Daikin Mini Split Error Codes: How to Read Them From the Remote, and What Each Means

Homeowner aiming the remote at a wall unit to read daikin mini split error codes

Daikin mini split error codes are two characters, such as U4, A5 or E7, and a wall unit only blinks its operation lamp until you ask the remote. Hold TIMER CANCEL for 5 seconds until 00 shows, then press it again and again: the code on screen at the long beep is the fault.

Every meaning below is from Daikin service manuals SiUS041829EA (FTXR-T) and SiUS091601E (FTX-N and FVXS-N), checked against Daikin’s global SM-TS3 code list. Read the code before any power cycle.

How do you read a Daikin mini split error code from the remote before cutting power?

Point the remote at the indoor unit, hold TIMER CANCEL for 5 seconds until 00 appears, then press it one step at a time. Both manuals call this Method 1 for the ARC466 and ARC480 remotes: a short beep or two beeps means “not this code”, and a long beep marks the stored fault.

1. Aim the remote at the indoor unitHold TIMER CANCEL for 5 seconds2. 00 shows on the remote display00 means Normal: no fault at this step3. Press TIMER CANCEL onceThe remote steps to the next code in its list4. Listen to the indoor unitShort beep or two beepsNot your code:press TIMER CANCEL againLong beepThe code on the displayis the stored fault5. Write the code downHold TIMER CANCEL 5 seconds to exit,or leave the remote alone 60 seconds
Daikin Method 1 retrieval as written in service manuals SiUS041829EA (ARC466) and SiUS091601E (ARC480 and ARC466). Drawn by The HVAC Brief.

Both manuals warn that “Not all the error codes are displayed” in that list. For those, Method 2 opens a service check: on the ARC466, press the center of the TEMP button and MODE together, pick 5C, and press MODE; on the ARC480 it is TEMP with OFF, then FAN. You then step each digit with TEMP until the long beep.

What does each Daikin code mean on FTX-N and FTXR-T wall units?

Both manuals group U codes as System, A and C codes as Indoor Unit, and E, F, H, J, L and P codes as Outdoor Unit, and print the trip condition for each. LG uses a single run of CH numbers instead, with separate codes for lost indoor to outdoor communication and for low refrigerant, as the LG mini split error codes show.

Code Daikin’s description Trip point (manual) Owner check Technician job
00 Normal No fault None None
U0 (FTXR-T) Refrigerant shortage No page given Do not add refrigerant Leak search
U2 Low-voltage detection or over-voltage detection DC bus below 180 to 196 V or above 458 to 500 V Breaker on Supply voltage
U4 Signal transmission error (between indoor unit and outdoor unit) Outdoor data lost Outdoor disconnect on Wire No. 3, LED A
UA Unspecified voltage (between indoor unit and outdoor unit) Pair and multi models mixed None Model match
A1 Indoor unit PCB abnormality Settings fail One power cycle Indoor PCB
A5 Freeze-up protection control/heating peak-cut control Coil below 32°F cooling; above 144.5°F (FTXR-T) or about 140°F (FTX-N) heating Clean filter Coil, thermistor
A6 Fan motor (DC motor) or related abnormality Under 50% of maximum speed One power cycle Fan motor, PCB
C4, C9 Indoor heat exchanger thermistor (C4); room temperature thermistor (C9) 4.96 V or more, or 0.04 V or less None Thermistor
C7 (FTXR-T) Front panel open/close fault Repeats Panel moves freely Reduction motor
E1 Outdoor unit PCB abnormality Zero-cross signal missing One power cycle Outdoor PCB
E5 OL activation (compressor overload) Overload opens Clear outdoor coil Charge, valves
E6 Compressor lock Locked rotor None Stop valve, harness
E7 DC fan lock Fan not started in 15 to 30 seconds Power off; remove foreign matter Fan motor
E8 Input overcurrent detection About 12.0 to 12.5 A for 2.5 seconds None Compressor, power module
EA Four way valve abnormality Coil 9°F wrong side of room for 10 minutes None Valve coil
F3 Discharge pipe temperature control Above 230°F Clear outdoor coil Charge, expansion valve
F6 High pressure control in cooling Outdoor coil 135.5 to 140°F Clearances, clean coil Outdoor fan
F8 (FTXR-T) System shutdown due to compressor internal temperature abnormality 261.5°F in forced cooling None Air in circuit
H0, H6, H8 Compressor system sensor; position sensor; DC voltage/current sensor Out of range None Harness, outdoor PCB
H9, J3, J6, P4 Outdoor air, discharge pipe, outdoor coil and radiation fin thermistors 4.96 V or more, or 0.04 V or less None Thermistor
L3, L4 Electrical box temperature rise; radiation fin temperature rise Fin above 179.6°F (off) or 210.2°F (on) Outdoor fan free Fan motor
L5 Output overcurrent detection Inverter overcurrent None Stop valve, compressor

Compiled by The HVAC Brief from Daikin service manuals SiUS041829EA (FTXR-T with RX09/12/18RMVJU9) and SiUS091601E (FTX-N and FVXS-N with RXL09/12/15QMVJU). Rows marked FTXR-T, plus H8, appear only in that table. Thresholds are FTXR-T 09/12 class unless noted.

