Furnace not working after a power outage? Wait 5 minutes first: the control restarts its whole sequence, and a Resideo S9200U1000 board will not accept a heat call for about 20 seconds, then purges for 30. If it still fails, check the breaker, the service switch and the board fuse, and read the LED code before cutting power again.
Which symptom do you have once the lights come back on?
One of five: no power, no heat call, no draft proof, no flame, or a stored fault. Watch one full attempt with the blower door closed, then follow the chart.
| Symptom | Likely cause | Owner check | Confirming reading |
|---|---|---|---|
| LED off, silent | Breaker, service switch, door switch, board fuse | Breaker fully off then on; door seated | Goodman: 24 V at transformer, about 13 volts R to C = blown fuse |
| LED steady, no start | No heat call from thermostat | Heat mode, setpoint, AA batteries | Resideo PRO 3000: wait 5 minutes for the system to respond |
| Inducer runs, no glow | Frozen drain, iced vent, blocked hose | Vent and intake outside; ice in drain hose | Amana 50A65: 3 short flashes |
| Glows, no flame | Gas knob off or gas supply off | Knob on ON; other gas appliances lit | Amana: 1 flash, lockout after 3 attempts |
| Lights, then drops out | Flame not proven: ground, polarity, sensor | On a generator? Count flashes | Copeland 50M56D-751: code 25 |
| Blower only, no heat | Normal restart on some boards | Wait 2 full minutes | Copeland code 12; Rheem R801T 2 minute run |
What should the furnace do in the first 2 minutes after power returns?
It should self check, prove draft, purge and heat the igniter before any gas flows: on a Resideo S9200U1000 that is at least 67 seconds (20 + 30 + 17). Silence for 20 seconds, or a blower running with no flame for 2 minutes, can be normal.
| Control board | After power returns | Trials before lockout | Lockout clears by |
|---|---|---|---|
| Resideo S9200U1000 (universal) | Accepts W after approximately 20 seconds; 30 second prepurge; igniter 17/27 or 30/30 seconds | Three | 60 minutes, or power cycle |
| White-Rodgers 50A65 (Amana single stage) | 30 second purge, 20 second igniter preheat | Three | Thermostat off more than 5 and less than 20 seconds; or one hour |
| Copeland 50M56D-751 (Carrier replacement) | Code 12 if the blower starts after power up | 3 retries or 10 recycles | 24 VAC off greater than 10 seconds; or 1 hour |
| Rheem R801T (80+ Ultra Low NOx) | Inducer and blower run a 2 minute period, then a learning cycle | Four | Power cycle; or one hour |
Rheem’s manual: “if main power is interrupted the IDM and main blower will be energized for a 2 minute period prior to the learning cycle.” Our ignition sequence walkthrough shows where later failures stop.
No lights at all: is it the breaker, the service switch or the board fuse?
A dark LED means the board has no power. Ready.gov warns that power “may return with momentary surges or spikes that can cause damage,” which trips breakers and blows the low voltage fuse. Outages are getting longer, mostly because of major storms, as our power outage statistics by state show.
Reset the furnace breaker, check the service switch, press the blower door shut. Read the sight glass first: Goodman’s RS6612022R1 says removing it without holding the switch “will result in the loss of the stored failure code.” The Resideo S9200U1000 carries a 3.0 amp automotive type fuse, and the Copeland 50M56D-751 reports an open one as code 24, “Secondary Voltage Fuse is Open.” A fuse that blows again points to a shorted control wire, traced in our furnace control board guide; a breaker that trips again is covered in why an HVAC breaker keeps tripping.
A steady LED with no start is the thermostat. The Resideo PRO 3000 guide says settings are “permanently stored in memory, and do not require battery power”; batteries only keep the display lit. A dark screen is its own branch, Honeywell thermostat blank screen, and the AC version of this diagnosis covers the outdoor unit.

The inducer runs but it never lights: did the condensate drain freeze?
On a 90% furnace, check that first: hours without heat can freeze a trap in a garage or attic, and the pressure switch stays open.
