 7 for reversed polarity.
Thresholds differ: Reznor requires 1.0 microamps minimum; Modine calls 1 to 5 micro-amps proper; Mr. Heater calls 0.6 to 1.0 microamps normal and locks out with 2 flashes below 0.6. The cleaning steps match those for a furnace flame sensor.
How do you reset a garage heater lockout, and when does it retry on its own?
Interrupt the call for heat; never light the burner by hand. Modine and Reznor reset a soft lockout when power is off for more than 1 second, or the call is removed for more than 1 and less than 20 seconds; otherwise they retry after an hour. Mr. Heater says to move the thermostat from HEAT to OFF and back.
Reset once after fixing the cause. Leave the gas valve off if you smell gas, see flame rolling out, or find a tripped manual reset rollout: Mr. Heater says to check combustion air before resetting one, the same caution as a tripped furnace limit switch.

Can a cold garage or a low mounting height stop the heater from lighting?
Cold can; height does not, though it is a code issue. Reznor says not to run unit heaters where the space is below 40°F (4°C) because condensation forms in the heat exchanger. Modine’s HD manual gives low profile heaters ambient startup between -40°F and 90°F and operation between 40°F and 90°F. For sizing a replacement, see our garage heating and cooling guide.
The 2021 International Fuel Gas Code, as reprinted by Seattle, puts the ignition source at least 18 inches above a private garage floor (305.3) and the appliance 6 feet up unless protected from vehicles (305.5). Mr. Heater asks for 8 feet to the bottom of an MHU; Modine says 7 ft unless guarded. The local inspector decides.
Frequently asked questions
Why is my Mr. Heater Big Maxx not igniting?
Count the green LED on the board. Per the MHU50/80/125 manual, 2 flashes means it failed to detect or sustain flame, 3 flashes means the pressure switch failed closed or open, and 4 flashes means a high limit or rollout switch is open. It tries three times with 10 second trials, then waits 60 minutes before retrying on its own.
Can a natural gas garage unit heater run on propane?
Only with the maker’s conversion kit. Mr. Heater says a natural gas to LP changeover kit is required for the MHU, and Modine directs conversions to its propane kits in Manual 75-515 even though the same burner serves both gases. Propane inlet pressure must then fall in the 11 to 14 in. w.c. window that Modine, Reznor and Mr. Heater each list.
What thermostat works with a garage unit heater?
A 24 V heat-only thermostat wired to R and W; Modine’s troubleshooting table says to verify connections to the R and W terminals only. Mr. Heater warns that its spark board emits radio noise that can disturb a microprocessor thermostat and recommends an isolation relay. Our thermostat wiring guide explains the terminal letters.
Can garage unit heater venting be PVC?
Not on the Modine HD: its manual says “Do not vent unit with PVC or other forms of plastic venting material.” For horizontal commercial installs in buildings not attached to living space, Mr. Heater allows sealed single wall Category III stainless vent on the MHU. Vent material, diameter and length come from each maker’s manual.
How we researched this
On November 26, 2026 we read the Modine HD/HDB manual (6-583.11) and Hot Dawg Troubleshooting Guide, the Reznor UBXC/UDXC manual (08-24) and UDX specification, the Mr. Heater MHU50/80/125 manual, 10 CFR 431.246, and the 2021 Seattle Fuel Gas Code Chapter 3. Codes appear only where one of those documents defines them. We excluded Dayton heaters (no manual obtained) and older Reznor UDX and Modine boards, whose codes may differ. Forum and contractor pages in the current results were read for questions only.
Sources
- Modine Manufacturing. “Installation and Service Manual: Gas-Fired Unit Heaters Model HD and HDB (6-583.11).” https://www.modinehvac.com/wp-content/uploads/2020/01/Hot-Dawg-Power-Vented.pdf. Accessed November 2026.
- Modine Manufacturing. “Hot Dawg Troubleshooting Guide: Troubleshooting HD Direct Spark Units” (distributor-hosted copy). https://northstock.com/content/product-catalogs/modine/Modine-Hot-Dawg-Troubleshooting-Guide.pdf. Accessed November 2026.
- Reznor. “Gas-Fired Unit Heater Installation, Operation, and Maintenance: Models UBXC and UDXC (UBXC-UDXC-IOM 08-24).” https://res.cloudinary.com/dzhpkjoqj/image/upload/v1731427980/Reznor/UBXC-UDXC-IOM. Accessed November 2026.
- Reznor. “UDX Series Technical Specifications” (distributor-hosted copy). https://www.sidharvey.com/documents/UDX-200.pdf. Accessed November 2026.
- Mr. Heater (Enerco). “Operating Instructions and Owner’s Manual: MHU50, MHU80, MHU125 Compact Unit Heater” (retailer-hosted copy). https://images.toolsid.com/mr-heater/items/pdf/big-maxx-unit-heater-manual.pdf. Accessed November 2026.
- U.S. Department of Energy via eCFR. “10 CFR 431.246 Energy conservation standards and their effective dates (unit heaters).” https://www.ecfr.gov/current/title-10/section-431.246. Accessed November 2026.
- City of Seattle. “2021 Seattle Fuel Gas Code, Chapter 3: General Regulations.” https://www.seattle.gov/documents/Departments/SDCI/Codes/FuelGasCode/2021SFGCChapter3.pdf. Accessed November 2026.