Owners can often clear A5 themselves: both manuals list a clogged air filter and indoor coil dust as causes, and it trips in cooling when the coil drops below 32°F. A filter cleaned as our mini split cleaning guide describes is the first test.

How many TIMER CANCEL presses until U4, A5 or E7 shows up?

On the ARC466 and ARC480 remotes, A5 is one press past 00, E7 two, F3 three and U4 eight. On the older ARC433B list the order changes and U4 comes first, so a count that worked on one remote is wrong on another.

Code ARC466 remote ARC480 remote ARC433B67/68/69/76
A5 1 1 21
E7 2 2 10
F3 3 3 2
U4 8 8 1
E6 9 9 3
U0 13 13 9
A3 15 15 14
E5 23 25 6
E1 25 27 23
U2 30 34 29
EA 31 35 31
E8 Not listed: Method 2 38 Not listed: Method 2
F8 Not listed: Method 2 Not listed: Method 2 Not listed: Method 2

HVAC Brief calculation: presses of TIMER CANCEL after 00 appears, assuming each press advances one step, from the sequence tables in SiUS041829EA, SiUS091601E and Daikin SM-TS3. The lists hold 38, 43 and 33 codes.

Reach the end without a long beep and the remote returns to normal after 60 seconds untouched. Then use Method 2: E8 and F8 sit in the FTXR-T code table but not in the ARC466 step list.

Why is a Daikin blinking green, blue, red or orange light not always a fault?

On FTXR-T units the colored multi-monitor lamp shows the mode: Blue for COOL, Red for HEAT, Green for DRY, White for FAN, Red/Blue for AUTO and Orange for TIMER. The color is not the fault. The fault signal is the operation lamp blinking on its own, which the manual ties to an activated protection device, a thermistor fault or a transmission error.

The lamp also blinks twice to confirm a timer setting, and the TIMER lamp periodically lights orange once a weekly timer is set. FTX-N units pair a green operation lamp with an LED for timer (yellow); a blinking green lamp with the unit stopped is the cue to run Method 1. A blink while the unit keeps running is often normal on any brand, and why a mini split is blinking sorts defrost and power restore signals from real fault codes.

Communication faults are traced at the terminal blocks of the indoor and outdoor units.
Communication faults are traced at the terminal blocks of the indoor and outdoor units. AI illustration.

Does Daikin U4 mean a bad board, or a wire No. 3 problem?

U4 means valid data from the outdoor unit did not arrive, and a bad board is one of eight listed causes, alongside low supply voltage, a wiring error, a break in wire No. 3, a shorted fan motor winding and a distorted power waveform. Fujitsu calls the same kind of fault a serial communication error and shows it by counting OPERATION and TIMER lamp blinks, as the Fujitsu mini split error codes explain.

The safe owner step is to confirm the outdoor unit has power at its AC disconnect and breaker. The technician’s flowchart in SiUS041829EA checks supply voltage within ±10% of rated, then the voltage between terminals No. 1 and No. 3 and between No. 2 and No. 3, then whether LED A on the outdoor board blinks, after waiting at least 7 seconds from power on.

The global SM-TS3 list has a detail code column, and its how-to sheet gives wired controller steps for SkyAir and VRV. For a ducted mini split on a wired controller, read a hyphenated code against that model’s own manual.

Are Daikin U0 and F3 refrigerant faults you can fix?

No. U0 is “Refrigerant shortage” in the FTXR-T table, and F3 stops the compressor when the discharge pipe passes 230°F. Refrigerant shortage is also listed under E5 and EA, so a leak can show up as any of the four codes; finding it is the work in our refrigerant leak detection guide, not a homeowner top-off.

F3 clears itself once the discharge pipe falls below 190.4°F or 203°F depending on unit size, which is why the unit may restart and trip again. Listed causes also include the expansion valve, the four way valve and a closed stop valve.

Stop here for anything inside the outdoor unit. SiUS041829EA warns that its step-up capacitor supplies high voltage and “A charged capacitor may cause an electrical shock” until discharged.

Which searched Daikin codes do these manuals not define: A3, 34 and blinking 3 times?

A3 is the clearest gap: it sits in all three remote step lists, but neither US wall unit manual defines it. The global SM-TS3 list calls A3 “Drain Level Control System Abnormality”, citing drain clogging, a drain pump or a float switch.

No Daikin document we opened defines an “error code 34” or a three-blink pattern; Daikin’s lists use two-character codes such as A5. A different format may mean a different brand, covered on our Mitsubishi mini split error codes and MRCOOL mini split error codes pages.

A clogged filter can trigger protection codes that clear and return.
A clogged filter can trigger protection codes that clear and return. AI illustration.

Why does a Daikin code clear itself and then return, and when does the unit lock out?

Most outdoor codes retry on their own, and repeats shut the system down. The manuals print a reset condition for each: about 11 minutes of clean running for E6, E7, H6 and L5, and about 60 minutes for E5, EA, F3, H8 and L4.