Goodman’s RS6610004 says that if the trap and drain line “will be exposed to temperatures near or below freezing, adequate measures must be taken,” recommending insulation or heat tape, and its RS6612022R1 chart lists a “blocked drain system” as a cause of an inducer that runs with no furnace operation. On an Amana 50A65 board the switch gets 5 minutes, then the control enters a 1 hour lockout. Clear snow from the vent pipes, thaw the trap with warm water, reset once. Snow that buries the intake or exhaust between storms has the same effect, and a furnace vent blocked by snow shows how to clear the pipe ends without cracking them. Hose and inducer tests are on our furnace pressure switch page.
What do Amana furnace blinking codes mean after a blackout?
Goodman’s service manual RS6610004 covers Amana brand furnaces and prints flash codes for two White-Rodgers controls. Count flashes between pauses before touching the power.
| Flashes | 50A65 (Amana 80% and 90% single stage) | 50V61 (Amana variable speed) |
|---|---|---|
| Off | Internal failure, no power or blown fuse | Same |
| 1 | Lockout after gas valve cycled 3 times | Same |
| 2 | Pressure switch stuck closed | Low stage pressure switch stuck closed |
| 3 | Pressure switch stuck open; 1 hour lockout | Same |
| 4 | Open primary or auxiliary limit | Same |
| 5 | Flame sensed with no call for heat | Same |
| 6 | Open rollout limit | Not listed in the 50V61 text |
| 7 | Low flame sense signal | Same |
| 8 | Igniter circuit or poor ground (AMS8, AMS9, ADS8, ACS9) | Igniter or no ground condition |
| 9 | Not listed in the 50A65 text | High stage pressure switch stuck open |
| Continuous | Reversed polarity or poor unit ground | Same |
Two and three blinks are both pressure switch faults, which is why a frozen drain often shows as 3 flashes. Six flashes is the rollout limit, which the manual ties to restricted flue piping; Rheem’s R801T text for that switch reads “DO NOT jumper or reset this switch.” Tri color and display boards are sorted in our Goodman furnace error codes table.
How many times should you reset a furnace after a power outage?
Once. Every board above clears a soft lockout by itself after one hour, and Goodman’s note is blunt: “If the furnace frequently has to be reset, it means that a problem exists that should be corrected.”
Set the thermostat to Off, switch the furnace off for at least 10 seconds (the Copeland board needs greater than 10, the Amana 50A65 at least 5), restore power and call for heat. A second lockout with the same flash count makes the code your diagnosis. Rollout buttons and oil burners follow other rules in our furnace reset guide.
Does a standing pilot go out when the power goes out?
Usually not. The Honeywell VR8200 sheet says “Loss of power closes the automatic valves, but leaves the pilot lit, ready to return to normal service when power is restored,” because a 30 mV thermocouple, not house power, holds the pilot valve.
A pilot that is out afterward means a gas interruption, a draft or a weak thermocouple. Resideo label 69-0183 says to turn the knob to OFF and “wait five (5) minutes to clear out any gas,” then hold the reset about one (1) minute after lighting; steps are in our furnace pilot light guide. Smell gas? Light nothing and call the gas supplier from outside.

Can a generator run the furnace, and why does it lock out on one?
Yes, through a transfer switch with a proper neutral and ground. A furnace that drops flame only on generator power has a grounding or polarity problem (Copeland code 25).
OSHA’s generator grounding fact sheet says never connect a portable generator to a home’s wiring “unless the generator has a properly installed open-transition transfer switch,” and points to Article 250 of the National Electrical Code for grounding; permits are set locally. Goodman’s RS6612022R1 warns that a missing earth ground, reversed polarity “or a high resistance connection in the neutral line may cause the control to lockout due to failure to sense flame,” and wants under 2 ohms from neutral to burner. Size for the blower’s start, using these ceilings:
| Moment | Loads | Amps | Watts |
|---|---|---|---|
| Prepurge and igniter | Inducer + igniter | 4.0 | 480 |
| Blower start | Locked rotor + inducer | 27.8 | 3,336 |
| Steady heating | Blower + inducer | 12.8 | 1,536 |
| Rheem R801T circuit | 15 A limit | 15 | 1,725 |
Ready.gov puts the generator outdoors “at least 20 feet away from windows, doors and attached garages,” with battery backed carbon monoxide alarms on every level; our carbon monoxide detector placement page lists where they go. A generator covers only part of a long outage, and how to keep a house warm during a power outage starts in the first hour by moving everyone into a single interior room and blocking its gaps with towels.