Clean run time that resets the Daikin error counterMinutes of continuous running with no other error, per service manualE6, E7, H6, L5about 11 minE5, EA, F3, H8, L4about 60 minU2 restart wait3 min0 min15 min30 min45 min60 min
Reset conditions from Daikin SiUS041829EA and SiUS091601E; U2 restart wait is the 3-minute standby in the U2 page. Drawn by The HVAC Brief.

U2 is softer: the compressor restarts after a 3-minute standby, and the listed causes include noise and a momentary drop of voltage, events an AC surge protector is meant to absorb. After an outage, our AC not working after a power outage page covers restart checks.

Before re-powering, Daikin says to make sure the power has been off for at least 30 seconds. EA needs 5 minutes of running plus 10 minutes of a wrong coil reading, so a short test run cannot prove EA fixed; it judges the four way valve that a heat pump defrost cycle shifts on purpose.

Frequently asked questions

What does 00 mean on a Daikin remote?

00 means Normal. Both Daikin service manuals list 00 as Normal in the code table, and it is the first item the remote shows after you hold TIMER CANCEL for 5 seconds. Keep pressing until the indoor unit gives a long beep.

Can I clear a Daikin error code by turning off the breaker?

You can restart it, but the cause stays. Daikin flowcharts say to make sure the power has been off for at least 30 seconds before turning it back on, and repeated errors shut the system down until it runs about 11 or 60 minutes clean, depending on the code. Read the code with the remote first.

Does Daikin E6 mean a bad capacitor?

Not according to Daikin. The E6 compressor lock page lists a closed stop valve, a locked compressor and a disconnected compressor harness as causes. Among the causes on the FTXR-T code pages, the only capacitor named is the fan motor capacitor under A6, so an E6 diagnosis starts at the stop valve and harness.

Where is the full Daikin ac error code list?

Daikin Industries publishes an Error Code Search and the SM-TS3 list for RA, SkyAir, VRV, PA and heat reclaim ventilator equipment. It adds codes the wall unit manuals skip, such as UF, System is not set yet, with a closed stop valve among the causes.

How we researched this

In November 2026 we read the troubleshooting chapters of Daikin service manuals SiUS041829EA (06/2020, FTXR-T with RX09/12/18RMVJU9) and SiUS091601E (02/2016, FTX-N and FVXS-N), plus Daikin’s global SM-TS3 code list and its how-to-check sheet from daikin.com. We excluded contractor blogs and code-lookup sites as sources because they disagree with the manuals: one site tells owners to press MODE twice and blames E6 on a failed run capacitor that the E6 page never lists. The US manuals are third-party hosted copies. Other Daikin lines, ducted models and wired controllers were out of scope.

Sources

  1. Daikin. “Service Manual SiUS041829EA, Wall Mounted Type FTXR-T Series.” https://resource.ecmdi.com/is/content/Watscocom/Gemaire/daikin_rx-rmvju9_en_sm.pdf (distributor-hosted copy). Accessed November 2026.
  2. Daikin. “Service Manual SiUS091601E, Wall Mounted Type FTX-N Series, Floor Standing Type FVXS-N Series.” https://st.storeland.ru/11/2207/818/FTX_FVXS_series_Service_Manual.pdf (retailer-hosted copy). Accessed November 2026.
  3. Daikin Industries. “Simple Self-Diagnosis by Malfunction Code (SM-TS3).” https://www.daikin.com/-/media/Project/Daikin/daikin_com/products/ac/services/error_codes/pdf/sm-ts3_p1-6_errorcode-pdf.pdf?rev=-1&hash=EB9A47B35985182BC51091ECC254E40F. Accessed November 2026.
  4. Daikin Industries. “Self-Diagnosis by Remote Controller (SM-TS3, How to Check Error Codes).” https://www.daikin.com/-/media/Project/Daikin/daikin_com/products/ac/services/error_codes/pdf/sm-ts3_p7-8_howtocheck-pdf.pdf?rev=-1&hash=37B7BAB69F43DC0452FB8F32D7834A55. Accessed November 2026.
  5. Daikin Industries. “Error Codes.” https://www.daikin.com/products/ac/services/error_codes. Accessed November 2026.

Comments

4 responses to “Daikin Mini Split Error Codes: How to Read Them From the Remote, and What Each Means”

  1. […] remote and wait 3 minutes. If it starts and then flashes a code, look the code up by series on our Daikin mini split error codes table rather than resetting […]

  2. […] green searches belong to other brands: Daikin’s operation lamp is on our Daikin mini split error codes page, Fujitsu’s lamp counts on the Fujitsu mini split error codes […]

  3. […] The PUZ-M outdoor manual OCH773 prints both forms together: E6 beside 6840, E9 beside 6841, U1 beside 1302. Letter codes are brand-specific, so do not borrow meanings from our MRCOOL code tables or the Daikin mini split codes. […]

  4. […] read the code, hold Timer Cancel for 5 seconds until 00 shows; our Daikin error code page lists the presses for each […]