Frequently asked questions
Why is my Amana furnace blinking 3 times?
On the White-Rodgers 50A65 and 50V61 controls Goodman documents for Amana furnaces, three flashes means the pressure switch is stuck open; after 5 minutes the control goes into a 1 hour lockout. After an outage, check for a frozen condensate drain and snow over the vent pipes.
What does Amana furnace code 1 dl mean?
No Amana or Goodman document we opened defines a code written “1 dl.” On the Amana 50A65 board a single flash means lockout after the gas valve cycled 3 times without flame. Display boards use a different table, so identify your board first.
What does a blinking orange or yellow light mean on an Amana furnace?
The two Amana controls in Goodman manual RS6610004 use one LED and define faults by flash count, not color. Amber codes belong to other boards, such as the Copeland 50M56D-751, where amber 41 means a weak flame sensed and amber 42 is normal heat mode.
How we researched this
In November 2026 we read the sequence and fault sections of Goodman RS6610004 and RS6612022R1, the Copeland 50M56D-751 sheet, the Rheem R801T manual, Resideo 69-2075, 69-0183 and 69-1776EFS, the Honeywell VR8200 sheet, OSHA’s generator grounding fact sheet and Ready.gov. Each timing or code row comes only from the board its document covers. We excluded ranking contractor articles (no maker citations) and forum rules of thumb; the National Electrical Code is cited only as OSHA restates it.
Sources
- Goodman Manufacturing. “Service Instructions RS6610004: 80%, 90%, 95% Gas Furnaces and Accessories.” https://s3.amazonaws.com/s3.supplyhouse.com/product_files/Goodman-GMS951155DXA-Install-Instructions.pdf. Accessed November 2026.
- Goodman Manufacturing. “Service and Troubleshooting RS6612022R1: GM9S92 / GM9S96 / AM9S92 / AM9S96 Single Stage Gas Furnaces.” https://mobile.goodmanmfg.com/mobileapp/stellent/pdf/infoPdf/Lit/RS6612022R1.pdf. Accessed November 2026.
- Copeland (White-Rodgers). “50M56D-751 Carrier Integrated Single Stage 120V Hot Surface Ignition Control Kit, Installation Instructions.” https://media.copeland.com/7b1c16cb-45cd-45fe-8e23-b16b0109fc57/0037-7757001%20%2D%2050M56D-751%20Instruction%20Sheet%20(EF).pdf. Accessed November 2026.
- Rheem Manufacturing. “Installation Instructions for Upflow/Horizontal Single Stage Ultra Low NOx Gas Furnaces (R801T).” https://resource.gemaire.com/is/content/Watscocom/Gemaire/rheem_r801t_en_ii.pdf. Accessed November 2026.
- Resideo. “S9200U1000 Universal Hot Surface Ignition Integrated Furnace Control, 69-2075.” https://www.cochranesupply.com/media/assets/product/documents/Honeywell/S9200U1000.pdf. Accessed November 2026.
- Resideo (Honeywell). “VR8200; VR4200 Combination Gas Controls, 68-0046.” https://www.cochranesupply.com/media/assets/product/documents/Honeywell/VR8200.pdf. Accessed November 2026.
- Resideo. “For Your Safety Read Before Lighting, lighting instructions label 69-0183.” https://res.cloudinary.com/dzhpkjoqj/Resideo/69-0183.pdf. Accessed November 2026.
- Resideo. “PRO 3000 Non-Programmable Digital Thermostat, owner’s guide 69-1776EFS.” https://res.cloudinary.com/dzhpkjoqj/Resideo/69-1776EFS.pdf. Accessed November 2026.
- Occupational Safety and Health Administration. “Grounding Requirements for Portable Generators.” https://osha.gov/OshDoc/data_Hurricane_Facts/grounding_port_generator.pdf. Accessed November 2026.
- Ready.gov (FEMA). “Power Outages.” https://www.ready.gov/power-outages. Accessed November 2026.

Leave a Reply